Sensor error indication, inside and outside range
Input ”out of range” indication
Valid measurement range:
Out of range limit
Display readout
f to I function:
0.001 Hz to 50 kHz
< 0.0009 Hz (18 min. 31 sec.)
or
0.5 Hz (2.0 s) if L.COF=YES (Low
cut-off frequency)
If In.Lo is set to 0.000 Hz:
”0.0”
If In.Lo is set ≥ 0.001 Hz:
”IN.LO” - flashing
> 50.5 kHz
”IN.HI” - flashing
Period time function:
20 µs to 999.9 s
> 1111 s (18 min. 31 sec.)
(Low cut off time)
”IN.HI” - flashing
< 19.8 µs
”IN.LO” - flashing
Sensor error indication in 5725, only available for NAMUR input:
Condition
Out of range
limit
Relay
behaviour
Analog
output value
Display
redaout
Sensor input
type = NAMUR
and sensor error
detection = ON
> 6.9 mA
Set to user
defined value: HOLD.
ACTIVE. DEACTIVE
or NONE
Set to user-
defined value
(23, 0, 3.5 mA
or NONE)
”SE.SH”
< 0.1 mA
”SE.BR”