22
EN
Parameter 2: 002
Set shutdown voltage for programmable output.
Parameter 3: Shutdown voltage in V.
Setting range is from 11.2 to 13.6. If the battery voltage is less than the
setting point, the programmable output will be cut off. The default
value is 11.2V.
12: Hot standby function enable/disable
Interface
Setting
Parameter 2: HS.H
Enable or disable Hot standby function. You may choose following two
options in
Parameter 3
:
YES:
Hot standby function is enabled. It means that the current UPS is
set to host of the hot standby function, and it will restart after AC
recovery even without battery connected.
NO:
Hot standby function is disabled. The UPS is running at normal
mode and can’t restart without battery.
13: Battery voltage adjustment
Interface
Setting
Parameter 2:
Select “
Add
” or “
Sub
” function to adjust battery voltage
to real figure.
Parameter 3:
the voltage range is from 0V to 5.7V, the default value is
0V.
14: Charger voltage adjustment
Interface
Setting
Parameter 2:
you may choose
Add
or
Sub
to adjust charger voltage
Parameter 3:
the voltage range is from 0V to 9.9V, the default value is
0V.
NOTE:
*Before making voltage adjustment, be sure to disconnect all batteries
first to get the accurate charger voltage.
*We strongly suggest to use the default value (0). Any modification
should be suitable to battery specifications.
15: Output voltage adjustment
Interface
Setting
Parameter 2:
you may choose
Add
or
Sub
to adjust Inversor voltage
Parameter 3:
the voltage range is from 0V to 6.4V, the default value is
0V.