4222V101-UK 15
PNP output
I
out
max. ....................................................................... 30 mA
V
out
................................................................................ 24 VDC
±
10%
C
out
................................................................................ 10 nF
R
out
typ. ....................................................................... 20
Ω
Electromechanical counter ................................... 24 V / 135 mA / 20 ms /
≤
10 Hz
NPN output
I
sink
max. ...................................................................... 150 mA
I
sink
max. peak ........................................................... 300 mA
External voltage (terminal 23) max. ................ 55 VDC
C
out
................................................................................ 10 nF
R
out
typ. ....................................................................... 10
Ω
TTL output
I
sink/source
max. .......................................................... 15 mA
I
sink/source
peak.......................................................... 100 mA
V
out
................................................................................ 5 V ±5%
C
out
................................................................................ 10 nF
R
out
typ. ....................................................................... 55
Ω
Sensor error detection
Programmable ........................................................... 0...26250 Hz
Ex / I.S. approval
FM, applicable in ....................................................... Class I, Div. 2, Group A, B, C, D
Class I, Div. 2, Group IIC
Zone 2
Max. ambient temperature for T5 .................... 60°C
Observed authority requirements
Standard
EMC 2004/108/EC .................................................. EN 61326-1
LVD 2006/95/EC ...................................................... EN 61010-1
FM .................................................................................. 3600, 3611, 3810 and ISA 82.02.01
UL, Standard for Safety ......................................... UL 508
EAC TR-CU 020/2011 ............................................ EN 61326-1
of span =
of the currently selected measurement range