1. Flush all piping thoroughly before installing.
2. Locate HydroGuard
®
as close as possible to the fi xture being supplied
3.
Consult proper medical/safety authorities for the optimum
temperature for your application. Before use, check for proper
discharge temperature. Reset if necessary. Valve is preset for
85°F (29°C)
Prior to Installation
■
1. Open emergency fi xture to allow fl ow through HydroGuard
®
2. Loosen adjustment locking setscrew on the side of the orange top
3. Use special wrench (provided with the valve) to adjust the dis-
charge tempered water. Place wrench at temperature adjust-
ment screw. Turn screw counterclockwise to full hot position
4. Turn clockwise to desired temperature. Allow valve temperature
to settle before making next adjustment.
5. When desired temperature is set, tighten the adjustment lock-
ing screw. Remove special wrench and keep in a safe place for
future use
6. Close emergency fi xtures
Temperature Adjustment
■
1. Open emergency fi xture
2. Close hot water checkstop
3. Verify there is adequate fl ow at the emergency fi xture
4. If there is less fl ow than required, adjust cold water bypass fl ow
as follows:
a) Loosen the locknut at the top of the cold water bypass. This
must be all the way out to allow full range of adjustment
b) To increase bypass fl ow, turn adjusting screw clockwise or
turn counterclockwise to reduce fl ow
NOTE: Improper setting of cold water bypass may lead to con-
tinuous cold water fl ow that will effect tempered water setting.
c) Once proper fl ow conditions are set, tighten the locknut
d) Open hot water checkstop
NOTE:
For any problems, refer to Troubleshooting section of this
document or contact Powers' Technical Support Department at
1.800.669.5430 or [email protected].
Adjustment of Cold Water Bypass
■
What to look for if:
• The fl ow of water is less then desired:
1. Checkstops are not fully open
2. Clogged checkstop strainer screen
3. Accumulation of lime deposits around the valve
4. Low supply pressure or unusual supply temperature
5. Bypass valve not open. Refer to adjustment of cold water
bypass instructions
• The fl ow of water is completely shut off:
1. Checkstops are not fully open
2. Fixtures downstream of HydroGuard
®
are fully closed
3. Loss of cold water supply
• The tempered water is too cold:
1. Refer to temperature adjustment instructions
2. Make sure hot and cold water are at least 15°F (8°C) from
desired set point
3. Cold water bypass incorrectly set
Troubleshooting
■
Emergency tempering valves are control devices which must be
cleaned and maintained on a regular basis.
1. Test HydroGuard
®
system every week:
a) Open all fi xtures and verify tempered water is still at set point
b) Verify fl ow rate is adequate at fi xture
c) Shut cold water checkstop to verify that fl ow through mixing
valve shuts down immediately
e) Open cold water checkstop and shut hot water checkstop.
Verify adequate fl ow from fi xtures. If not, refer to adjustment
of cold water bypass instructions.
f) Open hot water checkstop. Verify temperature returns to set
point.
2) Before servicing checkstops or piping, turn off the water
upstream. At least every twelve (12) months open up the
checkstops and check for the free movement of the poppet.
3) Before servicing the valve, turn off the water supply upstream
or close the checkstops. To close the checkstops, turn the
adjusting screw clockwise.
4) When opening checkstops after servicing, turn adjusting screw
counterclockwise to fully open position then turn adjusting
screw 1/2 turn clockwise for fi nal setting
5) Every three (3) months, check the maximum temperature adjust-
ments.
6) Every twelve (12) months, remove the valve bonnets and check
the internal components for freedom of movement.
Preventative Maintenance
■
See TI ES150 or TI ES200/ES400
PART LIST FOR VALVE
■
USA:
Phone: 1.800.669.5430 • Fax 1. 847. 229 . 0526 • www.powerscontrols.com
Canada:
Phone: 1.888.208.8927 • Fax 1. 888. 479.2887 • www.powerscontrols.ca
IS-P-ES150-200-400XBY 0826
EDP# 6512315
© 2008 Powers
Warranty
■
The Seller warrants that the equipment manufactured by it and covered by this order or contract is free from defects in material and workmanship and, without
charge, equipment found to be defective in material or workmanship will be repaired, or at Seller’s option replaced F.O.B. original point of shipment, if written
notice of failure is received by Seller within one (1) year after date of shipment (unless specifically noted elsewhere), provided said equipment has been properly
installed, operated in accordance with the Seller’s instructions, and provided such defects are not due to abuse or decomposition by chemical or galvanic action.
THIS EXPRESS WARRANTY IS IN LIEU OF AND EXCLUDES ALL OTHER WARRANTIES, GUARANTEES, OR REPRESENTATIONS, EXPRESS OF IMPLIED. THERE ARE
NO IMPLIED WARRANTIES OF MERCHANTABILITY OR OF FITNESS FOR A PARTICULAR PURPOSE. The Seller assumes no responsibility for repairs made on the
Seller’s equipment unless done by the Seller’s authorized personnel, or by written authority from the Seller. The Seller makes no guarantee with respect to materia
not manufactured by it.
CAUTION: Any changes in supply
condition could effect the outlet water
temperature. Check and adjust the
valves accordingly to prevent injury to the users.
!