background image

10.00

DISP.HI

Txt 9

99.99 

-19.99

1 2

*3

*2

*4

CURR

ANA.OUT

Txt 10

VOLT 
CURR

1 2

3

ACTI

OUT.MOD

Txt 13

-/+20 

-/+10 

S4-20 

4-20 
0-20

VOLT

ANA.OUT

Txt 10

3

0-10

O.RANGE

Txt 12

-/+10

-/+5

-/+1 
2-10 
0-10 

1-5 

0-5 

0.2-1 

0-1

1 2

3

4-20

O.RANGE

Txt 11

1 2

3

UP

OUT.ERR

Txt 14

ZERO 

UP 

DOWN 
NONE 

1 2

3

1 2

PASS 

ACTI

3

0.0

RESP

Txt 15

60.0 

0.0

1 2

3

3

3

18 

4104 V100-UK

To default state 1.0 

Menu only displayed if password is enabled. (

E.PAS 

YES

)

*1

Menu not displayed if a Bipolar Output Range is selected.
Direct or Inverted output characteristics must be set in the ADV setting OFUN menu. 

Only ranges starting at zero are available for OFUN = V.FUNC - refer to *7.

Menu only displayed if input type supports sensor error check.
Selectable range as defined by DEC.P, DISP.LO and DISP.HI.

VFUN (V-shaped output function) is only available when 
an output range starting at zero is selected.
DIR (direct) and INV (inverted) output characteristics can be 
combined with all selectable output ranges.

Selectable range equals selected input range.

*2

*4

*3

*5

*7

*6

Summary of Contents for 4104

Page 1: ...4 1 0 4 S I G N A L S T H E B E S T P E N D I N G Universal Sign al Tra nsmitt er N o 4 1 0 4 V 1 0 0 U K F r o m s e r n o 1 2 1 4 7 9 0 0 1 ...

Page 2: ...R electronics A S offre une large gamme de produits pour le traite ment des signaux analogiques et numériques dans tous les domaines industriels La gamme de produits s étend des transmetteurs de température aux afficheurs des isolateurs aux interfaces SI jusqu aux modules universels Vous pouvez compter sur nos produits même dans les conditions d utilisation sévères p ex bruit électrique vibrations...

Page 3: ... Applications 6 Technical characteristics 6 Mounting installation 7 PR 4501 Display programming front 8 Connections 9 Order codes 10 Specifications 10 4501 display readout of input 4 20 mA loop error detection and signal outside range 14 Block diagram 15 Configuration operating the function keys 16 Routing diagram 17 Routing diagram Advanced settings ADV SET 19 Scrolling help text in display line ...

Page 4: ...vice must only be applied as described in the following Prior to the commissioning of the device this installation guide must be examined carefully Only qualified personnel technicians should install this device If the equipment is used in a manner not specified by the manufacturer the protection provided by the equipment may be impaired WARNING Until the device is fixed do not connect hazardous v...

Page 5: ...se contact your local distributor or alternatively PR electronics A S Mounting and connection of the device should comply with national legislation for mounting of electric materials i e wire cross section protective fuse and location Descriptions of input output and supply connections are shown in this installation guide and on the side label The following apply to fixed hazardous voltages connec...

Page 6: ...nal transmitter is in conformity with the following directives and standards The EMC Directive 2004 108 EC and later amendments EN 61326 1 For specification of the acceptable EMC performance level refer to the electrical specifications for the module The Low Voltage Directive 2006 95 EC and later amendments EN 61010 1 Rønde 1 October 2012 Kim Rasmussen Manufacturer s signature ...

Page 7: ...ent of the outgoing current is carried out on a 4 20 mA output signal If the analogue output current is 0 mA can e g be caused by an open output loop an error mode switches on the red front LED and the 4501 display shows AO ER This function is not a default option but must be actively selected in the menu by programming the analogue output to S4 20 The error mode can only be reset by switching off...

Page 8: ... floating signals Process control is possible using the unipolar bipolar analogue voltage and current output The analogue output can be set to either active current or passive 2 wire output The analogue output signal is linear and selectable as direct or inverted but can also be set to V curve function 100 0 100 on the basis of a linear 0 100 input signal Technical characteristics All programming ...

Page 9: ...ort 2 3 kVAC galvanic isolation and an excellent signal noise ratio 60 dB Mounting installation A very low power consumption allows for tight DIN rail mounting in Safe area or in Zone 2 Cl 1 Div 2 Approved for marine applications Programming signal monitoring and a 2 point process calibration is possible via the 4501 detachable display All programming can be protected by a user password ...

Page 10: ...rogramming and signal monitoring Application Communications interface for modification of operational parameters in 4104 When mounted in the process the display shows process values and device status Technical characteristics LCD display with 4 lines Line 1 H 5 57 mm shows the scaled process value OK or error Line 2 H 3 33 mm shows the selected engineering unit Line 3 H 3 33 mm shows analogue outp...

Page 11: ...2 14 13 11 10 V 1 V 10 V 1 V 4104V100 UK 9 Connections Input signals Output signals Supply 21 6 253 VAC or 19 2 300 VDC Current 3 wire Tx 2 wire Tx Voltage V supply Safe Area or Zone 2 Cl 1 Div 2 gr A D Current voltage 2 wire ...

Page 12: ...nical specifications Dimensions HxWxD 109 x 23 5 x 104 mm Dimensions HxWxD w 4501 display 109 x 23 5 x 116 mm Weight approx 250 g DIN rail type DIN EN 60715 35 mm Wire size 0 13 2 08 mm2 AWG 26 14 stranded wire Screw terminal torque 0 5 Nm Common electrical specifications Supply voltage universal 21 6 253 VAC 50 60 Hz or 19 2 300 VDC Power consumption 2 5 W Internal power dissipation 2 0 W Isolati...

Page 13: ...y limitation terminal 44 nom 30 mA Voltage input Signal range 12 V Programmable measurement ranges 0 1 0 2 1 0 5 1 5 0 10 2 10 V 1 5 and 10V Input resistance nom 2 MΩ Current output specifications Active unipolar and bipolar mA Programmable ranges 0 20 4 20 10 and 20 mA Direct or Inverted action V curve function 100 0 100 20 0 20 mA Load max 800 Ω 16 V 20 mA Accuracy values Input Absolute accuracy...

Page 14: ...orresponds to 0 mA at 0 20 mA and to 3 5 mA at 4 20 mA High corresponds to 23 mA at both 0 20 and 4 20 mA Zero equals 0 mA output None the output state is undefined Voltage output specifications Programmable ranges 0 0 2 1 0 1 5 0 2 10 1 5 and 10 V Direct or Inverted action V curve function 100 0 100 1 0 1 V 5 0 5 V and 10 0 10 V Load min 500 kΩ Programmable damping 0 0 60 0 s Output limitation at...

Page 15: ...4104V100 UK 13 Approvals EMC 2004 108 EC EN 61326 1 LVD 2006 95 EC EN 61010 1 UL Standard for Safety UL 508 GOST R Marine Det Norske Veritas Ships Offshore Pending Ex FM 3025177 ...

Page 16: ...load on the current output only S4 20 mA Communications test 4501 4104 NO CO Connection error Hardware error read note FL ER Error in FLASH Configuration error read note CO ER Error in FLASH Check that saved configuration in 4501 matches device TY ER Invalid type or rev no Hardware error read note AO SU Analogue output supply err Hardware error read note RA ER RAM error Hardware error read note EE...

Page 17: ...diagram 500 Ω EEPROM D A 11 13 14 50 Ω 33 31 12 PT C 43 44 42 41 20 Ω A D V V mA mA I 10 V 1 V 4104 Gnd I V I V HW Watchdog CPU mA 0 3 wire Tx 2 wire Tx Voltage Current 21 6 253 VAC or 19 2 300 VDC V supply 2 wire Green Red ...

Page 18: ...aving the changed values or parameters Further explanations Password protection Programming access can be blocked by assigning a password The password is saved in the transmitter in order to ensure a high degree of protection against unauthorised modifications to the configuration Default password 2008 allows access to all configuration menus Signal and loop error info via display front 4501 Input...

Page 19: ... mbar mils min mm mm s mol MPa mV MW MWh N Ohm Pa pH rpm s S t t h uA um uS V W Wh yd blank 1 2 4104V100 UK 17 1 0 Default state Line 1 shows input signal Line 2 shows UNIT By pressing 1 and 2 simultaneously line 3 alternates between A Out and TAG Line 4 shows trending in the process signal and communication status Continued on the page Routing diagram ADV SET Selectable UNITS 1 Routing diagram If...

Page 20: ...led E PAS YES 1 Menu not displayed if a Bipolar Output Range is selected Direct or Inverted output characteristics must be set in the ADV setting OFUN menu Only ranges starting at zero are available for OFUN V FUNC refer to 7 Menu only displayed if input type supports sensor error check Selectable range as defined by DEC P DISP LO and DISP HI VFUN V shaped output function is only available when an...

Page 21: ...xt 27 3 YES NO 1 2 5 0 V Txt 28 3 10 00 0 0 1 2 NO LANG SETUP 3 UK LANGUA Txt 31 DE DK ES FR IT SE UK PASS SETUP 3 3 YES EN PASS Txt 29 3 YES NO 1 2 NO 0000 NEW PAS Txt 30 3 9999 0000 1 2 3 1 2 5 5 6 OFUN SETUP 3 DIR O FUNC Txt 32 VFUN INV DIR 1 2 3 7 4104V100 UK 19 Routing diagram Advanced settings ADV SET To default state 1 0 Selectable range as defined by DEC P DISP LO and DISP HI 5 Selectable ...

Page 22: ...signal the device will return to factory calibration Process simulation function SIM If you agree to the point EN SIM it is possible to simulate an input signal by means of the arrow keys and thus control the output signal up or down You must exit the menu by pressing 3 no time out Password PASS Here you can choose a password between 0000 and 9999 in order to protect the device against unauthorise...

Page 23: ...t range Select active output mode Select passive output mode Select no error action output undefined at error Select downscale at error Select zero output at error Select upscale at error Set Analog output response time in seconds Select Analog output function Enter Language setup Enter Password setup Enter Simulation mode Perform Process calibration Enter Display setup Perform Memory operations L...

Page 24: ... Galvanic isolators for analogue and digital signals as well as HART signals A wide product range with both loop powered and universal isolators featuring linearisation inversion and scaling of output signals Isolation Interfaces for analogue and digital signals aswellasHART signalsbetweensensors I Pconverters frequency signals and control systems in Ex zone 0 1 2 and for some devices in zone 20 2...

Page 25: ...sales prelectronics it www prelectronics se sales prelectronics se www prelectronics co uk sales prelectronics co uk www prelectronics com sales prelectronics com www prelectronics cn sales prelectronics cn Head office Denmark www prelectronics com PR electronics A S sales prelectronics dk Lerbakken 10 tel 45 86 37 26 77 DK 8410 Rønde fax 45 86 37 30 85 ...