6. Error Display and Correction

Error Message

Action Needed

E.SYS

Needs Repair

E.RJC

Needs Repair

SP Decimal

Flashing

Check Comm Cable

S.OPN

Check Sensor

Error Incident

EEPROM, DATA Loss

RJC Sensor Failure

Communication Failure

Open Sensor Detected

                    PD560 Series Nova Digital Process and Temperature Meter

Instruction Manual             

25

www.

GlobalTestSupply

.com

Find Quality Products Online at:

[email protected]

Summary of Contents for NOVA PD560 Series

Page 1: ...DIGITAL METER NOVA PD560 Series Instruction Manual PD562 PD568 PRECISION DIGITAL CORPORATION 1 www GlobalTestSupply com Find Quality Products Online at sales GlobalTestSupply com...

Page 2: ...demarks mentioned in this document are the property of their respective owners 2009 2015 Precision Digital Corporation All rights reserved Options 00 None 21 2 relays 2 digital inputs 24 2 relays RS 4...

Page 3: ...1 Dimensions and Panel Cutouts 7 2 Panel Mounting 28 7 3 Power Cable Specifications 29 7 4 Terminal Specifications 29 7 5 Terminal Assignment Connections and Ratings 30 26 4 Operation Flow Chart 12 5...

Page 4: ...2 Table 1 Universal Input Selection 13 Table 2 DI Operation 17 Fig 2 Bias Formula Calculation 15 Fig 3 Alarm Operation 20 Fig 1 Temperature Bias 15 7 10 Digital Input Connection DI 34 Table of D Regis...

Page 5: ...alled external to this product 4 Do not make modifications or additions internally to the product It may cause personal injury to the user or damage to the product 5 Contact technical support as liste...

Page 6: ...nment Precautions 1 Only operate the controller when it is properly installed 2 When installing the controller select a location where Rear terminals are protected from accidental contact Mechanical v...

Page 7: ...AC 50 60 HZ 10 Watts FUSE Required fuse UL Recognized 1 A 250 V slow blow ISOLATION 2300 V input to output to power line 4 kV relay output to input output power line ENVIRONMENTAL Operating temperatur...

Page 8: ...nput Type UNIVERSAL INPUT TYPE AND ACCURACY Performance within recommended operating conditions 10 to 50 C 20 to 90 RH For a range scale of 0 to 100 C 0 3 C 1 digit and for a range scale of 100 to 100...

Page 9: ...igital Inputs CONFIGURATION Two contacts two operating modes CONTACTS Normally open switches external excitation note required or open collector transistor OPENCIRCUIT Approximately 5 VDC VOLTAGE LOGI...

Page 10: ...ay Used to move to the next digit when setting parameters S T UP DOWN W SHIFT SET ENT ENTER LED Function ALM1 2 3 LEDs turn on when the corresponding alarm relays are energized Control Keys LED Displa...

Page 11: ...A1DB ALT2 G ALM RET RETH RETL G RET COM P BAUD PRTY SBIT DLEN ADDR RP TM G COM AL 2 A2DB ALT3 AL 3 A3DB A A1DY A2DY A3DY SET ENT SET ENT SET ENT SET ENT SET ENT ST ST ST ST T NOTE PwD Lockout Passwor...

Page 12: ...display selected parameters in the operation display The parameters to be displayed are set from parameters US1 and US2 in G CTL The Table of D Registers provides the number to determine what paramet...

Page 13: ...800 0 to 1700 199 9 to 900 0 200 to 1300 199 9 to 400 0 0 to 2300 0 to1390 199 9 to 850 0 199 9 to 500 0 19 99 to 99 99 150 0 to 150 0 199 9 to 500 0 Temp Range F 300 to 2500 0 to 2300 300 to 2300 300...

Page 14: ...parameter sets the PV filter for stabilization from electromagnetic noise and interference This will effect the rate of change of the PV display value Its default setting is OFF and can be set from 1...

Page 15: ...C BS4 BSP1 BSP2 BSP3 RL RH Original Temp Fig 1 Temperature Bias 0 C BS0 RL BSP3 RH BSP1 BSP2 Original Temperature Temperature After Bias BS4 75 C 0 C 25 C 50 C 100 C 3 C BS3 2 C BS1 1 C BS2 0 C BS4 3...

Page 16: ...99 to 9999 INSH INSL Decimal position determined by IN DP ABS 100 0 mV V There are two types of engineering units values used in the setting of parameters absolute engineering units AEU and general en...

Page 17: ...ens for viewing confirmation and setup of commonly used parameters from the operation display To add the parameter to the operation display enter the corresponding number for the parameter from the Ta...

Page 18: ...et the password once it has been set If the password is forgotten contact technical support as listed on the back of this manual CAUTION PV Most parameters will be reset to their default settings when...

Page 19: ...G RET Q G ALM S T S T S T S T S T T S indicates standby operation F for forward operation r for reverse failsafe operation Alarm Types and LED Display Decimal point always displayed H indicates a hig...

Page 20: ...larm Absolute Value High Limit Alarm with Standby Absolute Value Low Limit Alarm with Standby Absolute Value High Limit Alarm with Standby Absolute Value Low Limit Alarm with Standby For 3 3 3 3 Rev 3...

Page 21: ...EU 100 0 Alarm 1 DB GEU 0 0 to 100 0 GEU GEU 0 5 Alarm Type 2 Refer to Table 3 Alarm Selection ABS AH F Set Value of Alarm 2 AEU 100 0 to 00 0 AEU AEU 100 0 Alarm 2 DB GEU 0 0 to 100 0 GEU GEU 0 5 A1D...

Page 22: ...PV LPS ABS PV Ret Scale High Limit T C RTD INRH to INRL mV V INSH to INSL RETH RETL AEU INRH Ret Scale Low Limit AEU INRL PV PWD Q G CTL Q G IN K R G COM Q G RET Q G ALM S T S T S T T S T S T NOTE RE...

Page 23: ...eter is not displayed when the communication protocol COM P is set for MODBUS ASCIII or RTU PV The parameter to set the communication address for the controller This can be set as 1 to 99 pcs address...

Page 24: ...e 600 1200 2400 4800 9600 19200 ABS 9600 Option Parity None Even Odd ABS None Option Stop Bit 1 2 ABS 1 Option Data Length 7 8 not used when set for MODBUS ABS 8 Option Address 1 to 99 maximum of 31 c...

Page 25: ...mal Flashing Check Comm Cable S OPN Check Sensor Error Incident EEPROM DATA Loss RJC Sensor Failure Communication Failure Open Sensor Detected PD560 Series Nova Digital Process and Temperature Meter I...

Page 26: ...or reference only Units m 3 78 0 45 3 92 3 78 4 23 3 61x3 61 4 72 4 72 3 62 3 62 3 78XN 3 62 1 4 DIN PD560 Series Nova Digital Process and Temperature Meter Instruction Manual 26 www GlobalTestSupply...

Page 27: ...0 70 3 62 1 77 4 72 2 76 48 96 3 78 1 89 99 6 44 6X91 6 3 92 0 45 1 76 X3 61 Units 1 8 H DIN PD560 Series Nova Digital Process and Temperature Meter Instruction Manual 27 www GlobalTestSupply com Find...

Page 28: ...1 Dimensions and Panel Cutouts 2 Insert the controller through the front of the panel rear terminals first 3 On applicable models attach the right and left mounting bracket and secure it to the panel...

Page 29: ...agnetic interference 7 3 Power Cable Specification Make power connections using 0 9 to 2 0 mm2 or 16 AWG vinyl insulated wire Voltage rating of 300 VAC Use M3 5 screw compatible crimp on terminals wit...

Page 30: ...00 bps 100 240 VAC 50 60 Hz Open circuit voltage approximately 5 VDC Logic levels Lo 0 to 0 8 VDC Hi 4 7 to 28 VDC NO switches external excitation not required or open collector transistor PD560 Serie...

Page 31: ...Open circuit voltage approximately 5 VDC Logic levels Lo 0 to 0 8 VDC Hi 4 7 to 28 VDC NO switches external excitation not required or open collector transistor Rating 250 VAC 1 A 30 VDC 1 A PD560 Se...

Page 32: ...Cable Connection CAUTION 7 7 Signal Input Connection CAUTION CAUTION A B b RTD INPUT NOVA SHIELD 1 RTD Input 2 DC Voltage Input 3 DC Current Input FG L N INPUT NOVA SHIELD V INPUT NOVA SHIELD DCmA R T...

Page 33: ...to the Nova Controller and the source circuit breaker before wiring CAUTION CAUTION Retransmitting Output RET RET NOVA SHIELD RET Receiver Recorder etc To prevent electric shock be sure to turn off p...

Page 34: ...of the relay contacts of the controller Diode Connect directly to the relay coil terminals Meter CAUTION CAUTION Switching Inductive Loads When using switching inductive loads the use of RC networks...

Page 35: ...unication Wiring RS 485 CAUTION Up to 31 slave controllers Nova series controllers equipped with the RS 485 serial communication option can be connected Be sure to connect terminating resistors 220 1...

Page 36: ...S2 17 A3DY BS3 18 ERROR BS4 19 20 AL1 H 21 PV LO AL2 H 22 PV HI AL3 H 23 24 25 AL1 L 26 AL2 L 27 AL3 L 28 29 30 31 32 33 34 US1 35 US2 37 LOCK 36 DI SL 38 DSP H 39 DSP L 40 41 42 43 Table of D Registe...

Page 37: ...TL 53 s 54 e 55 r 56 57 A 58 r 59 e 60 a 61 62 63 64 65 66 67 68 69 70 71 72 73 74 75 76 77 78 79 80 81 82 83 84 85 86 87 COM P BAUD PRTY SBIT DLEN ADDR RP TM PD560 Series Nova Digital Process and Tem...

Page 38: ...UT 0 100 200 300 400 500 600 88 89 90 91 92 93 94 95 96 97 98 99 Read Only Location NOTE PD560 Series Nova Digital Process and Temperature Meter Instruction Manual 38 www GlobalTestSupply com Find Qua...

Page 39: ...der a warranty claim should be returned freight prepaid Upon warranty confirmation Precision Digital will repair or replace and return the unit at no charge via UPS Ground Other shipping is available...

Page 40: ...LIM560_D 10 15 PD560 Series Nova Digital Process and Temperature Meter Instruction Manual 40 www GlobalTestSupply com Find Quality Products Online at sales GlobalTestSupply com...

Reviews: