Powered Aire TFD Owner'S Manual Download Page 3

5

The  bottom  of  the  air 

curtain  should  be  flush 

with the top of the 

opening  if  possible.  If 

not and the air curtain 

has  to  be  raised,  the 

following applies: 

For 

every one inch the bot-

tom of the air curtain 

is mounted above the 

door header, the back 

side of the air curtain 

should be moved away 

from the wall 1/2 inch.

INSTALLATION

NOTE

CORRECT Installation

INCORRECT Installation

CEILING

CEILING

DOOR

HEADER

Air stream blocked 

by door header 

before it reaches 

open door.

4 in.

8 in.

Air stream has a 

clear path to the 

open doorway.

Air

Curtain

Air

Curtain

BPA and XPA Replacement Parts List available upon request

6

* REPAIRS SHOULD BE PERFORMED BY A MECHANIC / ELECTRICIAN

                           TROUBLESHOOTING 

SYMPTOMS

POSSIBLE CAUSES

CHECK/REMEDIES

NON-OPERATIONAL

Main circuit breaker or discon

-

nect is in OFF position.

Move switch to ON position 

or reset.

Loose electrical connection.

Check / tighten connection.

Fuse blown.

Replace fuse.

MINIMAL / NO AIR

Intake screen and filter clogged. Remove, clean and / or replace.

Air intake restricted.

Remove obstruction or move air 

curtain.

Fan not rotating.

Affix set screw(s) to shaft.

Air discharge inadequate.

Obstruction in discharge path 

(i.e. door headers, automatic 

door openers, etc.) Move air 

curtain.

Air discharge deflecting into 

wall.

For every 1 inch air curtain is 

mounted above the door head

-

er, air curtain should be moved 

away from the wall 

1/2 inch.

Negative air pressure.

Equalize building pressure.

Multiple motor units: (only) one 

motor not operating.

Repair or replace motor.

EXCESSIVE BLOWER NOISE/ 

VIBRATION

Blower wheel loose on motor 

shaft.

Tighten set screw(s).

Air intake vibration.

Tighten air intake screws.

Blower wheel dirty.

Remove and clean.

Damaged blower or unbalanced 

wheel.

Repair or replace.

Motor being worn.

Replace motor.

Fan hitting / rubbing fan hous

-

ing.

Motor shaft bent. Repair or 

replace. Free housing from fan’s 

path.

EXCESSIVE AIR SPILL TO OUTSIDE 

OR INSIDE

Nozzle angle too great.

Optimum angle setting is 15 

degrees towards outside.

RETURN POLICY

• 

For all warranty issues contact factory at 724-985-4183.

 All returns must be approved in advance and accompanied by an RGA number or 

   will not be accepted.

 Once units have been installed no returns will be allowed.

 Units that are returned damaged will not be accepted and full payment will be required.

• 

No returns will be allowed after 10 working days from shipment.

• 

Contact factory for Restocking Fee Schedule.

1

2

3

4

6

5

7

9

8

10

15

12

13

14

11

3

1

2

4

5

6

7

8

9

10

11

12

13

14

15

Replacement Parts 

Models: TSD and EHD

For Part Numbers Below:

Replace XXX with the Model - TSD or EHD

ITEM

DESCRIPTION

PART#

1

48” TOP / BOTTOM PANEL

2148-051

1

60” TOP / BOTTOM PANEL

2152-051

1

72” TOP / BOTTOM PANEL

2167-051

2

LEFT SIDE PANEL

2148-052L

3

RIGHT SIDE PANEL

2148-052R

4

INTERIOR SIDE PANEL

2148-057

5

48” STRUT

2148-055

5

60” STRUT

2152-055

5

72” STRUT

2167-055

6

48” PLENUM

2148-011

6

60” PLENUM

2152-011

6

72” PLENUM

2167-011

7

48” STEERING VANE ASSEMBLY

SVA-48

7

60” STEERING VANE ASSEMBLY

SVA-60

7

72” STEERING VANE ASSEMBLY

SVA-72

ITEM

DESCRIPTION

PART#

8

MOTOR / BLOWER PLATE

2148-056

9

RIGHT BLOWER WITH HOUSING

XXXBLWR-R

10

LEFT BLOWER WITH HOUSING

XXXBLWR-L

11

MOTOR, 3 H.P. (208-230/480V)    TSD

37G561-3-480

11

MOTOR,  3 H.P. (575V)                 TSD

37G561-3-575

11

MOTOR, 5 H.P. (208-230/480V)    EHD

EHD-MTR-480

11

MOTOR,  5 H.P. (575V)                 EHD

EHD-MTR-575

12

48” INTAKE SCREEN

2148-061

12

60” INTAKE SCREEN

2152-061

12

72” INTAKE SCREEN

2167-061

13

48” TOP/BOTTOM SCREEN SUPPORT 2148-064

13

60” TOP/BOTTOM SCREEN SUPPORT 2152-064

13

72” TOP/BOTTOM SCREEN SUPPORT 2167-064

14

CENTER SCREEN SUPPORT

2148-063

Summary of Contents for TFD

Page 1: ... for installation Powered Aire will not be responsible for misplaced switches If remote switches are supplied with the air curtain they are shipped inside the Control Panel enclosure Location of Remote Switches Please review the following instructions for unpacking your air curtain and pre paring it for installation 1 Remove shrink wrap and wood slats from top and sides of crate 2 The air curtain ...

Page 2: ... INTAKE SCREEN CMCL 36 SCRN 17 48 INTAKE SCREEN CMCL 48 SCRN 17 60 INTAKE SCREEN CMCL 60 SCRN 18 36 TOP BOTTOM SCREEN SUPPORT CMCL 36 TBSB 18 48 TOP BOTTOM SCREEN SUPPORT CMCL 48 TBSB Replacement Parts Model TFD 1 4 5 7 6 8 20 17 18 19 3 15 16 14 13 12 11 9 10 2 3 1 2 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 INSTALLATION OPTIONS HIGH ROLL UP DOOR VERTICAL LIFT DOOR HIGH TURN BACK TRACK DOOR LO...

Page 3: ...amaged blower or unbalanced wheel Repair or replace Motor being worn Replace motor Fan hitting rubbing fan hous ing Motor shaft bent Repair or replace Free housing from fan s path EXCESSIVE AIR SPILL TO OUTSIDE OR INSIDE Nozzle angle too great Optimum angle setting is 15 degrees towards outside RETURN POLICY For all warranty issues contact factory at 724 985 4183 All returns must be approved in ad...

Page 4: ...ate of the warranty period All warranties cover parts only If Powered Aire does not supply the controls for the air curtain the unit will not be warrantied Procedure to Receive Warranty Service Customer should take or ship prepaid the Powered Aire product requiring warranty service to Powered Aire Contact the Home Office for autho rization number Include an explanation of the defect or problem a d...

Reviews: