UPS  status/user  setting 
display String 

Strings Indicate the UPS status( see Table 4) 
Strings Indicate user setting options( see Table 5) 

 

Warning indication 

Lights on when the UPS is failure or alarm. 

 

Settings  

Lights on when the UPS under settings mode. 

 

Battery  volume  level 
display 

Indicates  the  amount  of  battery  volume  remaining. 
Each battery volume level bar indicates approximately 
20% of total battery volume 

 

Load Power level display 

Indicates  the  load  level  of  the  UPS.  Each  level  bar 
indicates  approximately  20%  of  the  total  UPS  output 
Power. 

 
IV.

 

Rear Panels 

VI 1000 ERT 

1.

 

AC Output   

2.

 

Network Surge 
Protection   

3.

 

Intelligent Slot  

4.

 

AC Input  

5.

 

RS232 / Dry-
Contact Port 

6.

 

USB Port 

7.

 

EPO 

8.

 

Grounding 

 

VI 1000 RT and VI 1500 RT 

 

VI 2000 RT 

1.

 

AC Output   

2.

 

Network Surge 
Protection   

3.

 

Intelligent Slot 

4.

 

Fan 

5.

 

AC Input 

6.

 

RS232 / Dry-
Contact Port 

8

7

6

5

1

2

4

3

1

N

E

T

W

O

R

K

/T

E

L

E

P

H

O

N

E

P

R

O

T

E

C

T

IO

N

IN

P

U

T

2

2

0

-2

4

0

V

~

INTERFACE OPTION

EPO

USB

RS232

O

U

T

IN

L

S

2

O

U

T

P

U

T

2

5

K

V

~

1

0

A

L

S

1

O

U

T

P

U

T

2

5

K

V

~

1

0

A

L

S1

OU

T

PU

T

2

5

KV

~

1

0

A

L

S2

OU

T

P

U

T

2

5

KV

~

1

0

A

1

4

1

3

7

5

6

8

9

2

I

N

O

UT

NE

T

WO

RK

/T

EL

E

PH

ON

E

PR

O

TE

CT

IO

N

INTERFACE OPTION

EPO

USB

RS232

I

NP

U

T

2

20

-

24

0

V~

Summary of Contents for VI ERT HID Series

Page 1: ...ore than 3s release Press long Press and hold for more than 10s release Control Button Switch Function ON OFF Press to turn on or off the UPS Press to release the UPS from faulty mode Cut off input power and then press to shut down the UPS Test Alarm Silence Press the button to perform basic function test Press long to to perform battery life test Click to disable alarm buzzer Select Press the Sel...

Page 2: ...evel of the UPS Each level bar indicates approximately 20 of the total UPS output Power IV Rear Panels VI 1000 ERT 1 AC Output 2 Network Surge Protection 3 Intelligent Slot 4 AC Input 5 RS232 Dry Contact Port 6 USB Port 7 EPO 8 Grounding VI 1000 RT and VI 1500 RT VI 2000 RT 1 AC Output 2 Network Surge Protection 3 Intelligent Slot 4 Fan 5 AC Input 6 RS232 Dry Contact Port 8 7 6 5 1 2 4 3 1 NETWORK...

Page 3: ...ry contacts are not available for VI ERT series VII Extension Slot UPS allows extending communication means by extension cards Please check product website for list of accessories VIII UPS Initial Startup 6 Verify that the internal batteries behind front panel and optional battery packs are connected 7 Plug the equipment load but do not turn it on 8 Plug in the UPS input power cord The UPS front p...

Page 4: ...t Load segments are groups of outlets that can be configured through the display VI RT HID models have two configurable load segments excluding VI ERT HID When UPS is turned on it has activated output you can turn off a load segment If the UPS is turned off no output then a load segment cannot be turned on XII Configuring EBM quantity Setting correct EBM External Battery Module quantity is critica...

Page 5: ...ng every second OVLD on the screen Battery Replacement Sounding every second Alarm can be muted when it is activated but it will sound in case of low battery fan fault overheat and other major fault XVI Technical Specification Model 1000 ERT 1000 RT 1500 RT 2000 RT 3000 RT Power Watt 900W 900W 1350W 1800W 2700W Input Input voltage range 161 276VAC Frequency range 50 60Hz 5Hz for Normal Mode 40 70H...

Page 6: ...H Temperature 0 to 40 C Humidity 20 80 relative humidity non condensing Altitude 1500m Storage Temperature 15 to 45 C Net weight 15 0kg 17 8kg 17 8kg 27 8kg 27 8kg Dimensions 438 X 86 5 x 436 438 X 86 5 x 608 ...

Reviews: