9116QA01
LERBAKKEN 10, 8410 ROENDE DENMARK
Revision date:
2010-02-12
Version Revision
V5 R0–FR01
Prepared by:
PB
Page:
3/4
Uo
28 V
IIC
80 nF
4 mH 54 μH/Ω
Io
93 mA
IIB
640 nF
16 mH 218 μH/Ω
Po
650 mW
IIA
2.1 μF
32 mH 436 μH/Ω
Uo
21.4 V
IIC
0.16 μF
4 mH 54 μH/Ω
Io
93 mA
IIB
1.13 μF
16 mH 218 μH/Ω
Po
650 mW
IIA
4.15 μF
32 mH 436 μH/Ω
Group
Module 9116B1
Term. 54-52; 51-52
Module 9116B2
Term. 54-52; 51-52
Co
Lo
Lo/Ro
Co
Lo
Lo/Ro
Group
Terminal 54-52
Ui
30 V
Ii
120 mA
Pi
900 mW
Ci
3 nF
Li
2 μH
Module 9116B 1/2
Zone dangereuse
Zone non dangereuse
Zone 0,1,2, 20, 21, 22
ou Zone 2
-20 ºC ≤Ta ≤ +60ºC
T
+
-
54
53
52
51
44
43
42
41
9116
34
33
32
31
14
13
12
11
Power Rail
4501
54
53
52
51
44
43
42
41
9116
34
33
32
31
14
13
12
11
Power Rail
4501
Transmetteur
alimenté par la
boucle 4-20 mA
(bornes 11,12,13,14)
(bornes 31,32,33,34)
(bornes 91,92,93,94,95)
U
m:
253 V max. 400 Hz
Relais d’état, bornes (33,34)
Installation en zone non dangereuse
Tension max. : 125 Vca / 110 Vcc
Puissance max. : 62,5 VA / 32 W
Courant max. : 0,5 A ca / 0,3 Acc
Installation en zone 2
Tension max. : 32 Vca / 32 Vcc
Puissance max. : 16 VA / 32 W
Courant max. : 0,5 A ca / 1 A cc
Sortie relais, bornes (13,14)
Installation en zone non dangereuse
Tension max. : 250 Vca / 30 Vcc
Puissance max. : 500 VA / 60 W
Courant max. : 2 A ca / 2 Acc
Installation en zone 2
Tension max. : 32 Vca / 30 Vcc
Puissance max. : 64 VA / 60 W
Courant max. : 2 A ca / 2 A cc