ACE Series – Owner’s Manual – 03/17/09
away from any sharp metal edges.
9.3.5 Install the battery cables in such a way that the UPS battery mounting bracket cannot pinch them.
9.3.6 Do not connect the battery terminal to Ground.
If any battery terminal is inadvertently grounded, remove the source of the ground.
Contacting any part of a grounded battery can cause a risk of electric shock.
x
When replacing batteries, replace with
12Volt/34Watt cell and exact quantity as listed below based on UPS VA
rating:
x
600VA – 2 batteries
x
1000VA – 2 batteries
x
1500VA – 3 batteries
x
2000VA – 4 batteries
x
Please call your local POWERVAR representative for pricing and availability.
9.5
Hot Swappable Battery Replacement
Tower Procedure -
Step 1.
Remove front cover panel; pull out from top where finger grooves are located on each side. (See diagrams
below)
600 & 1000VA
1500 & 2000VA
Step 2.
Push down slightly to allow front cover to be moved to the side. (See diagrams below)