Powtier Controls Limited 

TC210 Instructional Manual 

210IM 

- 3 - 

20 June 1996

 

 

Issue 2.1 

TC210 Instructional Manual 

Tactical Controls Limited 

Under  normal  operating  conditions  it  is  important 
that   the   TC210   power   switching   unit   should   be 
mounted  VERTICALLY  (as  shown  in  figure  3),  with 
the  FAN  end  facing  DOWNWARDS  if  fitted.  Also 
the ambient temperature should not exceed 50 deg 
C. 
 
If  the  TC210  cannot  be  mounted  vertically  or  if  the 
ambient   temperature   is   higher   than   50   deg   C., 
please  contact  your  supplier  or  Tactical  Controls' 
directly   to   determine   suitability   and   possible 
operating constraints. 
 

PROTECTION FUSE 

 
The  integral  fuse  in  a  MAXIWAT  thyristor  unit  is 
designed primarily to protect the thyristors from any 
excessive  over  current  condition.  In  the  event  of  a 
fuse   blowing,   the   replacement   must   be   a   high 
speed   H.R.C.   fuse   of   an   approved   type. 
Replacement  fuses  can  be  ordered  directly  from 
Tactical Controls or an equivalent type can be used. 
Fuse  types  for  different  current  ratings  are  given  in 
Table 1. 
 

WIRING 

 
The wiring diagrams are shown in figure 1. 
 
The  basic  wiring  is  as  follow:  the  (L)  terminal  must 
be  connected  to  the  load  supply.  One  end  of  the 
load  must  be  connected  to  the  (LOAD)  terminal. 
The   other   end   of   the   load   is   returned   to   the 
`NEUTRAL'  terminal  or  `LINE  2'  or  `LINE  3'  of  the 
mains supply, according to the load configuration. 
 
The input  logic signal supply must be connected to 
the   terminals   marked   with   `I/P+'   and   `I/P-'.   The 
recommended  minimum  input  cable  size  is  0.5mm 
square. 

Table   1.   Fuses   and   fuse   ratings   for   the   TC210 
MAXIWAT range. 
 
Current Voltage  Tactical 

Equivalent 

Rating  Rating  Part no. 

Type 

(Arms)  (Vrms) 
 
16A 

240V 

FUS-660V-20A FERRAZ-660V-

20A 
 

440V 

FUS-660V-20A FERRAZ-660V-

20A 
25A 

240V 

FUS-660V-30A FERRAZ-660V-

30A 
 

440V 

FUS-660V-30A FERRAZ-660V-

30A 
40A 

240V 

FUS-50LET 

BRUSH-50LET 

 

440V 

FUS-45ET 

BRUSH-45ET 

 

500V 

FUS-45ET 

BRUSH-45ET 

 

660V 

FUS-45ET 

BRUSH-45ET 

55A 

240V 

FUS-63LET 

BRUSH-63LET 

 

440V 

FUS-80ET 

BRUSH-80ET 

 

500V 

FUS-80ET 

BRUSH-80ET 

 

660V 

FUS-80ET 

BRUSH-80ET 

75A 

240V 

FUS-80LET 

BRUSH-80LET 

 

440V 

FUS-90EET 

BRUSH-90EET 

 

500V 

FUS-90EET 

BRUSH-90EET 

 

660V 

FUS-90EET 

BRUSH-90EET 

100A 

240V 

FUS-140EET  BRUSH-140EET 

 

440V 

FUS-140EET  BRUSH-140EET 

 

500V 

FUS-140EET  BRUSH-140EET 

 

660V 

FUS-140EET  BRUSH-140EET 

125A 

240V 

FUS-160EET  BRUSH-160EET 

 

440V 

FUS-160EET  BRUSH-160EET 

 

500V 

FUS-160EET  BRUSH-160EET 

 

660V 

FUS-160EET  BRUSH-160EET 

INSTALLATION

 

Summary of Contents for MAXIWAT TC210 Series

Page 1: ...Instructional Manual 210IM 1 20 June 1996 Issue 2 1 TC210 MAXIWAT RANGE OF THYRISTOR SWITCHING UNITS INSTRUCTION MANUAL DESCRIPTION 2 INSTALLATION 3 DIAGNOSTIC AID LEDs 6 SPECIFICATION 7 ORDERING INFO...

Page 2: ...s from any suitable temperature or power controller Rated for up to 102 KW 660V per phase the TC210 family comprises assemblies with line current capacities of 16A 25A 40A 55A 75A 100A 125A and 155A E...

Page 3: ...is as follow the L terminal must be connected to the load supply One end of the load must be connected to the LOAD terminal The other end of the load is returned to the NEUTRAL terminal or LINE 2 or...

Page 4: ...TC210 Instructional Manual Powtier Controls Limited 20 June 1996 4 210IM Issue 2 1 Figure 1a Single phase 16 to 25A wiring Figure 1b Single phase 40 to 55A wiring...

Page 5: ...ntrols Limited TC210 Instructional Manual 210IM 5 20 June 1996 Issue 2 1 Figure 1d Single phase line to neutral connection Figure 1e Single phase line to line connection Figure 1c Single phase 75 to 1...

Page 6: ...in Table 2 A block diagram showing the diagnostic LEDs 1 and 2 is given in figure 2 Only LED1 is fitted to 16A and 25A units Note 1 With the load supply ON the possible faults are a fuse blown or b o...

Page 7: ...110 Vrms 110 240 Vrms 240 Options Protective cover PC End of code 00 For applications other than constant resistive loads or any other currents and voltage ratings not listed above please contact our...

Page 8: ...s C 16 25A 70 106 106 62 85 5 40 55A 124 170 170 110 110 6 75 154 170 170 141 110 6 100 155A 154 1701 200 141 110 6 All dimensions are in mm 1 Due to the fan the overall height is increased by 40 mm S...

Page 9: ...Powtier Controls Limited TC210 Instructional Manual 210IM 9 20 June 1996 Issue 2 1 TC210 25A with soft start wiring diagram...

Reviews: