Working in the vicinity of a lead-acid battery is dangerous. Batteries generate explosive gases
during
normal operation. For this reason, it is of the utmost importance that prior to each use of your
charger, you read and follow
the instructions provided exactly.
Il est dangereux de travailler a proximité d’une batterie au plomb. Les batteries produisent des gaz explosifs en service normal. Il est
aussi important de toujours relire les instructions avant d’utiliser le chargeur et de les suivre à la lettre.
Suitable for servicing only when de-energized.
Peut faire l
’objet d’un entretien uniquement s’ll est hors tension.
Do Not Expose to Rain.
NE PAS EXPOSER A LA PLUIE.
Model i4875OB480 only.
Connection to AC Mains
This model, designed for use with 480 VAC 60 Hertz, 3 Phase Delta, is provided with an AC power cord - 4xAWG14, 3 Mains +
Ground. The green conductor (Earth Ground) is connected directly to the chassis internally. To connect the charger to AC mains,
conductors rated 600V 14 AWG 90 DEG C or higher must be used. Installation must be performed by a certified licensed professional
electrician.
For i4875OB480 units supplied with optional AC Plug (NEMA L16-20)
If already equipped with NEMA L16-20P from the manufacturer, only plug in to a
grounded
L16-20 receptacle connected to 480V 60
Hertz Delta Mains. Consult a certified licensed professional electrician
.
Do nor use with High-Leg Delta Mains supply, this may result in damage to the charger and/or electric
shock. Consult a certified licensed professional electrician.
AC Fuse Replacement
Only replace AC input fuses (3 locations located on rear of the unit) with rating of 10A 600V.
CHARGING INDICATIONS
When your battery charging system is activated, the battery status indicator provides charging information utilizing three red LED
indicators and one green LED indicator.
Battery Type Indicators
Two amber LED indicators are provided to display what type of battery the charger has
been programmed to charge. NOTE: For information on reconfiguring the battery type,
please contact technical support (615.471.5300)
Battery System Percent Charged Indicators
Four LED indicators are provided to display the progress of the charge cycle in percentage
of charge. Indicators are as follows:
1
ST
Amber LED . . . . . . . . . . . Illuminated configured for Wet Cell and
AGM*
batteries
2
ND
Amber LED . . . . . . . . . . . . . Illuminated configured for Gel Cell batteries
1
ST
RED LED . . . . . . . . . . . . . Charging - Initial Charging Up To 30%
2
ND
& 3
RD
RED LEDS . . . . . . . Charging - 60% Complete
1
ST
, 2
ND
& 3
RD
RED LEDS. . . . Charging - 90% Complete
BLINKING GREEN LED . . . . Finishing Stage (Note: Battery Type Indicator will also blink during this stage)
STEADY GREEN LED . . . . . . Charge Complete
–Float/Maintenance Mode-On for 5 minutes and off for 60 minutes
*We normally recommend our STANDARD Delta Volt profile for AGM Batteries. Always consult with your AGM battery
manufacturer first regarding charging instructions. There are some cases where certain AGM batteries are manufactured
to different specifications and may need a special profile with a much lower finish voltage limitation. In this case, we will
do our best to accommodate your unique need.