PD154 & PD158 Vigilante II Annunciators 

Instruction Manual 

 

14 

 

NO/NC Programming Example 

The following is an example of NO/NC setup. Input 

channel 1 and 2 are changed from the default settings 

of NO to be NC inputs.

 

1.  Press and hold 

ACK

 and 

RESET

 for 3 sec-

onds. When all LEDs cycle, release. 

2.  Press 

ACK

 within 3 seconds. All LEDs blink in 

unison. 

3.  Press 

ACK

 again while LEDs blink 

 

4.  LED 1 will be off 

indicating a NO input 

for channel 1. All 

other LEDs will be 

dim. 

 

 

5.  Press 

RESET

 to 

change LED 1 from 

off to on, setting 

channel 1 for a NC 

input. 

 

 

6. 

Press 

ACK

 to confirm 

the NC setting and 

proceed to program 

channel 2.

 

 

7. 

Press 

RESET

 to 

change LED 2 from 

off to on, setting 

channel 2 for a NC 

input.

 

 

 

8.  Press 

ACK

 to confirm the NC setting and 

program channel 3. 

9.  Press and hold 

ACK

 for five seconds to return 

to normal operation. 

 

Relay Operation 

Relays 1 and 2 have standard functionality as defined 

below. 

Relay 1 Operation 

Relay 1 enters alarm state when there is a new alarm. 

This relay will clear when the alarm is acknowledged, 

generally by pressing the 

ACK

 pushbutton. 

Relay 2 Operation 

Relay 2 enters alarm state when any channel displays 

in alarm state. This relay will clear when all indication 

LEDs are cleared. 

Relay Fail-Safe 

In fail-safe operation, a relay coil is energized in non-

alarm condition. In case of power failure, relays will go 

to alarm state. Fail-safe operation is set 

independently for each relay. 

Programming Relay Fail-Safe 

1.  Press and hold 

ACK

 and 

RESET

 for 3 

seconds. When all LEDs cycle, release. 

2.  Press 

RESET

 within 3 seconds of release 

while LEDs cycle.

1

  

3.  Press 

RESET

 within 3 seconds of release 

while LEDs blink.

1

 

4.  Press the 

RESET

 pushbutton to turn LED 1 

off for normal operation, or on for fail-safe 

operation of Relay 1. 

5.  Press 

ACK

 to accept the type of operation 

for Relay 1. 

6.  Press the 

RESET

 pushbutton to turn LED 2 

off for normal operation, or on for fail-safe 

operation of Relay 2. 

7.  Press 

ACK

 to accept the type of operation 

for Relay 2. 

8.  Press and hold 

ACK 

for five seconds to 

return to operation. 

During programming, LEDs 1 through 4 will light. The 

LED being programmed will display as either off or 

brightly on. The other 3 LEDs will be dim. On a 

PD158, LEDs 5 through 8 will be off. 
The green power LED will blink quickly to indicate the 

unit is in the advanced programming mode. The unit 

will automatically leave setup mode if no pushbutton 

is pressed for 3 minutes. 

Note:

 LED 3 and 4 are used for the silence 

pushbutton enable/disable option (see  page 15) and 

no lock-in option (see page 16)

 

 

1

The unit will automatically leave setup mode if steps 2 and 3 

are not followed.

 

 

Summary of Contents for PD154-6R2-1

Page 1: ...Functions Sunlight Readable Indication Shallow Depth Case Extends Only 3 6 91 mm Behind Panel Isolated 24 VDC 200 mA Transmitter Power Supply AC Models 2 SPDT Relays for Alarm Activated Devices Opera...

Page 2: ...y Information and Terms Conditions on www predig com for complete details 2020 Precision Digital Corporation All rights reserved Introduction The Vigilante II is a multipurpose panel mounted alarm ann...

Page 3: ...AC Enclosures Model of Units Description Mounting PDA2301 V 1 Plastic NEMA 4X Enclosure Through Door PDA2302 V 2 Plastic NEMA 4X Enclosure Through Door PDA2303 V 3 Plastic NEMA 4X Enclosure Through Do...

Page 4: ...Input Types 11 External Pushbutton Connections 11 Multiple Unit First Out Indication Connections 11 Setup and Programming 12 Overview 12 Front Panel Pushbuttons and Status LED Indicators 12 Full Func...

Page 5: ...sions Side View 9 Figure 4 Case Dimensions Top View 9 Figure 5 Connector Labeling for PD154 6R2 1 9 Figure 6 Connector Labeling for PD158 6R2 1 9 Figure 7 Connector Labeling for PD154 7R2 0 9 Figure 8...

Page 6: ...steps 4 and 5 for all input channels Press and hold ACK for five seconds to return to normal operation with the programmed input types Basic Connections All connections are made to removable screw ter...

Page 7: ...orage temperature range 40 to 85 C Relative humidity 0 to 90 non condensing Connections Removable screw terminal blocks for 12 to 22 AWG wire Enclosure 1 8 DIN high impact plastic UL 94V 0 front color...

Page 8: ...only by trained service personnel Installation There is no need to remove the instrument from its case to complete the installation wiring and setup Unpacking Remove the instrument from box Inspect th...

Page 9: ...0 C or 60 75 C insulation for all line voltage connections Observe all safety regulations Electrical wiring should be performed in accordance with all applicable national state and local codes to prev...

Page 10: ...eparate in put channel and all emitters connected to common All channels are factory set for transistor inputs normally in the cutoff or off state For normally active saturation state or on transistor...

Page 11: ...nputs OC or TTL signals However throughout this manual the term pushbutton is used to describe these external inputs Please refer to the chart below for signal logic External Input Type Active When Sw...

Page 12: ...ISA sequences A F1A and F2A which reset acknowledged channels automatically See selected sequence details for complete function description see Full Sequence Descriptions page 17 LED TEST SILENCE ACK...

Page 13: ...ition Alarm Conditions for normally closed inputs 1 An open contact between an input channel and common will cause an alarm condition 2 An off or cutoff state transistor between an input channel and c...

Page 14: ...cleared Relay Fail Safe In fail safe operation a relay coil is energized in non alarm condition In case of power failure relays will go to alarm state Fail safe operation is set independently for eac...

Page 15: ...ton enable disable option see page 15 and no lock in option see page 16 Relay Operation Overview The following figure illustrates the operation of the relays ACK Pressed ON OFF Relay 1 ON OFF Relay 2...

Page 16: ...conds to return to operation The green power LED will blink quickly to indicate the unit is in the advanced programming mode The unit will automatically leave setup mode if no pushbutton is pressed fo...

Page 17: ...The input is in alarm state and the channel has not been acknowledged with the ACK pushbutton Acknowledge The alarm state is acknowledged with the ACK pushbutton This will restart the first out indica...

Page 18: ...dge Steady Steady Off Normal Off Off Off Condition LED Horn 1st Pt Next Pt Normal Off Off Off Alert Flash Steady On Normal Flash Off On ACK Pushbutton Acknowledge Off Off Off Condition LED Horn 1st Pt...

Page 19: ...al Off Off Off Alert Intermittent Flash Fast Flash On RESET Pushbutton 1st Out Reset Fast Flash Fast Flash On ACK Pushbutton Acknowledge Steady Steady Off Normal Off Off Off Maintained Alarm ACK befor...

Page 20: ...Flow Chart Condition LED Horn Normal Off Off Alert Steady On Normal Off Off Condition LED Horn Normal Off Off Alert Flash On Normal Flash On ACK Pushbutton Acknowledge Steady Off RESET Pushbutton Rese...

Page 21: ...ledge Steady Steady Off RESET Pushbutton Reset Off Off Off Condition LED Horn 1st Pt Next Pt Normal Off Off Off Alert Flash Steady On ACK Pushbutton Acknowledge Steady Steady Off Normal Steady Steady...

Page 22: ...echnical standards and when applicable or required a European Union notified body certification Standards EN 55022 2003 EN 61000 6 2 2001 EN 61010 1 2001 EN 61326 2006 The standards EN 55022 2003 EN 6...

Page 23: ...PD154 PD158 Vigilante II Annunciators Instruction Manual 23 This page left blank intentionally...

Page 24: ...www predig com LIM158_F SFT043 Ver 1 0 up 05 20 Contact Precision Digital Technical Support Call 800 610 5239 or 508 655 7300 Fax 508 655 8990 Email support predig com Sales Support Call 800 343 1001...

Reviews: