F10  High input current 

ON 

OFF 

0.5s ON / 1.0s 

OFF 

F11  Power Fail on Auxiliary 1 

ON 

OFF 

ON 

F12  Power Fail on Auxiliary 2 

ON 

OFF 

ON 

L01  Lock for overload on Output 1 

ON 

OFF 

ON 

L02  Lock for overload on Output 2 

ON 

OFF 

ON 

L03  Lock for overload on Output 3 

ON 

OFF 

ON 

L04  Lock for overload on Output 4 

ON 

OFF 

ON 

L05  Lock for overload on Output 5 

ON 

OFF 

ON 

L06  Lock for overload on Output 6 

ON 

OFF 

ON 

L07  Lock for overload on Output 7 

ON 

OFF 

ON 

L08  Lock for overload on Output 8 

ON 

OFF 

ON 

L13  High input voltage 

ON 

OFF 

ON 

 

NOTE: 

The output lock due to overload is permanent and only can be reset by switching 

on the locked output again. Please simply press the ON/OFF button to turn on the output. 
 

 

Summary of Contents for PDU RC-16A

Page 1: ...Power Distribution Unit Version 1 0 User Manual PowerWalker PDU RC 16A...

Page 2: ...1 1 1 Package Contents 1 1 2 Safety 1 1 3 Disposing of PDU 1 1 4 Function 1 1 5 Overview 2 2 Installation 3 2 1 Rack Mounting 3 2 2 Connections 3 3 Operation Display 4 3 1 Panel Overview 4 3 2 Operati...

Page 3: ...in a temperature and humidity controlled indoor environment Ambient temperature must not exceed 50 C The PDU is not intended for outdoor use 1 3 Disposing of PDU The PDU contains internal components t...

Page 4: ...MUTE FUNCTION button to silence the buzzer RS232 communication port Expansion slot for communication boards SELECT button to toggle the different status screens in LCD display Output IEC 10A sockets...

Page 5: ...n a 19 inch bay with a depth of 600mm at the desired height in the cabinet uprights Secure the device adequately to cabinet with four screws 2 2 Connections For connecting the PDU plug the input to th...

Page 6: ...et icon on output on icon off output off icon blinking output overload alarm overload or output shutdown due to overload Fault code please check section 3 2 4 for detailed codes 3 2 Operation The LCD...

Page 7: ...on The displayed information is switched as below order Total input voltage input current input voltage output current for each active numerical plug and fault codes Information LCD Display Input Volt...

Page 8: ...one Turn on selected output socket To switch on a numerical output socket you have to switch to specific plug number shown on left corner by keep pressing SELET button Then press ON OFF button 1 to 2...

Page 9: ...ound again If one or more alarms occur after buzzer has been mute the buzzer will sound again Function Operation It s to switch displayed information on specific output The displayed information is ou...

Page 10: ...N 0 5s OFF S06 Immediate shutdown on Output 6 Blinking OFF 0 5s ON 0 5s OFF S07 Immediate shutdown on Output 7 Blinking OFF 0 5s ON 0 5s OFF S08 Immediate shutdown on Output 8 Blinking OFF 0 5s ON 0 5...

Page 11: ...utput 3 ON OFF ON L04 Lock for overload on Output 4 ON OFF ON L05 Lock for overload on Output 5 ON OFF ON L06 Lock for overload on Output 6 ON OFF ON L07 Lock for overload on Output 7 ON OFF ON L08 Lo...

Page 12: ...68KVA at 230V Overload Protection 16A Breaker Output Nominal Output Voltage 220V 230V 240V Rated Output Voltage 184 300V Output Connections 8 IEC C13 Output Current Accuracy 0 1A Physical Dimensions...