background image

2

Please read these instructions carefully before starting installation and retain for 

future reference. The centre page test record can be removed and kept with the 

building fire safety records.
IMPORTANT SAFETY INFORMATION

NOTE: Before drilling any holes, check that there are no hidden obstructions behind the 

mounting surface such as pipes or cables. 

1.  Prize off the legend diffuser by inserting a flat blade screwdriver into the slot on the 

end of the unit and turning it. Disconnect the wiring plugs from the PCB noting their 

position and remove the front panel.

2.  Using the back of the product as a template, mark the position of the fixing holes on 

your mounting surface.

3.  Drill the fixing holes and fit wall plugs as appropriate and secure the back of the 

product to the mounting surface using suitable fixings (not supplied).

4.  Cable access points are provided in either end of the rear panel. Cut out the 

required cable access from one matching position on the front panel as required. 

5.  Secure the cable with the cable grip.

6.  Make connection to the supply using the terminal block provided. Ensure that the 

correct polarities are observed i.e.:

●  Brown – Live terminal ‘L’

●  Blue  – Neutral terminal ‘N’.

●  Link wire ‘L’ to ‘L1’ can be removed to change between maintained and non-

maintained.

7.  Write the current date on the battery pack in the space provided.

8.  Reconnect the wiring plugs previously disconnected and also connect the battery to 

the socket on the PCB marked ‘BATTERY’.

9.  Refit the diffuser making sure that it is securely clipped in place.

10.  Turn on the power supply. The green LED should light to indicate that the battery is 

charging.

11.  In maintained mode, the lamp will illuminate.

12.  Perform the electrical tests specified in the Wiring Regulations (BS7671).

INSTALLATION

RISK OF ELECTRICAL SHOCK. ALWAYS ISOLATE THE POWER AT THE MAINS 

BEFORE INSTALLING OR MAINTAINING THIS EMERGENCY LIGHT.

• 

This product must be installed by a competent person in accordance with the 

Building Regulations and the current edition of the IET Wiring Regulations 

(BS7671).

• 

This product is suitable for mounting on normally flammable surfaces such as 

wood, plasterboard or masonry.

• 

Emergency light fittings should have their own separate mains circuit, protected 

with an appropriate MCB or fuse. They should not share their supply with other 

lighting or electrical equipment.

• 

This product is suitable for connection to a 220-240V~ 50Hz.

• 

This product is for indoor use only. 

• 

Ensure that after installation the equipment remains accessible for regular 

maintenance and testing.

Reviews: