TROUBLE SHOOTING (TK-HC, TK-C)

Trouble shooting Therma-Fuser diffusers requires looking at 

the system as a whole. Before examining the Therma-Fuser 

diffuser for failure it is worth the time to be sure the system 

is functioning properly and that something has not been 

overlooked. Before calling Acutherm, please complete the 

data log for all Therma-Fuser diffusers to be evaluated.

SYSTEM CHECK LIST

The system should be:
1. Delivering 50°- 68°F/10° - 20°C supply air when in the

cooling mode.

2. Delivering 80°-120°F/26.5° – 49°C supply air when in

the heating mode.

3. Maintaining static pressure at the inlet to each Therma-

Fuser diffuser between .05” and .25”wg/12 Pa and 62 Pa.

4. Maintaining continuous fan operation during occupied

hours.

THERMA-FUSER DIFFUSER CHECK LIST

Once the above checks have been completed, examine 

and record the following (temperature may vary over time; 

several measurements at different times may be required):
1. Room temperature 4 feet above the floor directly under

the Therma-Fuser diffuser.

2. Supply air temperature at the Therma-Fuser diffuser.
3. Static pressure at the inlet of the Therma-Fuser diffuser.

Thermostats

Read setpoints here

Measure from induction housing 

to edge of slider.

Cooling mode < 7/8 in / 22 mm

Heating mode > 1 in / 25 mm

TROUBLE SHOOTING DATA LOG

Time

Date

Location

Set Points

Heating Cooling

Damper 

Opening 

Cam 

Position

Room 

Temp

S.A. 

Temp

Duct  

S.P. 

Blade 

Opening

T-stat 

Slider

4. Blade opening from the edge of the blade, measured

perpendicular to the housing.

5. Thermostat slider position.

6. Cooling and heating setpoints.
7. Damper opening cam—positioned for blades fully

closed, partially open or fully open.

8. Is the Therma-Fuser diffuser located within

2ft/600mm of a vertical protrusion such as a wall

or dropped beam which could disturb induction air

flow?

Foam

Housing

Blade

Small Steel Rule

TK-HC THERMA-FUSER diffuser 

APPEARANCE PANEL REMOVED

Summary of Contents for Acutherm THERMA-FUSER SYSTEMS

Page 1: ... 5 Ten Year Warranty 6 4 If other than 4 way blow pattern is factory installed note the AIRFLOW markings on the top of the diffuser and locate those sides in the proper direction 5 Install in ceiling grid Install T bar support wire close to each corner of diffuser Make sure that only wire suspended T bars are used to support diffuser weight Adaptor frames are available for other ceilings 6 Connect...

Page 2: ... sensor for static pressure controller Measure supply return and branch duct air flow 4 Place a direct reading diffuser balancing hood over the face of each Therma Fuser diffuser and adjust damper at duct takeoff to obtain maximum design air volume If a velocity meter is used measure discharge velocity at the housing See Fig 3 Multiply the velocity in fpm times Ak of 12 ft2 to get air flow in cfm ...

Page 3: ...en the housing and the diffusion plate blade assembly and wedge between the standoffs See Fig 7 Take care to clear the damper hinges so that the damper operates freely The rule for blocking the appropriate side is Always block the side adjacent to the thermost See Fig 8 for examples When blocking for direction reduce maximum air volume for a given static pressure and throw in the performance guide...

Page 4: ... temperature limit should be as low as possible These objectives are best achieved by modulating chilled water valves hot water valves and other variable equipment from supply air temperature On off equipment such as DX compressors and electric heat are cycled from supply air temperature Use a discharge air sensor for the supply air temperature signal Mode change between heating recirculation and ...

Page 5: ... temperature may vary over time several measurements at different times may be required 1 Room temperature 4 feet above the floor directly under the Therma Fuser diffuser 2 Supply air temperature at the Therma Fuser diffuser 3 Static pressure at the inlet of the Therma Fuser diffuser Thermostats Read setpoints here Measure from induction housing to edge of slider Cooling mode 7 8 in 22 mm Heating ...

Page 6: ...and found defective and provided the diffusers have been given normal and proper usage and all parts and controls remain unaltered Acutherm makes NO WARRANTY OF MERCHANTABILITY OF PRODUCTS OR OF THEIR FITNESS FOR ANY PURPOSE OR ANY OTHER EXPRESS OR IMPLIED WARRANTY WHICH EXTENDS BEYOND THE LIMITED WARRANTY ABOVE ACUTHERM S LIABILITY FOR ANY AND ALL LOSSES AND DAMAGES RESULTING FROM DEFECTS SHALL I...

Reviews: