![Powerware PW5110 User Manual Download Page 2](http://html1.mh-extra.com/html/powerware/pw5110/pw5110_user-manual_1592109002.webp)
BATTERY REPLACEMENT PROCEDURE:
1.
Disconnect the UPS from the power source and slide the battery door open.
See pictures 1 and 2.
2.Disconnect the battery and remove as indicated below. See pictures 3 and 4
3.Insert the replacement battery and reconnect the battery cables.
See pictures 6 and 7
NOTE:
It is important that the connectors be firmly attached to new batteries.
4.Reposition the battery door and slide closed. See pictures 8 and 9.
NOTE:
Properly recycle used battery.
4.5AH, 5AH batteries (350VA, 500VA models)
STATUS INDICATORS
The UPS provides both visual and audible status indicators. Visual indicators
consist of three LEDs to represent the following conditions:
On utility power operation
On battery power operation
UPS fault/alarm
LED Indicator Table
On Utility (AC mode)
On Battery (Backup mode)
Low Battery
Fault/Output Short
Overload/Check Battery
Green Lighting
Yellow Lighting
Yellow Flashing
Red Lighting
Red Flashing
LED Audible Alarm Table
Backup mode
Battery low
Overload
Replace battery
Fault or output short circuit
Battery over charge
Sounding every 5 seconds
Sounding (two beeps) every 5 seconds
Sounding every 0.5 seconds
Sounding (three beeps) every 30 seconds
Continuous sounding
Sounding (three beeps) every 5 seconds
7AH x 2, 9AH x 2 batteries (1000VA, 1500VA models)
7AH x 1 battery (700VA models)
1
2
3
4
5
6
7
8
9
1
2
3
4
5
6
7
8
9
1
2
3
4
5
6
7
8
9
SPECIFICATIONS
PW5110 350A
PW5110 500A
PW5110 700A
PW5110 1000A
PW5110 1500A
Model Numbers
350 VA / 210W
500 VA / 300W
700 VA / 420W
1000 VA / 600W
1500 VA / 900W
Capacity
Nominal Output Voltage
Nominal Input Voltage
240Vac
240Vac
Automatic Voltage Regulation (AVR)
Frequency
Outlets
15%
50 / 60 Hz auto sensing
6 Outlets (3 Battery Backup & Surge Protection;
3 Surge Protection only)
Lighting / Surge Protection
Transfer time to Battery/AC
Battery Type
476 Joules
6ms typical
Maintenance free lead-acid battery
Battery Specification
Typical Backup Time
LAN / Phone / Fax Protection
Short Circuit Protection
Communication Port
Operation Temperature
Operation Relative Humidity
Storage Temperature
350 VA: 12V 4.5 Ah
500 VA: 12V 5 Ah
750 VA: 12V 7 Ah
1000 VA: (2) 12V 7 Ah x 2
1500 VA: (2) 12V 9 Ah x 2
3 MINUTES MINIMUM AT FULL RATED LOAD
RJ11
Circuit Breaker
USB
0 C~40 C
0 to 95% non-condensing
-15 C~50 C
350 VA: 5.9 kg
500 VA:6.1 kg
700 VA: 7.5 kg
1000 VA: 13.2 kg
1500 VA: 13.7 kg
350/500/700 VA: 270 x 87 x 259mm
1000/1500 VA: 270 x 87 x 384mm
Net Weight
Dimensions (HxWxD)
* Due to continuing product improvement programs, specifications are subject to change
without notice.
TROUBLESHOOTING
Symptom
Possible Cause
Action to Take
Ensure the UPS is securely
connected to an AC outlet.
Reduce the amount of equipment
plugged into the “Battery Backup &
Surge Protection” outlets of the
UPS. Reset the circuit breaker by
pushing it back in. Switch the UPS
back on.
The UPS is not connected
to the power source.
Circuit Breaker has
tripped.
UPS will not turn on
UPS is making a
continuous sound and the
“Overload” indicator is on
The “Battery Backup &
Surge Protection” outlets
are overload.
Turn off the UPS and reduce the
amount of equipment connected to
these outlets.
The UPS battery is
discharged due to a power
outage and has not
recharged.
Charge the battery for 8 hours. The
UPS runtime is reduced until the
battery is fully charged.
Unplug non-essential equipment
(printers, scanners, etc) from the
Battery Backup outlets and plug
into 'Surge Only' outlets
UPS does not provide
expected runtime
Disconnect non-essential equipment
from the UPS. Reset (push in) the
circuit breaker and switch the UPS on.
Plug equipment in one-at-a-time. If
the circuit breaker trips again,
disconnect the device that caused the
breaker to trip.
Replace the battery or the battery
module.
Unplug device from 'Surge Only' outlet
and move to a 'Battery Backup outlet.
The UPS circuit breaker
tripped
.
The battery has reached
the end of its life.
Equipment plugged into a
Surge Only outlet.
Red LED Indicator ON
Internal UPS fault.
Contact Technical Support (see
Service and Support below).
UPS does not power
essential equipment
during an outage
SERVICE AND SUPPORT
MA6B412008(2005/01/20)
Devices plugged into Back
up & surge protection
receptacles exceed the
rated load for the UPS run
time
Please have the following information ready:
Model number and serial number
Symptoms of failure or problem
Customer contact information
For additional information and to register your warranty, please visit
www.powerware.com.au
Register your warranty within 30 days and receive an extended pro-rated
warranty and load protection guarantee.
Eaton Power Quality Pty Ltd
119-127 Wicks Road,
North Ryde NSW 2113
For service and support please call your local distributor or the Powerware
Australia National Service and Repair Centre.
Australia freecall 1300 303 059.