9106 - Product version 9106-002 

19

Help text overview

[01] 
[02] 
[03] 
[04] 
[05] 
[06] 

[09] 
[10] 
[11] 
[12] 

 
[15] 
[16] 
[17]
[18]
[19]
[20]
[21]
[22]

Set correct password [PASS]
Enter advanced setup [ADV.SET]
Set low limit for loop error detection [LO.LIM1] [LO.LIM2]
Set high limit for loop error detection [HI.LIM1] [HI.LIM2]
Enable rail status signal output? [RAIL.ER]
Enter display setup [SETUP]
Enter password setup [SETUP]
Enter language setup [SETUP]
Enter rail setup [SETUP]
Adjust LCD contrast [CONTRA]
Adjust LCD backlight [LIGHT]
Write a 5-character tag no. [TAGNO1] [TAGNO2]
Show loop values in display
Show Tag no. in display
Alternate shown information in display
Enable password protection [EN.PASS]
Set new password [NEW.PAS]
Select language [LANGUA]
Loop signal limit exceeded
Loop wire breakage
No communication - check connections
Eeprom error - check configuration
Hardware error

Summary of Contents for 9106B

Page 1: ...PERFORMANCE MADE SMARTER CCOE Product manual 9106B HART transparent repeater TEMPERATURE I S INTERFACES COMMUNICATION INTERFACES MULTIFUNCTIONAL ISOLATION DISPLAY No 9106V105 UK Product version 9106 002 ...

Page 2: ...nication interfaces that can access your PR installed base of products All the interfaces are detachable have a built in display for readout of process values and diagnostics and can be configured via push buttons Product specific functionality includes communication via Modbus and Bluetooth and remote access using our PR Process Supervisor PPS application available for iOS and Android Our display...

Page 3: ...4511 8 Mounting demounting the PR 4511 4501 8 Order 9 Accessories 9 Technical data 9 Visualisation in 4511 4501 of hardware software error 12 Connections 13 Block diagram 14 Signal error indications without display front 15 Configuration operating the function keys 16 Routing diagram 17 Routing diagram advanced settings ADV SET 18 Help text overview 19 Appendix 20 IECEx Installation Drawing 21 ATE...

Page 4: ...sulation Ex devices have been approved acc to the ATEX directive for use in connection with installations in explosive areas See installation drawings in appendix Safety instructions Definitions Hazardous voltages have been defined as the ranges 75 to 1500 Volt DC and 50 to 1000 Volt AC Technicians are qualified persons educated or trained to mount operate and also trouble shoot technically correc...

Page 5: ...on Power Rail 9400 the power is supplied by Power Control Unit 9410 Year of manufacture can be taken from the first two digits in the serial number Calibration and Adjustment During calibration and adjustment the measuring and connection of external voltages must be carried out according to the specifications of this manual The technician must use tools and instruments that are safe to use Normal ...

Page 6: ... following output configuration When using 9106xxB in a SIL2 safety function channel 1 is used for the safety loop Channel 2 can be used for any non safety device For higher safety purposes SIL 3 9106xxB can be used as a splitter for SIL 3 loops Channel 1 and 2 are then connected to the same safety PLC where channel 2 is used as a redundant diagnostic channel For more information consult the FMEDA...

Page 7: ...roduct version 9106 002 7 Applications Rail supply Rail supply Power rail Status relay signal Zone 0 1 2 20 21 22 M1 Cl I II III Div 1 gr A G Zone 2 Cl 1 Div 2 gr A D or Safe Area Device status Device status Supply Supply 19 2 31 2 VDC N C No connection No connection Power connection Channel 2 Output signals Analog 4 20 mA Input signals Channel 1 2 wire transmitter Current Passive 2 wire Current 2...

Page 8: ...loop current in mA for channel 2 or tag no Line 4 shows communications status In order to protect the configuration against unauthorised changes access to the menus can be blocked by a password Using Modbus output via 4511 When using the digital output of the 4511 and no load on the output terminals of the 9106 the output terminals need to be shorted to make sure that the 9106 does not overheat A ...

Page 9: ...nd Protection degree IP20 Installation in Pollution degree 2 overvoltage category II Mechanical specifications Dimensions HxWxD 109 x 23 5 x 104 mm Dimensions HxWxD w 4501 4511 109 x 23 5 x 116 131 mm Weight approx 250 g Weight incl 4501 4511 approx 265 g 280 g DIN rail type DIN EN 60715 35 mm Wire size 0 13 2 08 mm2 AWG 26 14 stranded wire Screw terminal torque 0 5 Nm Vibration IEC 60068 2 6 2 13...

Page 10: ...dB Response time 0 90 100 10 5 ms Effect of supply voltage change on output nom 24 VDC 10 µA Current input Measurement range 3 5 23 mA 2 wire transmitter supply terminal 44 43 and 54 53 9106B1x Uo 27 5 VDC 16 V 20 mA 9106B2x Uo 25 3 VDC 15 V 20 mA Sensor error detection Loop break 4 20 mA 1 mA Input voltage drop Supplied unit 4 V 23 mA Non supplied unit 6 V 23 mA EMC immunity influence 0 5 of span...

Page 11: ...point 0 29 9 mA Hysteresis for setpoints 0 1 mA Max voltage 110 VDC 125 VAC Max current 0 3 ADC 0 5 AAC Max voltage hazardous installation 32 VDC 32 VAC Max current hazardous installation 1 ADC 0 5 AAC Observed authority requirements EMC 2014 30 EU LVD 2014 35 EU ATEX 2014 34 EU RoHS 2011 65 EU Approvals Det Norske Veritas Ships Offshore Stand f Certific No 2 4 ClassNK TA18527M c UL us Standard fo...

Page 12: ...ER Supply error Hardware error RA ER RAM error Hardware error FL ER Flash error Hardware error IN ER Initialization error Hardware error C1 ER Hardware error channel 1 Hardware error C2 ER Hardware error channel 2 Hardware error DE ER General error All error indications in the display flash once per second The help text explains the error In case of cable fault the backlight also flashes This can ...

Page 13: ...rrent Passive 2 wire Current Passive 2 wire 2 wire transmitter Current 2 wire transmitter Current Channel 1 Channel 2 Channel 2 Ex inputs SIL 2 Channel 1 Current 2 wire transmitter Current Current Ex inputs SIL 3 Supply and status relay Power rail connections N C NC no connection Supply Supply Supply Supply NC NC Error signal HART communication is possible directly on the input and output terminal...

Page 14: ...mA mA Tx 2 1 14 9106 Product version 9106 002 Block diagram Status relay N C Status relay N C Supply Power Rail connections Supply 19 2 31 2 VDC 2 wire transmitter 2 wire transmitter Channel 1 Channel 2 2 wire supply 2 wire supply Supply Green Ch 1 status Red Ch 2 status Red Gnd Gnd NC No connection Supply Supply ...

Page 15: ...ON OFF De energized ON Ch 2 defective ch 1 OK Blinking OFF ON De energized ON Channel 1 signal OK Blinking OFF OFF Energized OFF Ch 1 signal limit exceeded Blinking Blinking OFF De energized ON if activated Ch 1 fixed loop break limit exceeded Blinking Flashing OFF De energized ON if activated Channel 2 signal OK Blinking OFF OFF Energized OFF Ch 2 signal limit exceeded Blinking OFF Blinking De en...

Page 16: ...or both channels This function can be deactivated by selecting limits outside the range 3 5 23 mA Alternatively the status relay can be used as a simple limit switch in the 1 channel version The loop break limit is fixed 1 mA If this limit is exceeded the status relay will be de energized Signal and sensor error indication via display front 4511 4501 Sensor error loop break is shown in line 1 on t...

Page 17: ...en value and proceed to the next menu Hold 3 Back to previous menu return to menu 1 0 without saving To default state 1 0 Continued on the page Routing diagram ADV SET 1 1 Only if password protected 1 0 Default state Line 1 shows status for channel 1 and channel 2 Line 2 shows analogue value or tag no for channel 1 If the loop limit is exceeded LO LIM and HI LIM the analog value is shown for 5 sec...

Page 18: ...T TAG LOOP 1 2 TAG2 TAGNO Txt 11 9 A 1 2 3 3 3 3 3 3 PASS SETUP Txt 6 YES EN PASS Txt 15 YES NO 1 2 0000 NEW PAS Txt 16 9999 0000 1 2 3 3 3 NO LANG SETUP Txt 6 UK LANGUA Txt 17 9 0 1 2 3 3 RAIL SETUP Txt 6 YES RAIL EN Txt 5 YES NO 1 2 3 3 18 9106 Product version 9106 002 Routing diagram advanced settings ADV SET To default state 1 0 ...

Page 19: ...RAIL ER Enter display setup SETUP Enter password setup SETUP Enter language setup SETUP Enter rail setup SETUP Adjust LCD contrast CONTRA Adjust LCD backlight LIGHT Write a 5 character tag no TAGNO1 TAGNO2 Show loop values in display Show Tag no in display Alternate shown information in display Enable password protection EN PASS Set new password NEW PAS Select language LANGUA Loop signal limit exc...

Page 20: ...Appendix IECEx installation drawing ATEX Installation Drawing FM Installation Drawing Desenho de Instalaçao INMETRO Safety Manual 20 9106 Product version 9106 002 ...

Page 21: ...0 2011 Supply terminal 31 32 Voltage 19 2 31 2VDC Status Relay terminal 33 34 Zone 2 installation Voltage max 125 VAC 110 VDC 32 VAC 32 VDC Power max 62 5 VA 32 W 16 VA 32 W Current max 0 5 A AC 0 3 ADC 0 5 A AC 1 ADC Installation notes Install in pollution degree 2 overvoltage category II as defined in IEC 60664 1 Do not separate connectors when energized and an explosive gas mixture is present D...

Page 22: ...4 F Lo 4 15 mH 16 59 mH 33 17 mH 54 42 mH Lo Ro 223 µH Ω 447 µH Ω 733 µH Ω 20 Ta 60ºC terminal 11 12 13 14 terminal 31 32 33 34 terminal 91 92 93 94 95 Um 253 V max 400 Hz 44 43 42 41 54 53 52 51 34 33 32 31 14 13 12 11 9106 4501 91 92 93 94 95 Power Rail CH1 CH2 T T _ _ 9106B2A 9106B2B Ex input Loop current source CH1 terminal 43 44 CH2 terminal 53 54 Uo 25 3 V Io 96 mA Po 0 61 W IIC IIB IIA I Co...

Page 23: ...106B1B 9106B2A 9106B2B Ex input External current source CH1 terminal 41 42 CH2 terminal 51 52 Uo 0 V Io 0 mA Po 0 mW Ui 30 V Ii 120 mA Pi 0 85 mA Ci 2 nF Li 0 μH 44 43 42 41 54 53 52 51 34 33 32 31 14 13 12 11 9106 4501 91 92 93 94 95 Power Rail CH1 CH2 _ _ 20 Ta 60ºC terminal 11 12 13 14 terminal 31 32 33 34 terminal 91 92 93 94 95 Um 253 V max 400 Hz 9106 Product version 9106 002 23 ...

Page 24: ...3 94 F Lo 4 15 mH 16 59 mH 33 17 mH 54 42 mH Lo Ro 223 µH Ω 447 µH Ω 733 µH Ω 20 Ta 60ºC terminal 11 12 13 14 terminal 31 32 33 34 terminal 91 92 93 94 95 Um 253 V max 400 Hz 44 43 42 41 54 53 52 51 34 33 32 31 14 13 12 11 9106 4501 91 92 93 94 95 Power Rail CH1 CH2 T 9106B2A 9106B2B Ex input Loop current source 1 to 2 CH1 terminal 44 CH2 terminal 52 Uo 25 3 V Io 96 mA Po 0 61 W IIC IIB IIA I Co 0...

Page 25: ...al 11 12 13 14 terminal 31 32 33 34 terminal 91 92 93 94 95 Um 253 V max 400 Hz 9106B1A 9106B1B 9106B2A 9106B2B Ex input External current source 1 to 2 CH1 terminal 42 CH2 terminal 51 Uo 0 V Io 0 mA Po 0 W Ui 30 V Ii 120 mA Pi 0 85 W Ci 4 nF Li 0 μH 20 Ta 60ºC 44 43 42 41 54 53 52 51 34 33 32 31 14 13 12 11 9106 4501 91 92 93 94 95 Power Rail CH1 CH2 9106 Product version 9106 002 25 ...

Page 26: ...79 11 2012 EN 60079 15 2010 Supply terminal 31 32 Voltage 19 2 31 2VDC Status Relay terminal 33 34 Zone 2 installation Voltage max 125 VAC 110 VDC 32 VAC 32 VDC Power max 62 5 VA 32 W 16 VA 32 W Current max 0 5 A AC 0 3 ADC 0 5 A AC 1 ADC Installation notes Install in pollution degree 2 overvoltage category II as defined in EN60664 1 Do not separate connectors when energized and an explosive gas m...

Page 27: ...A I Co 0 084 F 0 670 F 2 23 F 3 94 F Lo 4 15 mH 16 59 mH 33 17 mH 54 42 mH Lo Ro 223 µH Ω 447 µH Ω 733 µH Ω 20 Ta 60ºC terminal 11 12 13 14 terminal 31 32 33 34 terminal 91 92 93 94 95 Um 253 V max 400 Hz 44 43 42 41 54 53 52 51 34 33 32 31 14 13 12 11 9106 4501 91 92 93 94 95 Power Rail CH1 CH2 T T _ _ 9106B2A 9106B2B Ex input Loop current source CH1 terminal 43 44 CH2 terminal 53 54 Uo 25 3 V Io...

Page 28: ... 1 2 20 21 22 or Zone 2 9106B1A 9106B1B 9106B2A 9106B2B Ex input External current source CH1 terminal 41 42 CH2 terminal 51 52 Uo 0 V Io 0 mA Po 0 mW Ui 30 V Ii 120 mA Pi 0 85 mA Ci 2 nF Li 0 μH 44 43 42 41 54 53 52 51 34 33 32 31 14 13 12 11 9106 4501 91 92 93 94 95 Power Rail CH1 CH2 _ _ 20 Ta 60ºC terminal 11 12 13 14 terminal 31 32 33 34 terminal 91 92 93 94 95 Um 253 V max 400 Hz ...

Page 29: ... IIA I Co 0 084 F 0 670 F 2 23 F 3 94 F Lo 4 15 mH 16 59 mH 33 17 mH 54 42 mH Lo Ro 223 µH Ω 447 µH Ω 733 µH Ω 20 Ta 60ºC terminal 11 12 13 14 terminal 31 32 33 34 terminal 91 92 93 94 95 Um 253 V max 400 Hz 44 43 42 41 54 53 52 51 34 33 32 31 14 13 12 11 9106 4501 91 92 93 94 95 Power Rail CH1 CH2 T 9106B2A 9106B2B Ex input Loop current source 1 to 2 CH1 terminal 44 CH2 terminal 52 Uo 25 3 V Io 9...

Page 30: ...e 0 1 2 20 21 22 or Zone 2 terminal 11 12 13 14 terminal 31 32 33 34 terminal 91 92 93 94 95 Um 253 V max 400 Hz 9106B1A 9106B1B 9106B2A 9106B2B Ex input External current source 1 to 2 CH1 terminal 42 CH2 terminal 51 Uo 0 V Io 0 mA Po 0 W Ui 30 V Ii 120 mA Pi 0 85 W Ci 4 nF Li 0 μH 20 Ta 60ºC 44 43 42 41 54 53 52 51 34 33 32 31 14 13 12 11 9106 4501 91 92 93 94 95 Power Rail CH1 CH2 ...

Page 31: ...ion Voltage max 125 VAC 110 VDC 32 VAC 32 VDC Power max 62 5 VA 32 W 16 VA 32 W Current max 0 5 A AC 0 3 ADC 0 5 A AC 1 ADC Installation notes In Class I Division 2 installations the subject equipment shall be mounted within a tool secured enclosure which is capable of accepting one or more of the Class I Division 2 wiring methods specified in the National Electrical Code ANSI NFPA 70 or Canadian ...

Page 32: ...12 11 9106 4501 91 92 93 94 95 Power Rail CH1 CH2 T T _ _ 9106B2A 9106B2B Ex input Loop current source CH1 terminal 43 44 CH2 terminal 53 54 Uo 25 3 V Io 96 mA Po 0 61 W IIC or A B IIB or C E F IIA or D G Co 0 104 F 0 818 F 2 85 F Lo 3 85 mH 15 43 mH 30 86 mH Lo Ro 234 µH Ω 468 µH Ω Simple Apparatus or Intrinsic safe apparatus with entity parameters Vmax Ui Vt Uo Imax Ii It Io Pi Pt Po Ca Ccable C...

Page 33: ...4501 91 92 93 94 95 Power Rail CH1 CH2 _ _ 20 Ta 60ºC terminal 11 12 13 14 terminal 31 32 33 34 terminal 91 92 93 94 95 Um 253 V max 400 Hz Simple Apparatus or Intrinsic safe apparatus with entity parameters Vmax Ui Vt Uo Imax Ii It Io Pi Pt Po Ca Ccable Ci La Lcable Li Hazardous Classified Location Unclassified Location or Class I II III Division 1 Group A B C D E F G Hazardous Classified Locatio...

Page 34: ... 60ºC terminal 11 12 13 14 terminal 31 32 33 34 terminal 91 92 93 94 95 Um 253 V max 400 Hz 44 43 42 41 54 53 52 51 34 33 32 31 14 13 12 11 9106 4501 91 92 93 94 95 Power Rail CH1 CH2 T 9106B2A 9106B2B Ex input Loop current source 1 to 2 CH1 terminal 44 CH2 terminal 52 Uo 25 3 V Io 96 mA Po 0 61 W IIC or A B IIB or C E F IIA or D G Co 0 104 F 0 818 F 2 85 F Lo 3 85 mH 15 43 mH 30 86 mH Lo Ro 234 µ...

Page 35: ...i 120 mA Pi 0 85 W Ci 4 nF Li 0 μH 20 Ta 60ºC 44 43 42 41 54 53 52 51 34 33 32 31 14 13 12 11 9106 4501 91 92 93 94 95 Power Rail CH1 CH2 Simple Apparatus or Intrinsic safe apparatus with entity parameters Vmax Ui Vt Uo Imax Ii It Io Pi Pt Po Ca Ccable Ci La Lcable Li Hazardous Classified Location Unclassified Location or Class I II III Division 1 Group A B C D E F G Hazardous Classified Location ...

Page 36: ...inais de alimentação 31 32 Voltagem 19 2 31 2VDC Relé de estado terminais 33 34 Instalação Zone 2 Voltagem máx 125 VAC 110 VDC 32 VAC 32 VDC Potência máx 62 5 VA 32 W 16 VA 32 W Corrente máx 0 5 A AC 0 3 ADC 0 5 A AC 1 ADC Notas de Instalação Instalação em grau de poluição 2 categoria de sobretensão II conforme definido no IEC 60664 1 Não separe conectores quando energizado ou quando uma mistura d...

Page 37: ... 4 15 mH 16 59 mH 33 17 mH 54 42 mH Lo Ro 223 µH Ω 447 µH Ω 733 µH Ω 20 Ta 60ºC terminais 11 12 13 14 terminais 31 32 33 34 terminais 91 92 93 94 95 Um 253 V máx 400 Hz 44 43 42 41 54 53 52 51 34 33 32 31 14 13 12 11 9106 4501 91 92 93 94 95 TRILHO DE ENERGIA CH1 CH2 T T _ _ 9106B2A 9106B2B Entrada Ex Fonte de corrente da malha CN1 terminais 43 44 CN2 terminais 53 54 Uo 25 3 V Io 96 mA Po 0 61 W I...

Page 38: ...9106B2A 9106B2B Entrada Ex Fonte de corrente externa CN1 terminal 41 42 CN2 terminal 51 52 Uo 0 V Io 0 mA Po 0 mW Ui 30 V Ii 120 mA Pi 0 85 W Ci 2 nF Li 0 μH 44 43 42 41 54 53 52 51 34 33 32 31 14 13 12 11 9106 4501 91 92 93 94 95 TRILHO DE ENERGIA CH1 CH2 _ _ 20 Ta 60ºC terminais 11 12 13 14 terminais 31 32 33 34 terminais 91 92 93 94 95 Um 253 V máx 400 Hz 38 9106 Product version 9106 002 ...

Page 39: ... Lo 4 15 mH 16 59 mH 33 17 mH 54 42 mH Lo Ro 223 µH Ω 447 µH Ω 733 µH Ω 20 Ta 60ºC terminais 11 12 13 14 terminais 31 32 33 34 terminais 91 92 93 94 95 Um 253 V máx 400 Hz 44 43 42 41 54 53 52 51 34 33 32 31 14 13 12 11 9106 4501 91 92 93 94 95 TRILHO DE ENERGIA CH1 CH2 T 9106B2A 9106B2B Entrada Ex fonte de corrente da malha 1 e 2 CN1 terminal 44 CN2 terminal 52 Uo 25 3 V Io 96 mA Po 0 61 W IIC II...

Page 40: ...2 13 14 terminais 31 32 33 34 terminais 91 92 93 94 95 Um 253 V máx 400 Hz 9106B1A 9106B1B 9106B2A 9106B2B Entrada Ex Fonte de corrente externa 1 a 2 CN1 terminal 42 CN2 terminal 51 Uo 0 V Io 0 mA Po 0 W Ui 30 V Ii 120 mA Pi 0 85 W Ci 4 nF Li 0 μH 20 Ta 60ºC 44 43 42 41 54 53 52 51 34 33 32 31 14 13 12 11 9106 4501 91 92 93 94 95 TRILHO DE ENERGIA CH1 CH2 40 9106 Product version 9106 002 ...

Page 41: ...106 002 41 Document history The following list provides notes concerning revisions of this document Rev ID Date Notes 105 1703 Installation drawings updated Ex barrier data changed Specifications for max required power added ...

Page 42: ...entation We are headquartered in Denmark and have offices and authorized partners the world over We are a local business with a global reach This means that we are always nearby and know your local markets well We are committed to your satisfaction and provide PERFORMANCE MADE SMARTER all around the world For more information on our warranty program or to meet with a sales representative in your r...

Page 43: ...andards for products communicating monitoring and connecting our customers process measurement points to their process control systems Our innovative patented technologies are derived from our extensive R D facilities and from having a great understanding of our customers needs and processes We are guided by principles of simplicity focus courage and excellence enabling some of the world s greates...