MM430_For_PS-Sheet_Test_1.pdf
Page 1
09/14/2007
The Hydroguard
®
XP MM430 and LFMM430 series is a tem-
perature actuated mixing valve designed for use in hot water
distribution systems, in compliance with ASSE 1017.
Description
n
Table 1, Capacity Tables, present the Hydroguard discharge capacity in gpm and l/m for various pressure differentials (the dif-
ference between the lowest inlet pressure and the discharge pressure at the Hydroguard).
Capacity
n
Maximum Operating Pressure ............................. 125 psi (861 kPa)
Maximum Hot Water Temperature ...................... 200°F (93°C)
Minimum Hot Water Supply Temp . ..................... 5°F (3°C) Above Set-Point*
Temp. Adjustment Ranges ** Standard: .............. 90 - 160°F (32 - 71°C)
Low: ......................... 60 - 90°F (16 - 32 C)
Hot Water Inlet Temperature Range ................... 120 -180°F (49 - 82°C)
Cold Water Inlet Temperature Range ................. 40 - 80°F (4 - 27°C)
Listing ........................................................................ ASSE 1017
Certified .................................................................... CSA B125
* With Equal Pressure
**
NOTE:
Low limit cannot be less than the cold water temperature.
For best operation, hot water should be at least 5°F (3°C) above desired set
point.
Specifications
n
* Minimum flow when Hydroguard is installed at or near hot water source with recirculated tempered water with continuously operating recirculating pump.
HYDROGUARD
®
XP
Master Tempering Valves
Series MM430 and LFMM430
Technical Instructions
Flow Capacity at 50-50 mixed ratio
P r e s s u r e D r o p A c r o s s V a l v e
Model
Min.
Min. Flow
5psi
10psi
20psi
30psi
45psi
60psi
70psi
Flow Rate*
to ASSE 1017
C
V
(34 kPa)
(69 kPa)
(138 kPa)
(207 kPa)
(310 kPa)
(414 kPa) (517 kPa)
MM431 and
LFMM431
0.5 gpm
3 gpm
6.32
14 gpm
20 gpm
28 gpm
35 gpm
42 gpm
49 gpm
53 gpm
1.89 lpm
11 lpm
53 lpm
76 lpm
106 lpm
132 lpm
159 lpm
185 lpm
201 lpm
MM432 and
LFMM432
0.5 gpm
4 gpm
9.49
21 gpm
30 gpm
42 gpm
52 gpm
64 gpm
74 gpm
79 gpm
1.89 lpm
15 lpm
80 lpm
114 lpm
159 lpm
197 lpm
242 lpm
280 lpm
299 lpm
MM433 and
LFMM433
0.5 gpm
5 gpm
16.44
37 gpm
52 gpm
74 gpm
90 gpm
110 gpm
127 gpm 138 gpm
1.89 lpm
19 lpm
140 lpm
197 lpm
280 lpm
341 lpm
416 lpm
481 lpm
522 lpm
MM434 and
LFMM434
0.5 gpm
7 gpm
21.50
48 gpm
68 gpm
96 gpm
118 gpm
144 gpm
167 gpm
180 gpm
1.89 lpm
26 lpm
182 lpm
257 lpm
363 lpm
447 lpm
545 lpm
632 lpm
681 lpm
MM435 and
LFMM435
0.5 gpm
10 gpm
31.00
69 gpm
98 gpm
139 gpm
170 gpm
208 gpm
240 gpm
259 gpm
1.89 lpm
38 lpm
261 lpm
371 lpm
526 lpm
644 lpm
787 lpm
908 lpm
980 lpm
IS-P-MM430
Advanced Thermal Activation
WARNING
!
TO ENSURE THE ACCURATE AND
RELIABLE OPERATION OF THIS PRODUCT,
IT IS ESSENTIAL TO:
• Properly size each valve based on the
individual application.
• Properly design the recirculation system
to minimize pressure and temperature
variations.
• Conduct an annual maintenance pro-
gram to ensure proper operation of all
critical components.
THIS VALVE MUST BE USED IN
CONJUNCTION WITH TEMPERATURE
ACTUATED POINT-OF-USE DEVICES
THAT COMPLY WITH ASSE 1016, 1069, OR
1070.
FAILURE TO COMPLY WITH PROPER
INSTALLATION INSTRUCTIONS COULD
CONTRIBUTE TO VALVE FAILURE,
RESULTING IN IN JURY OR DEATH.