9
2.3
Downloading data to PC
Connect the instrument to the PC and run ENVIS.Daq application. Select the appropriate
communication option and connect to the instrument. In the next screen press
Refresh All
. This
will load and display the actual status of each supported archive.
Device Information
section contains editable description and name under which the actual record is
stored.
Time Frame for Other Archives
tab allows you to limit the date ranges of all archives by the time
interval of the main archive. In the
Destination
section the actual storage can be selected - either to
the SQL database or to the file. The check boxes in
Archives to Download
determines which specific
archive(s) you want to download.
The actual download will start by pressing the
Download All
button. progress is displayed on screen.
When finished the archive can be viewed in the ENVIS application. User can open the downloaded file
directly from ENVIS.Daq.
2.4
Energy meter readings
UMD 705 has an embedded three phase, four-quadrant energy meter with automatic meter reading
functions and
multiple programmable tariffs (Time-of-Use, TOU). The instrument registers active
energy (EP, EP+, EP-) and reactive energy (EQL, EQC or EQC+, EQC-, EQL+, EQL-). According to
the configuration of meter readings are shuffled to the respective tariffs. It automatically provides
summaries per phase. For star connections and
single phase measurements it can also register
energy for each phase separately.
Meter data readings can be downloaded and analyzed in ENVIS or via the standard ModBus protocol
in any other system.
3
Technical Specifications
3.1
Basic Parameters
Auxiliary Voltage
model
„230V“
model
„24V"
aux. voltage range
85 ÷ 510 VAC
85 ÷ 350 VDC
20 ÷ 75 VDC
power supply
7 VA / 3 W
3,5 VA / 3,5 W
overvoltage category
III (300V)
II (100V)
pollution degree
2
connection
isolated, polarity free