- 6 -
•
Pin #14 DC+5V Output is not protected. To prevent damage or unit malfunc-
tion, use only the designated level of current.
•
Be sure to connect line #7 (SG) to the SG terminal of your Host (Device/PLC).
Dsub 25 pin socket-type connector (connect the HOST)
Recommended Connector: Dsub 25 pin plug XM2A-2501<made by OMRON Corp.>
Recommended Cover: Dsub 25 pin Cover XM2S-2511<made by OMRON Corp.>
Recommended Screw: Jack Screw XM2Z-0071<made by OMRON Corp.>
Pin No. Signal Name
Description
1
FG
Frame Ground
2
SD
Send Data
3
RD
Receive Data
4
RS
Request to Send
5
CS
Clear to Send
7
SG
Signal Ground
8
CD
Carrier Detect
14
+5V
DC +5V±5% Output 0.25A
*1
20
ER
Enable to Receive
*1
When connected to the GP, the power used should be a maximum of 0.25A. Be sure to not exceed
this level.
Recommended Connector: Dsub 37 pin plug XM2A-3701<made by OMRON Corp.>
Recommended Cover: Dsub 37 pin Cover XM2S-3711<made by OMRON Corp.>
Recommended Screw: Jack Screw XM2Z-0071<made by OMRON Corp.>
•
Pin #6 DC+5V Output is not protected. To prevent damage or unit malfunc-
tion, use only the designated level of current.
•
Be sure to connect line #25 (SG) to the SG terminal of your Host (Device/PLC).
*3
The DOUT ground is used in common with External Buzzer Output (BUZZ OUT), DOUT 0 (Zero)
output (DOUT0.C), and DOUT 1 (One) output (DOUT1.C).
*4
Disabled when “GP-H70 compatible mode” (set via GP2000H) is used.