Overload bypass:
When enabled, the
unit will transfer to line
mode if overload
occurs in battery
mode.
Bypass disable (default)
Bypass enable
25
Record Fault code
Record enable (default)
Record disable
26
Bulk charging voltage
(C.V voltage)
56.4V (default)
If “User-Defined” is selected in
program 5, this program can be set
up. Setting range is from 48.0V to
64.0V. Increment of each click is
0.1V.
27
Floating charging
voltage
54V (default)
If User-Defined” is selected in
program 5, this program can be set
up. Setting range is from 48.0V to
64.0V. Increment of each click is
0.1V.
28
AC output mode
*This setting is only
available when the
inverter is in standby
mode (Switch off).
Single: This inverter is used in
single phase application.
Parallel: This inverter is operated in
parallel system.
L1 phase:
L2 phase: