![Precision Digital Corporation ProVu PD6310-WM Instruction Manual Download Page 21](http://html.mh-extra.com/html/precision-digital-corporation/provu-pd6310-wm/provu-pd6310-wm_instruction-manual_1594189021.webp)
P
RO
V
U
™ PD6310-WM NTEP Certified Pulse Input Batch Controller
Instruction Manual
21
External Relay & Digital I/O
Connections
The relay and the digital I/O expansion modules
using a CAT5 cable provided with each module. The
two RJ45 connectors on the expansion modules are
identical and interchangeable; they are used to
connect additional modules to the system.
Note: The jumper located between the RJ45
connectors of the PDA1044 must be removed
on the second digital I/O module in order for the
system to recognize it as module #2.
•
DO NOT
connect or disconnect the expansion
modules with the power on! More detailed
instructions are provided with each optional
expansion module.
Figure 27. Expansion Module & DIN Rail Mounting
Kit
Figure 28. External Relays Module Connections
Figure 29. Digital I/O Module Connections
Remote Batch Control Connections
The batch controller can be operated via the front
panel push buttons or a remote control station using
the PDA1044 Digital I/O module as illustrated in
Figure 30. Controller to Control Station Connection
Figure 30. Controller to Control Station
Connection
Interlock Relay Feature
As the name implies, the interlock relay feature
reassigns one, or more, alarm/control relays for use
as interlock relay(s). Interlock contact(s) are wired to
digital input(s) and activate the interlock relay. This
feature is enabled by configuring the relay, and the
corresponding digital input(s), see
Interlock Relay (Force On) Feature
In the example below, an Interlock Contact switch is
connected to a digital input, which will be used to
force on (energize) the Interlock Relay. The Interlock
Relay and the Control Relay are connected in series
with the load.
•
When the Interlock Contact is closed (safe), the
Interlock Relay energizes, allowing power to flow
to the Control Relay; the corresponding front
panel LED is on.
•
When the Interlock Contact is open, the
corresponding front panel LED flashes (locked
out), the Interlock Relay is de-energized,
preventing power from flowing to the Control
Relay and the load.
Figure 31. Interlock Connection
1
2
RLY5
RLY6
RLY7
RLY8
3
4
5
6
7
8
NO
C
NO
C
NO
C
NO
C
1
2
3
4
5
6
+5
I1
I2
I3
I4
O1
7
8
O2
O3
9
10
O4
G
DI 1-4
DO 1-4
5 VDC
GND