Powrmatic HEM-NVx Series User, Installation & Servicing Manual Download Page 26

page no. 26 of 44      

    

 

HEMNVx & HEMSL Range  Users, Installation & Servicing Instructions  Doc Ref M103 issue 3.6 Mar 2020. 

Gas Safety (Installation & Use) (Amendment) 

Regulations

It is law that all gas appliances are installed, 

adjusted and, if necessary, converted by 

qualified persons* in accordance with the 

current issue of the above regulations. 

Failure to install appliances correctly can lead to 

prosecution. It is in your own interests and that of safety 

to ensure that the law is complied with. 

* Gas Safe Registered Engineer

Checks to ensure electrical safety must be carried out by 

a qualified person

 

and must include.

i) Ensure that a two pole electrical isolator having a 

minimum separation between pole of 3.0mm is fitted 

adjacent to the module.
ii) That the correct value fuse and cable size has been 

used.
iii) That the module is correctly earthed.
iv) That polarity at the module is correct.
v) That connections to the module are as per the wiring 

diagram.
vi) That the main air fan is interlocked with the module so 

that the module will not function if there is no air flow.
vii) That installation wiring has not been routed adjacent 

to components that will become hot when the module is 

working. e.g. burners, exhaust header box.

For new installations, the whole of the gas installation, 

including the meter, should be inspected and tested 

for soundness and purged in accordance with the 

recommendations of IGE/UP/1 (Edition 2) or IGE/UP/2A 

as appropriate.

 

The following preliminary checks should be made before 

lighting the heater(s)

a) Ensure that the ELECTRICAL supply to the heater is 

switched OFF.

b) Check that all warm air delivery outlets are open.
c) Check that all external controls are calling for heat.
d) Ensure the external control/BMS is set to winter 

operation.
1. Ensure that the gas service valve is closed.

2. Switch on the electrical supply at the isolator and 

the ignition sequence will commence. After a delay of 

approximately 45 seconds the ignition spark will be 

generated and the main gas valve(s) energised.

3. If the limit indicator light comes on press the limit 

thermostat reset switch on the front panel. The Red 

indicator light will go out and the ignition sequence will 

commence. After a delay of approximately 45 seconds the 

ignition spark will be generated and the main gas valves 

energised.

4. The burners will fail to light as the gas service valve is 

closed.

The control box will attempt ignition a further four times 

and then go to lockout and the lockout light/reset switch 

will be illuminated.

5. To restart the ignition sequence depress the lockout 

light/reset switch for about 3 seconds.

NOTE: On initial lighting of the heater(s), it may 

take some time to purge the internal pipe work 

of air.

IMPORTANT: The internal pipe work of the 

appliance has been tested for soundness 

before leaving the factory. After establishing 

the main burners test round the gas inlet 

connection using a leak detection fluid.

1. Switch on the electrical supply at the isolator and 

the ignition sequence will commence.  After a delay of 

approximately 45 seconds the ignition spark will be 

generated and the main gas valve(s) energised.

2. If the burners fail to light the control box will complete 

a further four ignition attempts. If at the end of five 

attempts the burners have still not lit the control box 

will go to lockout and the amber rocker switch will be 

illuminated. To restart the ignition sequence depress the 

illuminated reset button for about 1-2 seconds.

Set the external controls to OFF. If required, once the main 

air fan has stopped or the module is cold, the electrical 

supply to the module can be switched OFF.

Summary of Contents for HEM-NVx Series

Page 1: ...w w w p o w r m a t i c c o u k HEM User Installation Servicing Manual Issue 3 6 Mar 2020 Doc Ref M103 Issue 3 6 Mar 2020 ErP COMPLIANT S E P T E M B E R 2 0 1 8 NVx SL...

Page 2: ...1 The heater must have been installed by a competent qualified installer and in accordance with the manufacturer s instructions building regulations and local regulations 2 The heater has been profes...

Page 3: ...fication of Items 19 2 3 Electrical Cable Installation 20 2 4 Wiring Terminal Connections 20 2 5 Wiring Diagrams 22 2 6 Commissioning and Testing 26 2 7 Servicing 30 Additional Documents 3 1 Fault Fin...

Page 4: ...Unless the cause of the fault condition is readily obvious for example a power cut whilst the heater was operating a service engineer should be contacted E Maintenance To maintain efficient reliable...

Page 5: ...as Group H G20 Appliance Categories are Cat II2H GB IE All units are CE certified and conform to all the European directives stated in section 1 3 1 HEM heaters are based on aluminised mild steel tube...

Page 6: ...mp Rise t C 35 Air Off Max C 70 Airflow Min Airflow m3 s 0 34 0 44 0 58 0 71 0 86 1 01 1 55 1 94 2 28 2 78 2 99 3 39 4 14 4 67 Min Airflow P Pa 43 26 45 32 47 31 59 67 59 54 43 43 47 45 Electrics V ph...

Page 7: ...low P Pa 16 17 20 18 21 15 19 22 19 19 20 21 Electrics V ph Hz 1N 230V 50 Current A 0 30 0 90 3 50 Power kW 0 07 0 21 0 80 Fuel Natural Gas Connection BSP Rc 1 1 Minimum Inlet Pressure mbar 20 Rate m3...

Page 8: ...0 15840 16920 18000 19080 20160 21240 22320 22320 23400 24480 25560 26640 27720 28800 29880 29880 30960 32040 33120 34200 35280 36360 37440 37440 38520 39600 40680 41760 42840 43920 45000 45000 46080...

Page 9: ...0 13680 15120 16560 18000 19440 20880 20880 22320 23760 25200 26640 28080 29520 30960 30960 32400 33840 35280 36720 38160 39600 41040 41040 42480 43920 45360 46800 48240 49680 51120 51120 52560 54000...

Page 10: ...HEMNVx 125 15 9 6 2 54 750 10 8 13 4 5 0 9 2 HEMNVx 150 18 9 9 2 54 750 10 5 16 3 4 6 10 6 HEMNVx 175 21 12 9 2 54 750 11 0 18 4 5 0 13 3 Injector Sizes Burner Pressures Natural Gas Group H G20 Net CV...

Page 11: ...HEMNVx 110 13 109 9 98 0 75 0 66 0 3 0 10750 145 21 HEMNVx 125 15 126 4 112 0 86 5 76 5 3 4 12200 168 25 HEMNVx 150 18 153 9 134 9 100 2 78 8 4 1 14900 195 30 HEMNVx 175 21 174 0 154 4 125 7 112 8 4 7...

Page 12: ...ing should be consulted at the installation planning stage in order to establish the availability of an adequate supply of gas to suit the building requirements An existing service pipe must not be us...

Page 13: ...supply of air is necessary 1 3 4 3 Type C flued installations Where AHU s are installed in a plant room ie not within the heated space having g combustion air ducted to the appliance and combustion pr...

Page 14: ...19 8 439 6 219 8 1099 0 1099 0 549 5 549 5 HEMNVx 125 15 126 4 252 8 505 6 252 8 2528 0 2528 0 1264 0 1264 0 HEMNVx 150 18 153 9 307 8 615 6 307 8 n a HEMNVx 175 21 174 0 348 0 696 0 348 0 Type B22 In...

Page 15: ...or external units please note The lowest edge of air inlets must be at least 500 mm above ground level Access panels and doors to be removed during normal servicing shall be designed so that repeated...

Page 16: ...4 181 142 150 18 1347 204 181 142 175 21 1554 204 181 142 A B HORIZONTAL FLUE POSITION D HOLE FOR FLUE SEAL C A B HORIZONTAL FLUE POSITION D HOLE FOR FLUE SEAL C HORIZONTAL FLUE POSITION D HOLE FOR FL...

Page 17: ...uld be cut to the dimensions in the following table to accept the silicone seals supplied where D is the actual cut size in the casing sheet metal Type C Flue and air inlet cut hole sizes and centres...

Page 18: ...ttings in which case ensure that the dimensions shown are adhered to The trap must be filled with water after installation and before the heater is commissioned The trap and associated pipe work must...

Page 19: ...ing Electrical Connection Point Limit Indicators Lockout Indicators Fuses Burner Set behind Heat Shield Exhaust Fan Exhaust Header Box Spark Ignition Probe Gas Valv Inlet Control Panel Exhaust Fan Flo...

Page 20: ...eater s via a suitable fused isolator that will prevent remote activation of the heater during servicing see section 1 2 for ratings be in a readily accessible position adjacent to the heater s serve...

Page 21: ...ication 230V Output Lockout 1 Reset Neutral Input Main fan Proving Switch suppled by others Modulating Ground 0V Lockout 2 Indication 230V Output Lockout 2 Reset Neutral Input t3 t10 t8 t9 t4 t5 t6 t7...

Page 22: ...Internal Lockout Reset Button J Hylec Terminal Block 3 Way K Terminal Block L Ignition Electrode M Rectification Probe N O P Heat Demand 230V Input Heat Hi Demand 230V Input Lockout 1 Indicator 230v...

Page 23: ...K Terminal Block L Ignition Electrode M Rectification Probe N O P Br 0 5 Blu 0 5 Blu 0 5 Br 0 5 Blu 0 5 Br 0 5 Wiring Legend Heat Demand 230V Input Heat Hi Demand 230V Input Lockout 1 Indicator 230v...

Page 24: ...E E E N N N N 1 1 3 3 4 4 5 5 6 6 10 10 11 11 12 12 15 15 16 16 9 9 7 8 NC NO C 2 3 1 LIVE NEUTRAL EARTH Br 0 5 Br 0 5 Blu 0 5 Blu 0 5 Blu 0 5 Blk 0 5 Red 0 5 Yel 0 5 Wh 0 5 Br 0 5 Br 0 5 Blu 0 5 Wh...

Page 25: ...ch Supplied by Others Br 0 5 Br 0 5 Blu 0 5 Or 0 5 Yel 0 5 Or 0 5 External Controls Connections 1 2 3 4 5 6 7 8 9 10 11 12 16 17 18 19 13 14 15 J5 CON6 J6 CON5 JT2 JT1 1 1 1 Blu 0 5 1 2 3 4 5 6 7 8 9...

Page 26: ...Ensure the external control BMS is set to winter operation 1 Ensure that the gas service valve is closed 2 Switch on the electrical supply at the isolator and the ignition sequence will commence Afte...

Page 27: ...6 1 1 1 SIT Sigma 843 Adjustment Adjustment nut 10mm for maximum pressure setting Cap Adjustment screw for minimum pressure setting Maximum Setting With the controls set to high fire use an adjustable...

Page 28: ...res proceed as follows after removing the plastic cover from the Modulating regulator Note Minimum fire setting must be adjusted first after which the high fire setting can be set Any adjustment of th...

Page 29: ...V7335A is controlled by P1 varying between 50 and 100 of the input signal E g When P1 is set at 100 fully clockwise maximum power 165mA 22VDC is provided to the modulation coil with a 10VDC input con...

Page 30: ...vicing work has been complete or any component replaced the air heater s must be fully commissioned and tested for soundness as described in Section 2 6 2 6 Commissioning and Testing 2 6 6 2 Final Adj...

Page 31: ...electrode is located at the top of the burner assembly Inspect the electrodes making sure that they are in a sound and clean condition In particular check that the ignition electrode is clean and und...

Page 32: ...ssembly to the burner assembly side plate and withdraw the assembly 3 Fit replacement and reassemble in reverse order Check that the spark gap is 2 5mm See section 2 7 3 and the rectification electrod...

Page 33: ...gas supply is ON Exhaust fan runs continuously Electrical 1 Check overrun thermostat 3 1 Fault Finding 3 Whilst supporting the fan motor remove the three screws securing the fan motor mounting plate t...

Page 34: ...2 Rectification Flame Sensor Probe All 142423003 Burner All 142400240 Limit Thermostat All 142403611 Control Box Sequence Controller All High Low All Modulation 145030846 145030847 High Low Governor H...

Page 35: ...Switch HUBA 604 All 142522177 Exhaust Fan 10 50 140210496 Exhaust Fan 60 75 140201505 Exhaust Fan 100 140210499 Exhaust Fan 110 150 140201503 Exhaust Fan 175 140201502 Exhaust Fan 200 140201507 Brahma...

Page 36: ...eat Capacity kW 66 0 76 5 78 8 112 8 Gross Efficiency High Fire 80 0 80 0 79 0 80 0 Low Fire 81 0 80 0 81 0 82 0 Nett Efficiency High Fire 88 8 88 8 87 7 88 8 Low Fire 89 9 88 8 89 9 91 0 Seasonal Eff...

Page 37: ...nt 125 16 150 18 175 21 200 24 Rated Heat Capacity kW 116 7 135 7 160 8 178 3 Minimum Heat Capacity kW 70 5 79 9 82 6 108 3 Gross Efficiency High Fire 82 0 80 0 79 0 78 0 Low Fire 83 0 80 0 84 0 81 0...

Page 38: ...o be extended to a point where it has clearance from windows doors The following notes and sketches refer to Fluing Combustion Air and Ventilation requirements for modules fitted as stand alone applic...

Page 39: ...thin a secondary housing ahu etc Internal location HEM SL HEM NVx within open space ie not plant room Single module c w Powrmatic burner enclosure Combustion air to Powrmatic burner enclosure via Powr...

Page 40: ...Internal location HEM SL HEM NVx within a plant room as defined by BS6230 Single module c w Powrmatic burner enclosure Combustion air ventilation requirements in accordance with BS6230 Plant room vent...

Page 41: ...page no 41 of 44 HEMNVx HEMSL Range Users Installation Servicing Instructions Doc Ref M103 issue 3 6 Mar 2020 Notes...

Page 42: ...page no 42 of 44 HEMNVx HEMSL Range Users Installation Servicing Instructions Doc Ref M103 issue 3 6 Mar 2020 Notes...

Page 43: ...page no 43 of 44 HEMNVx HEMSL Range Users Installation Servicing Instructions Doc Ref M103 issue 3 6 Mar 2020 Notes...

Page 44: ...laght Dublin 24 tel 353 0 1452 1533 fax 353 0 1452 1764 e mail info powrmatic ie web www powrmatic ie Getting In Touch Powrmatic pursues a policy of continues improvement in both design and performanc...

Reviews: