Premium PFV306MS Service Manual Download Page 18

Maintenance Service and Trouble Shooting   

Analysis of Trouble 

 

Low efficiency of a refrigerating compressor refers to the actual 

 

reduction of gas discharge capacity ,and hence the corresponding 

 

reduction of refrigerating capacity ,under the condition that the refrigerant in 

 

the system is unchanged .This phenomenon occurs mostly when the 

 

compressor has been used for quite a long time ,its moving parts have 

 

worn to a considerable degree ,fit clearance between various parts have 

 

increased and sealing property of its gas valve has deteriorated ,resulting 

 

in an decrease in its actual gas discharge capacity . 

 

Methods of Judgment 

 

Measure the high and low pressures with pressure gauges to see 

 

whether they are normal .If an abnormal sound comes from the compressor 

 

or the temperature of its causing is too high ,Cut the discharge port open 

 

and operate the compressor ,feel it if there is pressure at the discharge port 

 

with your finger (For a normal compressor ,its discharge port is difficult to 

 

be blocked with your finger if you just apply a little effort). 

 

5)      Too thick frost layer formed on evaporator 

 

Analysis of Trouble 

 

If a direct cooling refrigerator is to be used for a prolonged period of 

 

time ,be sure to defrost its evaporator regularly ;if you fail to do so ,the frost 

 

layer on the evaporator tubing will become thicker and thicker .Heat 

 

conduction will be severely affected when the whole tubing is wrapped with 

 

a transparent ice layer ,and finally the temperature in the refrigerator 

 

cannot drop down to the prescribed range . 

 

Remedy 

 

Turn the refrigerator off , and make preparations for defrosting ,open the 

 

refrigerator door to let the air come in ,or use a fan to speed up air flowing 

 

so as to shorten the time needed for defrosting .Never strike the frost layer 

 

with any iron tools or wood stick in order to avoid damage to the evaporator 

 

tubing . 

 

6)      Refrigerating oil left in evaporator tubing 

 

Analysis of Trouble 

 

During the process of refrigerating cycles , a little refrigerating oil may 

 

remain in the evaporator tubing ,and after a longer time of operation ,if 

 

there is considerable refrigerating oil left in the evaporator ,the heat 

 

conduction effect will be severely affected ,thus causing a poor refrigerating 

 

effect . 

 

Remedy 

 

It is quite difficult to determine whether this trouble is caused by the 

 

refrigerating oil left in the evaporator tubing ,because this kind of 

 

phenomenon and other several trouble are tends to be confused .Generally 

 

speaking ,you can make a judgment based on the frost formed on the 

 

evaporator .If the frost does not cover the evaporator , and moreover ,it is 

 

loosely formed ,you can make a judgment that the deterioration of 

 

                         

 

                          

Summary of Contents for PFV306MS

Page 1: ...Service Manual Model PFV306MS...

Page 2: ...bs Unit Dimension W D H In In Packing Dimension W D H Container Quantity 40 HQ PCS 63 88 Net Weight Lbs 0 65 Power Consumption kW h 24h 80 Rated Input Power W 115 60 Power Supply V Hz White Color 85 P...

Page 3: ...Safety precautions Safety precautions 115V 60Hz AC...

Page 4: ...Safety precautions...

Page 5: ...Safety precautions...

Page 6: ...Function Schedule Energy efficiency Micro foam technology Low noise operation Thick insulation for energy efficiency Function Schedule...

Page 7: ...Chart Model HS 111F is a direct cooling single system refrigerator When the refrigerator is just powered on the refrigerant flows in the sequence 1 2 3 4 5 1 System Flow Chart System Flow Chart 1 Sche...

Page 8: ...Description of Control Principle Model HS 111F is a direct cooling single system refrigerator with a small ice box a mechanical type of all the control is generally adopted The thermostat directly con...

Page 9: ...r charge refrigerant again NO If compressor can run naturally and temperature raising of condenser is very low YES YES Check and repair according to the section of the compessor doesn t work NO If com...

Page 10: ...r by heat resource 3 The door was opened too many times or there are more fresh food inside YES Check and repair according to the section of Cooling capacity is insuffcient NO Is cooling capacity insu...

Page 11: ...how to use Does the refrigerant leak siowly NO YES Check the therostat is correct Is the ambient YES temperature low than 16 C Maintenance Service and Trouble Shooting 3 Cooling capacity is insufficie...

Page 12: ...control panel has 220V power output Adjust and instruct consumer how to use Check the therostat is correct YES 16 Is the ambient temperature low than YES YES Repair NO Check the power source and power...

Page 13: ...bles of refrigerators and their remedies we should firstly give a brief account of some normal phenomena which are not troubles In case any one of such phenomena occurs there is no need to worry about...

Page 14: ...stat is the highest In troubleshooting the first thing you must do is to determine where the trouble comes from the control system or the refrigerating system There is general no trouble indicating in...

Page 15: ...ed by a sound similar to water flowing this is the sound produced by the normal circulation of refrigerant within the evaporator In case only the gas flowing sound can be heard and there is no water f...

Page 16: ...ly due to a certain trouble With this method you can reject some suspicious troubles and finally make a correct judgment 7 Analysis of Troubles and Troubleshooting A Poor Refrigerating Effect The so c...

Page 17: ...xcessive refrigerant has been charged the liquid refrigerant that cannot evaporates in the evaporator will return to the compressor and thus a phenomenon of liquid striking will occur The liquid refri...

Page 18: ...orator regularly if you fail to do so the frost layer on the evaporator tubing will become thicker and thicker Heat conduction will be severely affected when the whole tubing is wrapped with a transpa...

Page 19: ...erant and seal the charging port B No Refrigerating The phenomenon that the compressor runs normally but no frost or only a little frost appears on the evaporator and the refrigerator temperature does...

Page 20: ...at these phenomena will appear intermittently sometimes the refrigerator works well and sometimes not well In order to determine whether it is clogged with ice heat the suspicious points with hot wate...

Page 21: ...logging with dirt 3 Troubles of Compressor a Breakage of gas suction and discharge valve blocks Analysis of Trouble The compressor works by means of the opening and closing of gas suction valve and di...

Page 22: ...the system Analysis of Trouble The residual air in the system will circulate together with the refrigerant in the system The major symptoms caused by this residual air is higher gas discharge pressure...

Page 23: ...ower supply c Abnormal thermal protection Analysis of Trouble The compressor current is within its normal range but the thermal protector actuates repeatedly Remedy Replace the thermal protector with...

Page 24: ...the user for buying a stabilizer so as to step up the voltage thus normal operation can be achieved 3 Check the thermal relay to see whether its contacts are closed Analysis of Trouble The contacts of...

Page 25: ...s caused mostly by poor lubrication such ad insufficient quantity of lubricant clogging in the lubricant oil line or intermittent lubricant oil supply Dirt and other impurities in the lubricant oil wi...

Page 26: ...s rated value the thermostat won t work thus the compressor runs continuously When the evaporation temperature in the system is too high the temperature sensing agent in the temperature sensor is also...

Page 27: ...t up intensively measure the resistance between the power cord plug and the case body with an avometer the reading will be zero 0 in the worst case the fuse will be blown Check the 3 prong outlet to s...

Page 28: ...ation becomes weake or vanishes If the refrigerator has not been levelly placed put a level meter on its top table and adjust the leveling screws on its legs In case noise occurs from the compressor s...

Page 29: ......

Reviews: