PowerBox DPC-4000 Installation And Operation Instructions Download Page 3

 

 
 
 

2.3A INSTALL OUTLET RECEPTACLE 

Install a NEMA 14-30R outlet receptacle by mounting the receptacle in the desired location and terminating conduit from the main panel to the outlet.  Connect 

wires to outlet terminals as pictured in FIGURE 3, and as per the instructions that come with the outlet.  Be sure to tightly connect the wires to the appropriate 
locations on the rear terminals of the outlet, as specified.  Once complete, refer back to 

SECTION 1.2, TEST THE CIRCUIT BEFORE CONNECTING POWERBOX

.   

 

2.3B INSTALL JUNCTION BOX

 

If installing a Powerbox hardwire model, select a standard metal junction box of sufficient size (roughly 5”x5”) where the incoming conduit will terminate and the 
panel wires will join with the wires from the Powerbox.  Mount the junction box securely to the wall.  Use Split-Bolt Connectors to join wires together, and once 
joined, wrap each connection with four turns of self-fusing amalgamating tape, followed by four turns of black electrical tape.  When connections are complete, 
secure the junction box with a cover plate.  
 

 

 
 

 
 

SOME OF THE ITEMS YOU MAY NEED: 

 

 
 
 
 
 
 
 

 
 

 
SECTION 2.4 TURN ON THE POWERRBOX 

1.  Once you have completed making the Main Connection, with the circuit breaker at the panel still in the OFF position, 
flip open the lid to the timer and make sure the recessed switch at the bottom is switched to the “OFF” position.   
2.  Turn the circuit breaker at the panel to the ON position. 
3.  Turn the recessed switch at the bottom of the timer to the “ON” position. 
4.  Proceed to SECTION 3, TIMER PROGRAMMING. 
 
 

 

   

Standard   metal   junction   box   

for   hardwire   installation.   

   

Split-­‐bolt   connector   

used   for   joining   wires   in   
hardwire   installation.   

   

Self-­‐Amalgamating   Tape   

used   to   wrap   and   insulate   
connections   made   with   

Split-­‐bolts.   

   

NEMA   14-­‐30R   wall-­‐mount   
receptacle   for   plug   &   play   

installation.

   

   

40 Amp double pole 
GFCI circuit breaker. 

   

BASIC CONNECTION FROM PANEL 

   