                                                                                                          Page 3 of 12 

Outputs:

 

 
The RCI-200 has two form ‘C’ relay contact outputs and two 0-20mA analog outputs. 
The relay contacts are capable of switching 120VAC, 10A or 240VAC, 6A.  An energy 
absorbing varistor is installed across each contact to limit switching transients.  A 
third relay contact acts as a communications fail indicator.  If no communication 
occurred within 30 seconds, this relay contact will energize. Upon re-established 

communication this relay will de-energize again. 
 
The two analog outputs are typically configured as 0-20mA outputs and can drive into 
a 1000

 load each, provided that the power supply to the unit is not below 24VDC.  

The outputs are not isolated from each other or from the inputs.  Care must be taken 
when connecting the outputs to different devices so that no inadvertent ground loops 
are established. 
 
 
 

 

Output Calibration & Input Testing: 

 

The outputs on the RCI-200 are factory calibrated and should not require any adjustments.

  To 

check the calibration of the outputs and relays use jumpers H1-7 & H1-8 as shown below to set them to 
known states.  If an output should require some adjustment, insert 
jumper H1-8 only and turn the OUTPUT CALIB. trim pot until the output 
reads 20mA. 
 
 
 
 
 
 
If both jumpers are IN the analog and contact inputs are passed straight through to the analog and 
relay outputs.  This may help in troubleshooting input and output signals. 
 

Make sure both jumpers are removed before resuming normal operation. 

 
 

H1-7 

H1-8 

Function 

OUT OUT Normal 

Operation 

OUT IN Outputs=20mA, 

Relays=Energized 

IN OUT 

Outputs=0mA, 

Relays=De-energized 

IN IN 

Outputs=Inputs, 

Relays=Contact 

Inputs 

Summary of Contents for RCI-200 series

Page 1: ...00 XXX If special or required 24 VDC 2 Dry Contacts and 2 Analog Inputs Input Remote Control Signal Interface XXX SER RS 232 485 Output 2 Form C Contacts and 2 Analog Outputs 117VAC 50 60Hz XXX RF9 90...

Page 2: ...ducts or all non standard products may not be returned for restocking Pribusin Inc warrants equipment of its own manufacture to be free from defects in material and workmanship under normal conditions...

Page 3: ...cks make for easy installation When connecting units on a PBX system make sure it can accept analog modem transmissions Serial systems connect via standard modem cable Standard Features Bi directional...

Page 4: ...ter 232 485COM RS 232 RS 485 up to 128 devices RS 485 Bus R S 232 System A System B System C Additional Signal Booster s required for 32 devices see SPB 485 Manufactured By 11 25 9 25 4 5 www pribusin...

Page 5: ......

Page 6: ......

Page 7: ......

Page 8: ...0mA SLOBLO fuse It can be wired for 240VAC operation by removing de soldering power jumpers J1 J2 and installing soldering jumper J3 When changing the RCI 200 to 240VAC power make sure to change the f...

Page 9: ...ts are connected to the RCI 200 in two fashions 1 Normal 3 wire connection or 2 two wire connection On a 3 wire connected input an external power supply or the 24V power output terminal of the RCI pro...

Page 10: ...om the inputs Care must be taken when connecting the outputs to different devices so that no inadvertent ground loops are established Output Calibration Input Testing The outputs on the RCI 200 are fa...

Page 11: ...nications failure occurs If H1 3 IN then analog output 1 will ramp to the setting of K1 and analog output 2 will ramp to the setting of K2 Both outputs will change at a rate determined by the setting...

Page 12: ...ddress 1 2 3 etc so that the host may distinguish between them There may at most be as many remotes as there are inputs outputs on the host For example an RCI 200 system having two analog contact inpu...

Page 13: ...perate as a host unit make sure that SW2 8 is flipped down Next set the number of remotes that the host is to communicate with using SW1 1 2 3 These switches are binary encoded as shown in the chart t...

Page 14: ...e to convert the remote address to binary first SW1 1 SW1 2 SW1 3 Remote Address UP UP UP 1 DOWN UP UP 2 UP DOWN UP 3 DOWN DOWN UP 4 UP UP DOWN 5 DOWN UP DOWN 6 UP DOWN DOWN 7 DOWN DOWN DOWN 8 Next se...

Page 15: ...2 Next set the number of channels on this remote using SW2 1 2 One channel is considered 1 analog input output plus 1 contact input output Hence an RCI 200 can have at most 1 channel SW2 1 SW2 2 Chann...

Page 16: ...sters listed in the table below are the only ones implemented on all RCI products at this time Description Function RCI 100 XXX RCI 200 XXX RCI 400 XXX RCI 800 XXX Read Relay Status 01 00001 00001 000...

Page 17: ...2 Number of Remotes 1 Address 1 Channels on Remotes 2 Example 3 An RCI 400 Host communicating with an RCI 400 Remote RCI 400 Host RCI 400 Remote Host Channels 4 Remote Channels 4 Number of Remotes 1 A...

Page 18: ...ample 4 An RCI 800 Host communicating with 3 RCI 200 Remotes RCI 200 Host RCI 100 Remote 1 RCI 100 Remote 2 Host Channels 2 Number of Remotes 2 Channels on Remotes 1 Remote Channels 1 Address 1 Remote...

Page 19: ...Page 12 of 12 RCI 800 Host Host Channels 8 Number of Remotes 3 Channels on Remotes 2 RCI 200 Remote 1 RCI 200 Remote 2 RCI 200 Remote 3 Remote Channels 2 Address 1 Remote Channels 2 Address 2 Remote...

Reviews: