10/44
2.2 Touch Panel specifications
GP-4301T/GP-4301TW adopts the Analog type.GP-4301Tand GP-4301TW doesn’t
support 2-point touch input (touching 2 points on the screen at the same time).
If you have used the 2-point touch input on GP-377R/377T/377L, change to the
1-point touch input setting using the switch delay function of GP-Pro EX.
When you use 2-point touch input ,there’s a difference between the GP-4301T and
GP-4301TW as below,
GP-4301T
Analog type
Even if you touch two points at the same
time, only the first touched point is
recognized, but the second touched one is
not.
GP-4301TW
Analog type
Even if two different points are touched
at the same time, that’s recognized as
touch input on the middle coordinates
between those two points.
2.3 Display Colors (Only GP-377L)
The display color of GP-477RE is monochrome, but GP-4501T/TW has a TFT color LCD.
After replacement, the display color changes from monochrome to color.
When data of a monochrome model is converted to data of a color model with GP-Pro
EX, the data may be displayed in colors depending on the version of the Project
Converter or settings of the drawing/the parts on the screen.After conversion, please
confirm the display colors of the drawing or the parts on the screens just in case.
If the display is in colors after the data conversion to GP-4301TW…
GP-Pro EX Ver. 3.01.200 (Service Pack1) or later supports the function which
changes drawing in colors to in monochrome. To change the setting, follow the steps
below.
(1)
Click [Project]->[System Settings]->[Display Unit].
(2)
Open the [Display Settings] tab.
(3)
Change [Color] setting to “16 Levels Monochrome, 3-Speed Blink”.
(4)
Select [Yellow/Black].
* [Reverse Display] setting is for displaying the screen with black/white reversed.
Check on it if needed.