TECHNICAL SPECIFICATIONS 

 
 

DEFINITIONS FOR ILLUMINATED LCD INDICATORS 

 
LCD Indication

 

 

 

 

 

 

 

 

Setting Item 

 
 

Line mode 

 

 

Fault 

 

Bat-mode 

 

 

Fault 

 

Sound disable 

(Press the display key 3s to disable and 

enable the buzzer sound) 

 

 

 

Bat mode: battery capacity 
Line mode:   
1. Battery charging: cycle lighting 
2. Battery full charged: lighting 
3. Line mode without charger: battery 
capacity 

 

Load capacity 

 

Line mode & Batt. Mode 
 

 

 

 

Initial 

AC INPUT(Voltage) 

 

OUTPUT 

(Voltage) 

 

 

TROUBLE SHOOTING

 

 

Problem 

Possible Cause 

Solution 

The UPS does not perform 
expected runtime. 

Batteries are not fully charged. 

Recharge the battery by leaving the UPS plugged in. 

Battery is slightly worn out. 

Contact Technical Support. 

The UPS will not turn on. 
 

The on/off switch is designed to 
prevent damage by rapidly turning 
it off and on. 

Turn the UPS off. Wait 10 seconds and then turn the UPS 
on. 

The unit is not connected to an AC 
outlet. 

The unit must be connected to a 220-240V 50Hz outlet. 

The battery is worn out. 

Contact Technical Support. 

Mechanical problem. 

Contact Technical Support. 

Outlets do not provide power 
to equipment 

Fuse is blown due to overload 

Turn the UPS off and unplug at least one piece connected 
equipment. Unplug the power cord of the UPS then remove 
the fuse compartment beneath the power inlet of the UPS 
and replace the blown fuse with a spare one. Lock the 
compartment back to the UPS. Connect power cord then turn 
the UPS on. Make sure that your spare fuse meets the 
specification. 

Batteries are discharged 

Allow the unit to recharge for at least 4 hours. 

Unit has been damaged by a 
surge or spike. 

Contact Technical Support. 

Software is inactive 

The network cable is not 
connected. 

Connect the network cable to the UPS unit and a network 
port on the hub.   

Software setting problem. 

Please read and follow NetAgent utility instruction during 
installation and operation of the NetAgen software, or contact 
technical support. 

 

All rights reserved. Reproduction without permission is prohibited. 

 

Model 

 

VI 500 R1U 

VI 750 R1U 

Capacity  (VA) 

500VA 

750VA 

Capacity  (Watts) 

300W 

450W 

Input 

Input Voltage Range 

165V~290V 

Frequency Range 

50Hz +/- 5 Hz 

Output 

On Battery Output Voltage 

Sine Wave at /-10% 

On Battery Output Frequency   

50Hz +/-1% 

Overload Protection 

On Utility: Fuse, On Battery: Internal Current Limiting 

AVR Function 

Boost Function 

Yes                                                                                                                                                             

Buck Function 

Yes 

Physical

 

Total # of UPS Receptacles 

IEC C13 x 4 

IEC C13 x 4 

Maximum Dimensions   
(H x D x W) 

44mm x 216mm x 433mm 

Weight (Kg) 

7.6 

8.6 

Battery

 

Sealed Maintenance Free Lead Acid 
Battery 

6V / 7AH x2 

6V / 9AH x2 

Typical Recharge Time 

8 Hours 

Warning Diagnostics 

Indicators 

Using AC / Using Battery / Fault 

Communication

 

Software

 

Windows 2000 / XP /7/8/10/ Server 2003 / Vista / Server 2008 

Environmental

 

Operating Temperature 

  0

°

C to 40

°

Operating Relative Humidity 

0 to 90% NON-CONDENSING 

Management

 

Auto-Charger 

Yes 

Auto-Restart 

Yes 