Installation
4
BestLink SNMP/WEB Adapter User’s Guide
:
LTM-1343 B
Draft 10/03/2001
Set both DIP switches
to the
0
(off) position
1
0
Slide the adapter into
the UPS BestDock
Figure 2. Installing the Internal BestLink Adapter
4.
Set both DIP switches on the adapter to the
0
(off) position.
5.
Connect an active 10BaseT cable to the network connector on the
BestLink Adapter.
NOTE
For an internal BestLink Adapter in a FERRUPS 0800, Axxium Pro, or Powerware 9170
UPS, you MUST change the Config BestDock parameter for that UPS to BestDock 1 or 2 as
applicable. Refer to the UPS user’s guide for detailed instructions on how to change the
parameter through the UPS front panel configuration menu.
6.
Continue to “Configuration” on page 6.
Installing the External BestLink Adapter
To install the external BestLink SNMP/WEB Adapter, perform the following
steps:
1.
Verify that the UPS is turned off.
2.
Use the supplied serial cable labeled “UPS” to connect the UPS port
on the BestLink Adapter to the UPS communication port.
If connecting to a FERRUPS model with a DB-25S communication
port, you must also use the supplied DB-9 to DB-25 adapter labeled
INT-0013B.
3.
Set both DIP switches on the adapter to the
0
(off) position.
Summary of Contents for BestLink IPK-0319
Page 4: ......
Page 24: ...Remote Configuration 18 BestLink SNMP WEB Adapter User s Guide LTM 1343 B Draft 10 03 2001...
Page 32: ...UPS Power Management 26 BestLink SNMP WEB Adapter User s Guide LTM 1343 B Draft 10 03 2001...
Page 42: ...Appendix 36 BestLink SNMP WEB Adapter User s Guide LTM 1343 B Draft 10 03 2001...
Page 43: ......
Page 44: ...38 BestLink SNMP WEB Adapter User s Guide LTM 1343 B Draft 10 03 2001 LTM 1343 B...