Chapter 5 Function parameter
84
Ch
ap
ter 5
selection
Under the parameter modify menu, the subtract function keys adjust the parameter value.
1:Multi-function key is defined free stop key.
The key is effective under Parameter selection monitor menu, the inverter is free stop. After
free stop , no startup command , after 1S, it is allowed restart .
2:Multi-function key is defined as FWD Forward running key.
Under monitor menu, the key is effective under Parameter selection menu, the inverter is
forward running.
3:Multi-function key is defined as FEV reverse running function key.
The key is effective under Parameter selection monitor menu, the inverter is forward running.
4: Multi-function key is defined as Forward Jog running key.
The key is effective under Parameter selection monitor menu, the inverter is forward jog
running.
5: Multi-function key is defined as Reverse Jog running key.
The key is effective under Parameter selection monitor menu, the inverter is reverse jog
running.
6: Multi-function key is defined as UP function key.
The key is effective at any time, the control way is same as terminal control UP.
7
:
Multi-function key is defined as DOWN function key.
The key is effective at any time , the control way is same as terminal control UP.
F6.20
Keyboard
lock
selection
RUN/STOP key is enabled
0
0
☆
STOP/RESET/ key and encoder is enabled
1
RUN/STOP/UP/DOWN key is enabled
2
STOP key is enabled
3
Pressing the PRG+ Encoder keys to achieve lock and unlock.
When the keyboard belongs to the lock state, when the keyboard is locked, the digital display
tube will show "A." in front, such as the keyboard on display 50, when the lock, press the
keyboard "PGR" key, digital display "A.50.00.
F6.21
QUICK
Function
Selection
No function
0
0
☆
jog running
1
shift key
2
forward/Reverse running switching
3
UP/DOWN setting remove
4
Free stop
5
commands switch orderly
6
1:Jog running: press QUICK key , the inverter will make jog running in the default direction.
2:Shift key : Choose displayed parameter circularly under running or stop interface
3:Forward/Reverse running switching: it can complete the request of forward/Reverse
running, it is effective under the keyboard command.
4:UP/DOWN setting remove: to remove the settings of the UP/DOWM.
5:Free stop; operate the quick key to stop the inveter.
6:Switch and display the commands orderly by pressing QUICK key ,Keyboard setting--
terminal setting-communications setting will switch orderly.
5-2-9.Auxiliary function: F7.00-F7.54
Code
Parameter name
Setting range
Factory
setting
Change
Limit
F7.00 Jog running frequency
0.00Hz~F0.19(maximum frequency)
6.00Hz
☆
F7.01 Jog acceleration time
0.0s~6500.0s
5.0s
☆
F7.02 Jog deceleration time
0.0s~6500.0s
5.0s
☆
Defined the inverter's reference frequency and ac/deceleration time when jogging.In
operation of Jog, the start-up mode is fixed as direct start-up mode (F3.00 = 0), the shutdown
mode is fixed as deceleration parking mode (F3.07 = 0).