Pro1 Technologies Z260W Installation Manual Download Page 2

WIRING

Caution: 

Electrical Hazard

Failure to disconnect the power 

before beginning to install this 

product can cause electrical shock 

or equipment damage. 

UP

NC

C

NO

R
C

2

QUICK REFERENCE

Damper Module(s)

The Damper Module is designed to operate with 24VAC 

2-wire and 3-wire zone dampers.

The Damper Module(s) must be hardwired with 24VAC 

connected to R and C. 

The zone damper will be connected to the NC, C, and 

NO terminals on the left side of the subbase.

The Master Thermostat will transmit the required 

damper position to the Damper Modules. 

When the damper position is open, the ZONE 

LED will be flashing. 24VAC will be supplied to 

NC and C terminals.

When the damper position is closed, the 

ZONE LED will be solid. 24VAC will be 

supplied to NO and C terminals.

Wire the terminals according to 

the damper type used.

(See page 3 for instructions)

Normally-Closed, Power-Open

Normally-Open, Power-Close

Power-Open/ Power-Close

Damper Type 

Terminals

NC & C

NO & C

NC, C, & NO

  To link damper module(s) to a desired zone, see page 4 for establishing communication.

NOTE:

NOTE:

 

Static/ Barometirc Bypass damper is recommended on all systems for safe and efficient zoning. 

This system does not control bypass dampers.