                                   SKP-500A/700A  SERVICE MANUAL V1.0                            

                                                                                  6 /6 

 

(5)TROUBLE SHOOTING FOT SKP-500A/700A SERIES: 

 

PROBLEM 

POSSIBLE CAUSE 

ACTION TO TAKE 

“On” switch not been push 

Push the “On” switch 

Battery voltage less than 10V 

Connect the utility power to the ups and test 

after 8hours. 

UPS not on & 

LED not light 

PCB failure 

Replace the PCB, call for service 

AC FUSE or Circuit breaker open 

Replace the AC fuse in the inlet, or re-push 

the circuit breaker. 

UPS always at 

battery mode 

Line voltage too high, too low or black 

out 

Normal condition 

Battery not fully charged 

Recharge the UPS at least 8 hours   

Battery too old 

Replace Battery, call for service 

Back up time too 

short 

PCB failure 

Replace PCB, call for service 

Buzzer continuous 

beeping 

Overload 

Remove the non-critical loads   

   