Connection of the UPS 

The  UPS  should  be  protected  with  circuit  breaker  on  the 
input.  Minimum  rating  should  10A  for  1000VA,  12A  for 
1500VA, 16A for 2000VA and 20A for 3000VA. For output 
connection  please  use  original  cables  and  share  the  load 
equally among outlets.

 

VI.

 

Connecting Battery Packs 

Remove front  panel, connect  the battery via Anderson PP45 connectors. Make sure you 
are connecting with correct polarity (red to red, black to black). Make sure the wires are 
connected tight. Close front panel. Setup the amount of battery packs in the settings. 

VII.

 

Communication Ports 

A  Local  communication  with  the  software  can  be 
established via USB or RS232 connector. Alternatively UPS 
can be controlled using dry contacts. 

VIII.

 

DB9 Female (RS232) pin description 

PIN # 

Signal name 

Function 

Direction from the UPS 

Tx 

Transmit to external device 

Out 

Rx 

Receive from external device 

In 

GND 

Signal common (tied to chassis) 

Not applicable 

Other 

 

Not Used 

 

Dry contacts are not available for VI ERT series. 

IX.

 

Dry contact port and EPO 

The  relay  output  contact  must  not  be  connected  to  any  utility  connected  circuits. 
Reinforced insulation to the utility is required. The relay output contact has a maximum 
rating of 30Vac/1A. 

 

 

The  signal  input  to  control  UPS  On/Off  status  is  the  same  as  one  button  to  control  UPS 
On/Off status. The relay output can be configured by protocol command: 

Dry out signal 

Description 

Summary Alarm 

[DEFAULT] 

Activated when any warning happens 

Dry contact input / EPO 

USB Port 

AC Input  

Dry contact output 

Intelligent Slot 

RS232 

Earth Line Port 