background image

PRECISION DIGITAL CORPORATION 

DART MODEL PD602 LOW-COST PROCESS METER

www.predig.com

    DO NOT OVER TIGHTEN.

SPECIFICATIONS

Except where noted all specifications apply to operation at +25°C.

General

Inputs:

 Field selectable: 4-20 mA, 0-5 V, 1-5 V, 0-10 V

Display:

 0.56" (14.2 mm) red LED, 3½ digits (±1999)

Accuracy:

 ±0.05% FS ±1 count

Calibration Range:

 Low input (e.g. 4 mA): -500 to 500

High input (e.g. 20 mA): 20 to 2000 above low input display.

Decimal Point:

 Jumper selectable up to three decimal places

Front Panel:

 NEMA 4X, IP65; panel gasket provided

Input Impedance:

 Voltage ranges: greater than 200 kΩ; 

Current range:

 10-60 Ω, varies with resettable fuse impedance

Input Overload:

 Protected by automatically resettable fuse

Display Update Rate:

 2.5/second

Overrange:

 Displays 1

Underrange:

 Displays -1

Temperature Drift:

 100 PPM/°C 

Recalibration:

 Recommended at least every 12 months

Power Options:

 85-265 VAC, 50/60 Hz, 90-265 VDC, 8 W max or 12-

36 VDC, 12-24 VAC, 6 W max.

Transmitter Supply:

 Isolated 24 VDC ±10% @ 200 mA max

Required Fuse:

 UL Recognized, 5 A max, slow-blow; up to 6 meters 

may share one fuse.

Normal Mode Rejection:

 62 dB at 50/60 Hz

Common Mode Rejection:

 120 dB at 50/60 Hz

Isolation: 

4 kV input-to-power line; 500 V input-to-24 VDC supply

Operating Temperature:

 0 to 65°C

Storage Temperature:

 -40 to 85°C

Relative Humidity:

 0 to 90% non-condensing

Connections:

 Removable screw terminals accept 12 to 26 AWG

Enclosure:

 1/8 DIN, high impact plastic, UL 94V-0, color: gray

Weight:

 5.0 oz (142 g)

Warranty: 

1 year parts & labor 

Extended Warranty:

 1 or 2 years, refer to Price List for details.

Features & Benefits

 

4-20 mA, 0-5 V, 1-5 V, 0-10 V inputs

  NEMA 4X front panel with protective overlay

  Calibrate from the front panel

  Easy to set up and calibrate

  Universal power supply

  12-36 VDC power option

  24 VDC @ 200 mA supply option

Panel Mounting Instructions

1.  Remove the two mounting brackets provided with the meter (back-off  

     the two screws so that there is ¼″ (6.4 mm) or less through the bracket. 

     Slide the bracket toward the front of the case and remove).
2.  Insert meter into the panel cutout.
3.  Install mounting brackets and tighten the screws against the panel.  

     To achieve a proper seal, tighten the mounting bracket screws evenly 

      until meter is snug to the panel along its short side.

3.622" (92mm)

1.772"

(45mm)

Panel Cutout

to DIN 43700

Square Corners to 0.060"

(1.5mm) Max Radius

A

B

 

Tolerances:

A: +0.032 (+0.8mm)

     -0.000 (-0.0mm)

B: +0.024 (+0.6mm)

     -0.000 (-0.0mm)

MOUNTING DIMENSIONS

 

1.76"

 

(45mm)

 

0.59"

 

(15mm)

 

3.2"

 

(81mm)

 

2.45"

 

(62mm)

 

3.61"

 

(92mm)

 

2.50"

 

(64mm)

 

4.68"

 

(119mm)

 

Dart Model PD602

85-265 VAC** 

Model

12-36 VDC** 

Model

Options Installed

PD602-6R0-0*

PD602-7R0-0

None

PD602-6R0-1*

24 VDC Transmitter Supply

 *Quick Shipment Program product, shipped within 2 working days.

**Meters may be powered from AC or DC, see Specifications for details.

ORDERING INFORMATION

Setup, Calibration & Labels

Model

Description

PDN-CAL

2-Point Input Calibration

PDN-CERTCAL

Certificate of Calibration

PDN-CERTCAL2 Certificate of Calibration with Data

PDLXXXX

Engraved Plastic Labels 

Reviews: