background image

 

ProtEX-MAX PD8-6310-WM Explosion-Proof  
NTEP Certified Batch Controller Instruction Manual 

 

 
 

 

 

www.predig.com

 

 

Weights & Measures

 

 

 

 

 

  NTEP Certified Weighing and Measuring Device 

  Mechanically Secured Programming Lockout 

  Pulse, Open Collector, NPN, PNP, TTL, Switch Contact,  

Sine Wave (Coil), Square Wave Inputs 

  5, 10, or 24 V Flowmeter Power Supply 

  K-Factor, Internal Scaling, or External Calibration 

  Start, Batch, Pause, & Stop with Front Panel Buttons 

  Display Batch Total + Rate, Grand Total, Batch Count or Preset 

  Single or Multi-Stage Batching with up to 4 Relays 

  Automatic Overflow Protection 

  Manual Control or Automatic Batching 

  Modern, Sleek and Practical Enclosure 

  Display Mountable at 0°, 90°, 180°, & 270° Degrees 

  Explosion-Proof, IP68, NEMA 4X Enclosure 

  SafeTouch

®

 Through-Glass Button Programming 

  Flanges for Wall or Pipe Mounting 

  Superluminous Sunlight Readable Display 

  Free USB Programming Software & Cable 

  4  Isolated 4-20 mA Output

 

 

USB Install

O

O

r

r

d

d

e

e

r

r

 

 

f

f

r

r

o

o

m

m

:

:

 

 

C

C

 

 

A

A

 

 

B

B

r

r

i

i

g

g

g

g

s

s

 

 

C

C

o

o

m

m

p

p

a

a

n

n

y

y

 

 

622 Mary Street; Suite 101; Warminster, PA 18974 

Phone: 267-673-8117 - Fax: 267-673-8118 

[email protected]

 - 

www.cabriggs.com

 

 

Summary of Contents for ProtEX-MAX PD8-6310-WM

Page 1: ...otal Batch Count or Preset Single or Multi Stage Batching with up to 4 Relays Automatic Overflow Protection Manual Control or Automatic Batching Modern Sleek and Practical Enclosure Display Mountable...

Page 2: ...e sure only qualified personnel perform the installation Never remove the instrument cover in explosive environments when the circuit is live Cover must be fully engaged to meet flameproof explosion p...

Page 3: ...put Units or Custom Tags units 34 Setting the Decimal Point dEc pt 35 Programming the Batch Controller prog 35 Input Calibration Method InCAL 36 K Factor Calibration Factor 36 Scaling the Controller S...

Page 4: ...ProVu Required Connections 17 Figure 8 Connector Labeling for Fully Loaded PD6310 18 Figure 9 Power Connections 18 Figure 10 Flowmeter Powered by Internal Power Supply 19 Figure 11 Flowmeter Powered b...

Page 5: ...le NTEP certified batch controllers provide excellent but simple batch control capabilities with features such as preclose relays and automatic overrun correction for more accurate batches and conveni...

Page 6: ...s Display Update Rate 5 second 200 ms Overrange Display flashes 999999 Underrange Display flashes 99999 Front Panel NEMA 4X IP65 Programming Methods Four front panel buttons digital inputs PC and Mete...

Page 7: ...Point d ddddd d dddd d ddd d dd d d or dddddd Calibration May be calibrated using K factor internal calibration or by applying an external calibration signal K Factor Field programmable K factor conve...

Page 8: ...2 to 4 relays Latching requires manual acknowledge Relay Reset User selectable via front panel buttons digital inputs or PC 1 Automatic reset only non latching when the input passes the reset point o...

Page 9: ...tal inputs 4 digital outputs Digital Input Logic High 3 to 5 VDC Digital Input Logic Low 0 to 1 25 VDC Digital Output Logic High 3 1 to 3 3 VDC Digital Output Logic Low 0 to 0 4 VDC Source Current 10...

Page 10: ...C to 60 C T5 40 C to 65 C Certificate number Sira 12ATEX1182 IECEx Ex d IIC T Gb Ex tb IIIC T90 C Db IP68 Ta 40 C to C T6 40 C to 60 C T5 40 C to 65 C Certificate Number IECEx SIR 12 0073 Special Con...

Page 11: ...ation 14 Measuring Devices 2014 Edition National Conference on Weights and Measures NCWM National Type Evaluation Program NTEP Certificate of Conformance available at www predig com Electromagnetic Co...

Page 12: ...t is installed in a high voltage environment and a fault or installation error occurs high voltage may be present on any lead Read all product labels completely and follow all instructions and require...

Page 13: ...conduit stopping plugs require the application of non setting solvent free thread sealant It is critical that all relevant hazardous area guidelines be followed for the installation or replacement of...

Page 14: ...d to provide 24 VDC power for the transmitter or sensor If the transmitter requires 5 or 10 VDC excitation the internal jumper J4 must be configured accordingly To access the voltage selection jumper...

Page 15: ...gramming lockout jumper will prevent access to the programming menus The jumper may be removed to regain access to the programming menus Combined with sealing the rear case to restrict access to the p...

Page 16: ...curity Seal Installation Guide LIM8 63101WM 2 for complete NTEP security seal installation instructions To install the wire security seal 1 Locate the wire security seal packed with the controller 2 P...

Page 17: ...n the back of the elec tronics module Some connectors may be provided already connected These connections are required for proper opera tion of the ProtEX MAX and should not be removed unless instruct...

Page 18: ...expansion modules cables or controllers to the RJ45 M LINK connector Otherwise damage will occur to the equipment and the controller Figure 8 Connector Labeling for Fully Loaded PD6310 Power Connecti...

Page 19: ...on Connections The ProtEX MAX has a 5 position terminal block for connecting RS 485 serial devices Figure 16 details the wiring connections from the ProtEX MAX to an RS 485 serial converter such as th...

Page 20: ...istors are optional and values depend on the cable length and characteristic im pedance Consult the cable manufacturer for recommendations 2 Refer to RS 232 to RS 485 Converter documentation for furth...

Page 21: ...local codes to prevent damage to the meter and ensure personnel safety When using more than one instrument in a multi drop or multi point mode each meter must be provided with its own unique address S...

Page 22: ...ng circuits for RC network assembly and installation Figure 21 AC and DC Loads Protection Choose R and C as follows R 0 5 to 1 for each volt across the contacts C 0 5 to 1 F for each amp through close...

Page 23: ...not used The I terminal is the 24 V and the R terminal is the return Interlock Relay Feature As the name implies the interlock relay feature reassigns one or more alarm control relays for use as inter...

Page 24: ...S located on the connector board To actuate a button press one finger to the glass directly over the marked button area Then retract finger more than three inches from the glass before pressing the ne...

Page 25: ...digital input Total overflow indicator M Manual control relays or analog output Programming Press the Menu button to enter or exit the Programming Mode at any time Press the Right arrow button to move...

Page 26: ...ocess in single or multi stage batch control or as alarms that will be active when the batch process is running A 4 20 mA output option is also available for retransmitting the process variable analog...

Page 27: ...tage batch control was desired with one relay for control then one would set the assignment of relay 2 assign2 to off rate or grand total The following pages show an illustration of how the above sett...

Page 28: ...ProtEX MAX PD8 6310 WM Explosion Proof NTEP Certified Batch Controller Instruction Manual 28...

Page 29: ...r and double click on the drive labeled MAINSTAL 3 Double click on the file named MAStart The program will open a few windows and install two programs on your com puter Simply follow the onscreen inst...

Page 30: ...urs or day T Cf Total conversion factor Enter the conversion factor decimal point and the conversion factor mode Batch mode Automatic or manual batch control T dly Time delay Set time delay for automa...

Page 31: ...Enter to reset max display Display Parameter Action Setting Description Rst Lo Reset low Press Enter to reset min display Rst HL Reset high low Press Enter to reset max min displays Rst t Reset total...

Page 32: ...to the settings are saved to memory only after pressing Enter The display moves to the next menu every time a setting is accepted by pressing Enter Setting Numeric Values The numeric values are set u...

Page 33: ...ble or disable totalizer and batching features 3 Select the display units tags 4 Decimal point position 5 Program menu for scaling or calibration 6 Display parameter and intensity 7 Relay operation 8...

Page 34: ...factor value i e pulses gal The controller will automatically calculate the flow rate using the K factor and the time base selected Default setting Setting the Totalizer and Batching Features total A...

Page 35: ...cy in Hz pulses sec The calibration equipment is traceable to NIST standards Use the K Factor menu to match the rate totalizer with a flowmeter s k factor pulse unit of measure Use the Scale menu to s...

Page 36: ...ed Only one of these methods can be employed at a time The Scale and Calibrate functions can use up to 32 points default is 2 The number of points should be set for Scale and Calibrate accordingly und...

Page 37: ...priate input signal to be applied or programmed The error message might be caused by any of the following conditions 1 Input signal is not connected to the proper terminals or it is connected backward...

Page 38: ...anual or automatic reset In the automatic reset mode a programmable time delay is available to reset the grand total after the assigned preset is reached Non Resettable Totalizer The total and grand t...

Page 39: ...max and min values 5 Display Modbus input 6 Off no display 7 Display rate units 8 Display rate 9 Display total 10 Display grand total 11 Toggle rate and total 12 Toggle rate and grand total 13 Display...

Page 40: ...h Clear manual reset when not in a batch process only after alarm condition has cleared e Pump alternation control automatic reset only for level applications unrelated to batch control f Sampling the...

Page 41: ...not appropriate for batch control applications but may be used then the controller is in other applications 4 Automatic manual reset when not in a batch process non latching 5 Latching manual reset o...

Page 42: ...been accepted Setting Fail Safe Operation In fail safe mode of operation the relay coil is energized when the process variable is within safe limits and the relay coil is de energized when the alarm c...

Page 43: ...r programmed states when the batch process is started Grand total alarm relays will initialize to their programmed state at controller power up Fail Safe Operation The following table indicates how al...

Page 44: ...be set up as interlock relays To set up the relays for the interlock feature 1 Access the Setup Relay Action menu and set the action to off 2 In the Advanced features User menu program any of the digi...

Page 45: ...erward See the diagram below for more details The utility of this function can of course be expanded beyond sampling and be used whenever a timed relay output closure is required when the batch total...

Page 46: ...d the relay resets The cycle repeats every time the set point is crossed going up for high alarms and going down for low alarms The sample time can be programmed between 0 1 and 600 0 seconds Total Re...

Page 47: ...ange state The same principle applies to the Off time delay Note If Automatic or Manual A mAn reset mode is selected the LED follows the reset point and not the relay state when the relay is acknowled...

Page 48: ...rol sets all relays and analog output for automatic operation Setting Up the Password pass The Password menu is used for programming three levels of security to prevent unauthorized changes to the pro...

Page 49: ...o gain access the menu After exiting the programming mode the controller returns to its password protected condition Disabling Password Protection To disable the password protection access the Passwor...

Page 50: ...d messages of the Advanced Features menu in the order they appear in the menu Display Parameter Action Setting Gate Gate Gate settings Lo G Low gate Program Low gate value Hi G High gate Program High...

Page 51: ...rogram maximum mA output allowed min Minimum Program minimum mA output allowed Calib Calibrate Calibrate 4 20 mA output internal reference source used for scaling the output Display Parameter Action S...

Page 52: ...f the F3 key No other functions including min max display manual alarm reset or total reset will function while a batch is running Multi Point Calibration Scaling The controller is set up at the facto...

Page 53: ...mmunications serial The controller is equipped with serial communications capability as a standard feature using Modbus RTU Serial Communication Protocol The meter may be connected to a PC for initial...

Page 54: ...network A multi point network consists of multiple drivers and receivers connected on a single bus where any point node can transmit and or receive data RS 485 allows multiple drivers and receivers o...

Page 55: ...he linear function The multi point linearization can be used to linearize the display for non linear signals such as those from level transmitters used to measure volume in odd shaped tanks or to conv...

Page 56: ...ion To perform the analog output calibration it s recommended to use a milliamp meter with a resolution of at least 0 1 A to measure the output current The values saved internally during this procedur...

Page 57: ...value on line 2 Ln2 HL Display maximum minimum dis play values on line 2 Ln2 gt Display the grand total on line 2 Ln2 bc Display the batch count on line 2 Contrl Directly access the control menu Disp...

Page 58: ...the diagnostic messages see Advanced Features Menu Display Messages page 50 Determining Software Version To determine the software version of a controller 1 Go to the Diagnostics menu diAG and press E...

Page 59: ...version factor T CF 1 000 Grand total reset T rst Manual Relay 1 assignment Asign1 Total Relay 2 assignment Asign2 Total Relay 2 preclose preCls No Relay 3 assignment Asign3 Rate Relay 4 assignment As...

Page 60: ...h buttons will be re enabled automatically 60 seconds after the last button push If slide switch on connector board is in DISABLE position switch to ENABLE Strong direct sunlight may interfere with Sa...

Page 61: ...number Check Display assignment it might be displaying max min or set point Display alternates between 1 Hi and a number 2 Lo and a number Press Menu to exit max min display readings Relay operation i...

Page 62: ...50mm of the enclosure Verify that the operating atmosphere of the instrument is consistent with the appropriate hazardous locations certifications If the instrument is installed in a high voltage envi...

Page 63: ...6310 WM Explosion Proof NTEP Certified Batch Controller Instruction Manual 63 Mounting Dimensions All units inches mm Figure 28 Enclosure Dimensions Front View Figure 29 Enclosure Dimensions Side Cros...

Page 64: ...ProtEX MAX PD8 6310 WM Explosion Proof NTEP Certified Batch Controller Instruction Manual 64 This Page Intentionally Left Blank...

Page 65: ...079 31 2008 EN 61000 6 4 2007 EN 61010 1 2001 and EN 61326 2006 are no longer harmonized The requirements of these standards have been checked against the harmonized standard EN 55022 2010 EN 60079 0...

Page 66: ...recision Digital For Technical Support please Call 800 610 5239 or 508 655 7300 Fax 508 655 8990 Email support predig com For Sales Support or to place an order please contact your local distributor o...

Reviews: