afet' of persons
Terminal blocks may be energized even if the system is disconnected from the AC
power source.
Dangerous voltage levels are present within the system. It should be opened exclusively
by qualified service personnel.
The system must be properly grounded, always connect the earth wire first.
Product safety
The MBP connection instructions and operation described in the manual must be
followed in the indicated order.
CAUTION - To reduce the risk of fire, the unit connects only to a circuit provided with
branch circuit overcurrent protection for:
63A rating, for 6kVA models,
80A rating, for 10kVA models
The upstream circuit breaker for Normal AC/Bypass AC must be easily accessible. The
unit can be disconnected from AC power source by opening this circuit breaker.
Disconnection and overcurrent protection devices shall be provided by others for
permanently connected AC input (Normal AC/Bypass AC) and AC output circuits.
Check that the indications on the rating label correspond with your AC powered system
and the actual electrical consumption of all the equipment to be connected to the
system.
For PLUGGABLE EQUIPMENT, the socket-outlet shall be installed near the equipment
and shall be easily accessible
Never install the system near liquids or in an excessively damp environment.
Never let a foreign body penetrate inside the system.
Never block the ventilation grates of the system.
Never expose the system to direct sunlight or source of heat.
If the system must be stored prior to installation, storage must be in a dry place.
The admissible storage temperature range is -25°C to +60°C.
Special precautions
This MBP is designed to work with UPS.
All repairs and service should be performed by AUTHORIZED SERVICE PERSONNEL ONLY.
There are NO USER SERVICEABLE PARTS inside the MBP.