2.7 Peripheral units and option units
2.7.1 Barcode reader connection
Like GP/ST-3500 series, GP-4500 series allows you to connect a barcode reader to
its USB interface (Type A) or its serial interface.
For the models GP-4500 series supports, see [OtasukePro!]
(
http://www.pro-face.com/otasuke/qa/3000/0056_connect_e.html
).
2.7.2 Printer connection
Like GP/ST-3500 series, GP-4500 series allows you to connect a printer on its USB
interface (Type A).
For the models GP-4500 series supports, see [OtasukePro!]
(
http://www.pro-face.com/otasuke/qa/3000/0056_connect_e.html
).
2.7.3 Expansion Unit (for GP-3500 series only)
GP-4500 series is not equipped with an expansion unit interface. The expansion
unit (each kind of unit like CC-LINK Unit) for GP-3500 series cannot be used.
2.7.4 Isolation Unit
RS-485 isolation unit for GP/ST-3500 series (CA3-ISO485-01) cannot be used for
GP-4500 series. You can use the RS-232C isolation unit (CA3-ISO232-01) for
GP-4500 series instead.
Note for using RS-232C isolation unit (CA3-ISO232-01)
・
Connect it to GP-4500 series via COM1 (232C). COM2 cannot be used.
・
It’s necessary to set the 9
th
pin of the COM port to VCC.
[Settings on GP-ProEX]
Select “VCC” from [System Settings] -> [Device/PLC] in the [Project] menu
on GP-Pro EX.
・
RS-422/485 (2-wire type) communication and serial multilink are not
supported.