Scroll Medical & Laboratory Compressed Air Systems
Powerex
•
150 Production Drive
•
Harrison, OH 45030
•
USA
P 1.888.769.7979
•
F 513.367.3125
•
www.powerexinc.com
IN907800AV
•
08/2018
Page 22 of 40
Alarm Configuration
1.
Click on the Other dropdown menu and select Alarm Configuration. Click on the Configuration Mode button to edit the alarm settings.
2.
To enable an alarm, check the enable box.
3.
If an alarm is enabled, then the Low Alarm and High Alarm must be set.
4.
If the value of the point falls below the Low Alarm, the alarm is set and an email is generated if email is configured.
5. If the value of the point reaches the High Alarm, the alarm is set and an email is generated if email is configured.
6. Scroll to the bottom and Save Parameters.
7.
To save changes and force the gateway back to running mode, click on the Reboot Now button and after 5 seconds hit the Refresh button.
You should see the gateway appear in Mode: Running.