F4 Digital Input Connections
A digital input, F4, is standard on the meter. This
digital input connected with a normally open closure
across F4 and COM, or with an active low signal
applied to F4. It can be used for remote operation of
front-panel buttons, to acknowledge/reset relays,
reset totals, or to reset max/min values. See
Keys & Digital I/O Available Settings
complete list of capabilities.
Figure 22. F4 Digital Input Connections
4-20 mA Output Connections
Connections for the 4-20 mA transmitter output are
made to the connector terminals labeled MA OUT.
The 4-20 mA output may be powered internally or
from an external power supply.
Figure 23. 4-20 mA Output Connections
Analog Output Transmitter Power
Supply
The internal 24 VDC power supply powering the
analog output may be used to power other devices, if
the analog output is not used. The I+ terminal is the
+24 V and the R terminal is the return.
Figure 24. Analog Output Supply Powering Other
Devices