14
Version No. V6R0
Safety Manual
9113 TEMPERATURE / mA CONVERTER
14.2.1 If no password is set
Action
Display shows
1
Press OK
ADV.SET
2
Set (ADV.SET) to Yes and press OK
SETUP
3
Set SETUP to SIL and press OK
EN.SIL
4
Set EN.SIL to YES and press OK
NEW.PAS
5
Set password to a number between 0 and
9999 and press OK
(At this time the device starts operating
in SIL mode with the entered configuration
parameters!)
CONFIG
Verify
OPEN->LOCK*
6
Press OK to confirm verification of the OPEN-
>LOCK in the display
CH1.TYP
7
Verify input type for Channel 1 and press OK
I.RANGE
8
Verify fixed input range and press OK
(ONLY IF CH1.TYP = CURR)
CONNEC
9
Verify sensor connection type and press OK
(ONLY IF SENSOR = Ni or Pt and CH1.TYP =
TEMP)
UNIT
10
Verify temperature unit and press OK
(ONLY IF CH1.TYP = TEMP)
SENSOR
11
Verify temperature sensor type and press OK
( ONLY IF CH1.TYP = TEMP)
Pt.TYPE
12
Verify Pt sensor type and press OK
(ONLY IF SENSOR = Pt and CH1.TYP = TEMP)
Ni.TYPE
13
Verify Ni sensor type and press OK
(ONLY IF SENSOR = Ni and CH1.TYP = TEMP)
TC.TYPE
14
Verify Thermocouple type and press OK
(ONLY IF SENSOR = TC and CH1.TYP = TEMP)
CJC
* Open is shown briefly in the display.