Input Scaling & Math Functions
The ConsoliDator is capable of various functions for scaling the 4-20 mA inputs.
Linear
Square Root,
Programmable Exponent,
and
Integration
are two-point scaling functions.
Multi-Point
is capable of handling up to 32 scaling points and requires that the ConsoliDator
Monitor Software be used to enter these points.
Linear
Linear mode refers to basic 2-point scaling of a 4-20 mA signal in engineering units.
The graph in
Figure 17
shows the display response based on example scaling
parameters. For this mode select [Linear] from
Function
options, then follow
Sensor
Input Setup
(page 29) to enter your scaling parameters.
Process
Scaling Parameters
Input
(mA)
Display
(%)
High Value:
100.00
Low Value:
0.00
4.00
0.00
Sensor:
20.00
Sensor:
4.00
5.00
6.25
Line a r Re sponse
0.00
20.00
40.00
60.00
80.00
100.00
4.00
8.00
12.00
16.00
20.00
Sensor (mA)
Display
(%
)
6.00
12.50
7.00
18.75
8.00
25.00
9.00
31.25
10.00
37.50
11.00
43.75
12.00
50.00
13.00
56.25
14.00
62.50
15.00
68.75
16.00
75.00
17.00
81.25
18.00
87.50
19.00
93.75
20.00
100.00
Figure 17. Linear Response Graph