Prella PLH-24V Installation Wiring Diagram Download Page 2

warm air at a temperature of between 65

°

C and 80

°

C.

(This requirement can be met by some domestic hair

dryers).

Proceed as follows:

(1). Switch on the warm airflow and check that

temperature is correct and stable.

(2). From a distance of several inches, direct the

airflow at the guard protecting the thermistor. The

detector should alarm within 30 seconds.

(3). Upon alarm immediately remove the heat source

and check that the red LED of the detector is

illuminated. Reset the detector from the control

panel.

(4). If detector fails to go into alarm mode within 30

seconds it is too insensitive and needs to be

returned to the distributor for servicing.

(5). After testing, check that the system is set for

normal operation and notify the appropriate

authorities that the testing operation is complete

and the system is active again.

CAUTIONS

This heat detector is particularly designed to

initiate and

activate

emergency action, but will do so only when it is

used in conjunction with an authorized fire alarm system.

This detector must be installed in accordance with NFPA

Standard 72. 

The purpose of design of heat detectors is meant to

protect property, not life.

 The heat detectors do not provide

early warning of fire and cannot detect smoke, gas,

combustion particles, or flame. They will alarm when

temperature at the heat detector reach 57

o

C (135

o

F) or

above. Given the rapid growth of certain types of fires, heat

detectors cannot be expected to provide adequate warning

of fires resulting from smoking in bed, inadequate fire

protection practices, violent explosions, escaping gas, and

improper storage of flammable liquids like cleaning solvents,

other safety hazards, or arson. 

Heat detectors do not always detect fires because the

fire may be a slow-smoldering, low-heat type (producing

smoke), or because they may not be mean where the fire

occurs, or because the heat of the fire may bypass them.

Heat detectors will not detect smoke, gas, flames, or

combustion particles.

Heat detectors are components in professionally installed fire

alarm systems.

They will not function if they have been

improperly wired into the fire alarm system or if power to

them is disconnected for any reason. 

Heat detectors cannon last forever.

They should be tested

and maintained following the instructions in this manual. To

be safe, they should be replaced after they have been

installed for ten years.

Refer to NFPA 72 for application. 

CAUTION: DO NOT ATTEMPT TO DISASSEMBLY OF THE

FACTORY SEALED HEAT DETECTOR. THIS ASSEMBLY

IS SEALED FOR YOUR PROTECTION AND IS NOT

INTENDED TO BE OPENED FOR SERVICING BY USERS.

TO OPEN THE DETECTOR HEAD WILL VOID THE

WARRANTY.

SPECIFICATION

Model

2/4

wire

Voltage

DC

Standby

Current

(Max.)

Alarm

Current

(Max.)

Surge

Current

(Max.)

Star-Up

Time

(Max.)

Permissible

Current

(Max.)

Frequency

Alarm contact

Base model

PLH-24V

2

15~35V

A

70mA

120 A

60 Seconds

80mA

2 Seconds

P/N870302

88

The detector to be tested should be subject to a flow of

HEATSENSORTESTING

Reviews: