background image

The Hydroguard 400/410 pressure balancing valve insures
safety to the bather upon hot or cold water supply pressure
failure or change. The internal balance chamber forces the
hot or cold water supply pressure to be equalized should
either pressure fail or change. To ensure correct repair
parts are installed, determine valve model by referring to
bonnet label (

see Figure 1

). Once model number is deter-

mined, refer to appropriate chart to ensure correct kit has
been supplied. 

Since kits contain parts for multiple

models, discard extra parts.

Replace Balance chamber if…

• The discharge water temperature is variable or untempered.
• The valve leaks after it is completely shut off.

Balance Chamber Removal:

TO REMOVE THE BALANCE CHAMBER

, using a bal-

ance chamber extraction tool (Part No. 401-202) is highly
recommended. To use the extraction tool, follow instruc-
tions below:

a. Insert hooked ends of extraction tool into HOT and

COLD outlet ports of the balance chamber (

see Figure

2

).

b. Insert screwdriver down through end of extraction tool.

c. Place a wood or plastic block (do not use metal)

between screwdriver and valve body. Firmly ease
screwdriver away and downward, using wood for
added leverage as cartridge is gradually pulled out.

Balance Chamber Installation:

1. Apply a small amount of silicone supplied to inner surface

of valve body and inlet “O”-rings of balance chamber.

2. Align chamber and valve body inlet holes.

3. Slowly push chamber in, being very careful not to pinch

side “O”-rings (item 5A in 

figures 5 and 6

).

Replace Gasket and Disks if…

• Flow continues after mixer is turned off.
• Stem or handle is damaged.
• Water leaks at stem and/or bonnet.

Gasket and Disc Replacement:

1. Replace all gaskets and discs according to the dia-

grams as shown in 

figures 5 and 6

. Use silicone gel

provided on all “O”-rings and related surfaces. Never
use grease.

2. The number of flat washers required for installation on

stem varies with each model. Refer to 

Figure 3

when

replacing the washers.

REPAIR FORM

HydroGuard

®

400/410/2000

Pressure Balancing Valves

All Models

DESCRIPTION

REPAIR INSTRUCTIONS

HOT

COLD

5

U7

MODEL

NUMBER

DATE

CODE

5U7

MODEL

401

-000

PA

RT

NO.

POWERS

FIGURE 1: Determine Your Valve Model

Washer(s) —  Models 1-3, 5, 7, 8    1 washer
                       Models 4, 6               4 washers

Figure 3

: Number of Flat Washers to Use By Model

NOTE: Be certain to refer to Figure 5 or Figure 6 to
locate the appropriate parts and kits for your model.

Figure 2

: Balance Chamber Removal

RF 400/410/2000 

Reviews: