Display Parameter Action/Setting
Source
Source
Select source for the 4-20 mA output
break
Loop break
Set relay condition if loop break detected
O-rang
Overrange
Program mA output for display overrange
u-rang
Underrange
Program mA output for display underrange
nmAx
Maximum
Program maximum mA output allowed
nmin
Minimum
Program minimum mA output allowed
Calib
Calibrate
Calibrate 4-20 mA output (internal
reference source used for scaling the
output)
4 nmA
4 mA output
Enter mA output value read by milliamp
meter with at least 0.001 mA resolution
20 nmA
20 mA output
Enter mA output value read by milliamp
meter with at least 0.001 mA resolution
User
User I/O
Assign function keys and digital I/O
F1
*
F1* function key
Assign F1 function key (*F1/F2/F3)
F4
F4 function
Assign F4 function (digital input)
dI I
Digital input 1
Assign digital input 1 – 8, if expansion
modules are connected
dO 1
Digital output 1
Assign digital output 1 – 8, if expansion
modules are connected
ICal
Internal
calibration
Enter internal calibration (used for
recalibrating the meter with a calibrated
signal source)
Ch-A
Channel A
Perform calibration on channel A
Ch-b
Channel B
Perform calibration on channel B
C CAL
Current
calibration
Calibrate 4-20 mA current input (internal
reference source used for scaling the
input)
C lo
Current low
Calibrate low current input (e.g. 4 mA)
C Hi
Current high
Calibrate high current input (e.g. 20 mA)
v CAL
Voltage
calibration
Calibrate voltage input
v Lo
Voltage low
Calibrate low voltage input (e.g. 0 V)