Pro1 Technologies T731W Installation Manual Download Page 3

Wiring

7

Wiring

8

Wiring

Technician Setup

11

12

Cooling 

Swing

Tech Setup Steps 

Adjustment Options

Default

LCD Will Show

Room

Temperature 

Calibration

This feature allows the installer to 

change the calibration of the am-

bient room temperature display. 

For example, if the thermostat 

reads 70 degrees and you would 

like it to read 72 then 2.

0˚F

4 ˚ -  -4 ˚  

Base Module - PTAC Installation

Side Mount:

Inside PTAC 

Housing

Front Mount:

Inside PTAC 

Housing

Range between the thermostat and the base module is up to 100 feet 

with no obstructions and up to 50 feet through standard building 

materials. To optimize the range try placing the base module with no 

metal between it and the thermostat.

The base module is designed to be mounted behind the front grille 

of a packaged terminal air conditioner (PTAC).  Refer to the PTAC 

manufacturer’s manual for instruction to remove the front grille. 

Check clearance to ensure the fit of front grille after base module 

installation. See below for a few location recommendations. 

When Working With A Vertical Unit

1. Do not mount Module inside the cabinet of the unit, or in a 

    metal enclosure.

2. Mount on the outside of the unit to maximize wireless 

    communication.

When Working With A Metal Sleeve Cabinet, Room Cabinet, 

or PTAC Cover

1. If cabinet has open bottom, mount the module just inside the 

cabinet as close to the open bottom as possible without placing it in 

danger of being bumped or touched by furnishings, vaccum, etc.

2. Another good module location would be on the underside of the 

top of the cabinet or cover.  Directly behind the open Louver/Grill.

Typical 1H/1C System: 1 Speed Fan

R

Y

W

C

GL
GH

HEAT RELAY

FAN RELAY

COMPRESSOR

RELAY

Typical 1H/1C Heat Pump System: 2 Speed Fan

R

Y

W

C

GL
GH

O/B

COMPRESSOR

RELAY

CHANGE OVER

VALVE

FAN LOW RELAY

FAN HIGH RELAY

C

R

L2
L1

C

R

L2
L1

Typical 2H/1C Heat Pump System: 2 Speed Fan

C

R

L2
L1

COMPRESSOR

RELAY

AUX HEAT 

RELAY

FAN LOW RELAY

FAN HIGH RELAY

CHANGE OVER

VALVE

CALIBRATE

The swing setting, often called 

“cycle rate”, “differential” or “antic-

ipation” is adjustable and dictates 

how frequenlty the system cycles 

on and off. For example: A swing 

setting of 0.8˚ will turn the 

heating on at approximately 0.8˚ 

below the setpoint and turn the 

heating off at approximately 0.5˚  

above the setpoint.

1.  Set the thermostat system switch to 

OFF

.

2.  To enter Tech Setup Menu, press and hold            and            together for 3 seconds.

3.  Use             or             to select desired setting for each option.

4. Tap            and             together to move next option.

5. To exit Tech Setup Menu, move system switch or wait 15 seconds.

Front Panel

Chasis

Sleeve Cabinet

Rough-In

 

Wall Opening

COOL CHANGE 

OVER VALVE

HEAT CHANGE 

OVER VALVE

O
B

COOL CHANGE 

OVER VALVE

HEAT CHANGE 

OVER VALVE

O
B

The swing setting, often called 

“cycle rate”, “differential” or “antic-

ipation” is adjustable and dictates 

how frequenlty the system cycles 

on and off. For example: A swing 

setting of 0.8˚ will turn the 

cooling on at approximately 0.8˚  

above the setpoint and turn the 

cooling off at approximately 0.8˚  

below the setpoint.

0.2 ˚ -  2 ˚  

0.8˚

Heating 

Swing

0.2 ˚ -  2 ˚  

0.8˚

0.8

COOL SWING

0.8

HEAT SWING

1.  Tech settings must be transferred to the basemodule.

2.  The transfer happens automatically when you exit the tech menu.

3.  The Screen will display “TEC SET OK” when the basemodule has received the  

new tech settings.

Important Tech Setting Notes