background image

General

1.  These guidance notes refer only to the installation of 

Concrete surround CNSB Bypass Separators.

2.  Manufactured to BS EN 858 Class 1 and Class 2.

3.  These guidance notes cannot provide specifi c, site-

related installation instructions.

4.  If in any doubt whatsoever about any aspect of the 

installation please contact Conder Aqua Solutions on 
0870 264 0004.

Pre-Installation Inspection

1.  The fi lter pod in these tanks is held in place during 

transportation by means of a Transit Brace. This is to 
hold the fi lter pod in place during transportation and 
ensure the separator is delivered to site in the same 
A1 condition as it left our manufacturing facility. THIS 
MUST BE REMOVED PRIOR TO INSTALLATION. Failure 
to remove the brace may prevent access to the pod for 
maintenance and WILL RENDER THE WARRANTY ON 
THE TANK INVALID.

2.  The timber transit brace consists of a vertical brace 

holding the fi lter pod in place and a horizontal restraining 
bar. To remove the brace, unscrew the horizontal 
restraining bar and remove both pieces of timber.

3.  Tanks should be subject to a visual inspection prior to 

installation

4.  Check the tank is the correct size and duty, see label on 

tank

5.  Any damage should be notifi ed to the delivery driver and 

to Conder Aqua Solutions on 0870 264 0004.

6.  Do not attempt to carry out any unauthorised repairs, as 

this will invalidate the warranty on the tank.

7.  Check for:
 

- Fractures to the shell or ribs

 

- Delaminations

 

- Scratches or abrasions deeper than 1.5mm

 

- Stress cracks or star crazing

8.  Check invert depth is correct and inlet and outlet pipe 

orientations are correct

9.  REMOVE TANK FROM PALLET

Service Specifi cation

1.  These tanks are designed to be installed below ground 

and completely surrounded with concrete. 

2.  Generally, the depth from fi nished ground level to the 

top crown of the main shell should be no more than 2 
metres, this may vary dependent upon ground water 
conditions. Deeper inverts may be accommodated on a 
standard shell providing the water table level does not 
exceed 2 metres above the top crown of the main shell. 
For deeper burial with high water table conditions heavy 
duty shells are available. Should you be in any doubt 
regarding suitable shell application please call our sales 
number 0870 2640004. If the tank is installed outside 
these parameters it may suffer irreparable damage.

Concrete Specifi cation

1.  The specifi cation for the concrete mix to surround the 

tank may be taken from BS 5328: Part 1: 1991 (including 
amendments), taking into account the site conditions and 
application requirements.  

2.   For a typical non-structural application in non-

aggressive soils a Standard Mix ST4 with a 50mm slump 
is generally suitable, but also permits the equivalent 
Designated Mix GEN3 to be specifi ed as an alternative.  
If for non-typical applications, structural or other reasons 
a higher than normal designation is required, the 
purchaser of the fresh concrete can use table 6 in BS 
5328: Part 2: 1991 (amendment 8759/October 1995) for 
guidance.

Lift height (Rate of Rise)

1.  Determine the lift height (m), or rate of rise (m/h) for 

the specifi c concrete type used, to ensure that a 
design pressure (P max) of 15kN/m2 on the tank is not 
exceeded.

Vibration

1.  The design of the tank assumes minimal compaction of 

the surrounding concrete.   Where necessary, this may 
be extended to include light internal vibration.   Never 
use deep revibration which will substantially increase the 
pressure on the tank, possibly causing failure.

Conder CNSB Bypass Separator: Concrete Surround

Conder Installation Guidelines  

 Ref: UTG9503