Pàgina 8 — Español

ASPECTOS ELÉCTRICOS

CALIBRE DEL CORDÓN DE EXTENSIÓN

Consulte el cuadro mostrado abajo para asegurarse de que el calibre de los cordones de extensión que utilice puedan con la 

carga eléctrica requerida. Los cordones de calibre insuficiente pueden causar una caída de voltaje, lo cual puede quemar el 

dispositivo y recalentar el cordón mismo.

Corriente en 

Amperios

Carga en vatios

Longitud máxima permitida del cordón

A 120 V A 240 V

Conduct. #8

Conduct. #10

Conduct. #12

Conduct. #14

Conduct. #16

2,5

 300

 600

305 m (1000 pies)

183 m (600 pies)

114 m (375 pies)

76 m (250 pies)

5

 600

1200

152 m (500 pies)

91 m (300 pies)

61 m (200 pies)

38 m (125 pies)

7,5

 900

1800

107 m (350 pies)

61 m (200 pies)

38 m (125 pies)

31 m (100 pies)

10

1200

2400

76 m (250 pies)

46 m (150 pies)

31 m (100 pies)

15 m (50 pies)

15

1800

3600

46 m (150 pies)

31 m (100 pies)

20 m (65 pies)

20

2400

4800

53 m (175 pies)

38 m (125 pies)

23 m (75 pies)

25

3000

6000

46 m (150 pies)

31 m (100 pies)

30

3600

7200

38 m (125 pies)

20 m (65 pies)

40

4800

9600

27 m (90 pies)

CARGAS DE MOTORES ELÉCTRICOS

Es característico en el funcionamiento normal de los motores eléctricos comunes consumir durante el arranque hasta seis veces 

su corriente de operación. Esta tabla puede emplearse para estimar la potencia necesaria (en vatios) para arrancar los motores 

eléctricos; no obstante, si un motor eléctrico no arranca o no alcanza la velocidad de funcionamiento, apague el dispositivo o 

herramienta de inmediato para evitar dañar el equipo. Siempre verifique los requisitos de la herramienta o aparato con la salida 

nominal del generador.

Capacidad del motor 

(H.P.)

Potencia en marcha 

(vatios)

Potencia necesaria para arrancar el motor (vatios)

Universal

Capacitor

Fase dividida

1/8

 275

N/A

 850

1200

1/6

 275

 600

 850

2050

1/4

 400

 800

1050

2400

1/3

 450

 950

1350

2700

1/2

 600

1000

1800

3600

3/4

 850

1200

2600

1

1100

N/A

3300

AVISO:

El requerimiento de voltaje y frecuencia operativa de todos los 

equipos electrónicos debe comprobarse antes de enchufarlos 

a este generador. Pueden ocurrir daños si el equipo no está 

diseñado para operar dentro de una variación de voltaje 

de +/-10% y una variación de frecuencia de +/-3 hz de los 

valores nominales que aparecen en la placa de identificación 

del generador. A fin de evitar daños, siempre tenga una carga 

adicional enchufada al generador en caso de usarse equipos 

de estado sólido (tales como un aparato de televisión). 

También podría resultar necesario un condicionador de la 

línea eléctrica para algunas aplicaciones; por ejemplo, con 

una computadora. También podria resultar necesario un 

condicionador de la línea eléctrica para algunas aplicaciones 

de equipo de estado sólido.

INTERRUPTOR DE CIRCUITO ACCIONADO 

POR FALLA DE CONEXIÓN A TIERRA

Vea la figura 1.

Los receptáculos (20 A, 120 V) del generador están protegidos 

con un interruptor de circuito accionado por falla de conexión a 

tierra (GFCI), el cual protege contra los peligros de las corrientes 

desarrolladas al presentarse tal falla. Un ejemplo de una corriente 

debida a una falla de conexión a tierra es la que fluiría a través 

de una persona que está utilizando un aparato con aislamiento 

defectuoso, y al mismo tiempo está en contacto con una tierra 

eléctrica como una parte de la plomería, suelo húmedo o tierra.

Los  receptáculos  protegidos  con  GFCIs  no  protegen  contra 

cortos circuitos, sobrecargas ni descargas eléctricas.

Los receptáculos con GFCIs pueden probarse con los botones 

TEST [PRUEBA] y RESET [REAJUSTE].

Summary of Contents for PS907500P

Page 1: ...anular lagarant a WARNING To reduce the risk of injury the user must read and understand the operator s manual before using this product ADVERTENCIA Para reducir el riesgo de lesiones el usuario debe...

Page 2: ...rilla medidora de aceite M Oil drain plug tap n de drenaje del aceite N Engine battery charge circuit fuse fusible del circuito de carga de la bater a del motor O Analog hour meter hor metro anal gico...

Page 3: ...ajustable A B B E E F C A A A Axle eje B Wheel rueda C Washer arandela D Wheel mounting hole U bracket Wheel mounting hole soporte en U E Hitch pin pasador del enganche D Fig 7 A B C A Lanyard correa...

Page 4: ...oil starter grip mango del arrancador retr ctil Fig 13 Fig 14 A Pull choke out to the start position tire del anegador a la posici n cerrado B Push choke in to the run position coloque del anegador en...

Page 5: ...B D E C Fig 18 A OFF B A A Fuel line conducto de combustible B Fuel filter filtro de combustible Fig 21 Fig 16 A Oil drain plug tap n de drenaje del aceite B Oil cap dipstick tapa de relleno de aceit...

Page 6: ...nd the nut and tighten the nut fully Connect the other end of the wire securely to a suitable ground source that is in contact with the soil for a minimum distance of 8 ft The National Electric Code c...

Page 7: ...individuals to use this unit Do not start or operate the engine in a confined space building nearopenwindows orinotherunventilatedspace where dangerous carbon monoxide fumes can collect Carbon monoxi...

Page 8: ...rom working areas to avoid noise interference Operating the generator in wet conditions could result in electrocution Keep the unit dry Keep the generator a minimum of 3 feet away from all types of co...

Page 9: ...isk of injury or damage avoid contact with any hot surface Lifting Hazard To reduce the risk of serious injury avoid attempting to lift the generator alone Ground Consult with local electrician to det...

Page 10: ...LED or SERIOUSLY HURT if you do not follow the Operator s Manual instructions Risk of fire Do not add fuel while the product is operating Generator is a potential source of electric shock Do not expos...

Page 11: ...t put any flammable or combustible materials in the direct path of the exhaust SPARK ARRESTOR Operation of this equipment may create sparks that can start fires around dry vegetation A spark arrestor...

Page 12: ...1 4 400 800 1050 2400 1 3 450 950 1350 2700 1 2 600 1000 1800 3600 3 4 850 1200 2600 1 1100 N A 3300 NOTICE Operating voltage and frequency requirement of all electronic equipment should be checked p...

Page 13: ...th nothing connected to the generator start the engine as described later in this manual 2 Plug in and turn on the first load preferably the largest load you have 3 Permit the generator output to stab...

Page 14: ...e engine is turned on and off using the fuel valve GROUND TERMINAL The ground terminal is used to assist in properly grounding thegeneratortohelpprotectagainstelectricalshock Consult with a qualified...

Page 15: ...y such alteration or modification is misuse and could result in a hazardous condition leading to possible serious personal injury WARNING Do not attempt to operate the generator until assembly is comp...

Page 16: ...n the handle and the generator frame to secure handle in place Repeat the process on the other side to lock the other handle CAUTION Do not attempt to lift the unit by the handle assembly If it is nec...

Page 17: ...This product is equipped with a spark arrestor that has been evaluated by the USDA Forest Service however product users must comply with Federal State and lo cal fire prevention regulations Check with...

Page 18: ...for five minutes before adding gas ALWAYS fill the fuel tank outdoors with the machine turned off Remove the fuel cap slowly Fill the fuel tank to 1 in below the top of the fuel neck Replace and secur...

Page 19: ...tructions can result in serious personal injury or property damage NOTICE Periodically inspect the entire product for damaged missing or loose parts such as screws nuts bolts caps etc Tighten securely...

Page 20: ...hazardous waste management guidelines in your area for the proper way to dispose of used fuel CHANGING ENGINE LUBRICANT See Figure 16 Remove the oil cap dipstick Place a container underneath the oil d...

Page 21: ...l valve to the ON position CHANGING ENGINE BATTERY CHARGE CIRCUIT FUSE See Figure 22 NOTICE Do not use a higher rated fuse other than the specified amperage This could cause damage to the product Grip...

Page 22: ...enerator is used in dusty areas When generator has exceeded the maximum figures specified in the table maintenance should still be cycled according to the intervals of time or hours stated herein STOR...

Page 23: ...line or refueled with bad gasoline Checkairfilterelement Cleanor replace as needed Drain fuel and carburetor Refuel with fresh gasoline AC receptacle does not work Circuit breaker is OFF GFCI is tripp...

Page 24: ...he Company or its authorized service representative Warranty is voided if the customer fails to install maintain and operate the product in accordance with the instruc tions and recommendations of the...

Page 25: ...Page 21 English NOTES...

Page 26: ...ierra a un ngulo de a lo sumo 45 Si aun as la jabalina se encuentra con el estrato rocoso se la puede enterrar en una trinchera de al menos 75 cm 30 pulg de profundidad En cualquier caso el extremo su...

Page 27: ...Nohagaarrancarofuncionarelmotorenunespacioconfinado de edificio cerca de ventana abiertas o en otro rea sin ventilaci n donde se puedan recolectar las emanaciones de mon xido de carbono El mon xido d...

Page 28: ...jo para evitar la interferencia del ruido Si se utiliza el generador en condiciones h medas puede causarse una electrocuci n Mantenga seca la unidad Mantenga el generador a una distancia m nima de 91...

Page 29: ...dor antes de usar este producto Alerta de condiciones h medas No exponga la unidad a la lluvia ni la use en lugares h medos Descarga el ctrica Si no se usa la unidad en condiciones secas y no se obser...

Page 30: ...s puertas y las ventanas abiertas S lo util celo AL AIRE LIBRE y lejos de ventanas puertas y respiraderos PELIGRO You WILL be KILLED or SERIOUSLY HURT if you do not follow the Operator s Manual instru...

Page 31: ...ICIE CALIENTE No toque el silenciador ni el cilindro de aluminio del motor Est n muyCALIENTESycausanquemadurasgraves Noponganing n material inflamable o combustible directamente en la trayectoria de l...

Page 32: ...rcha vatios Potencia necesaria para arrancar el motor vatios Universal Capacitor Fase dividida 1 8 275 N A 850 1200 1 6 275 600 850 2050 1 4 400 800 1050 2400 1 3 450 950 1350 2700 1 2 600 1000 1800 3...

Page 33: ...el generador Si excede la capacidad de corriente amperios y potencia vatios del generador puede da ar el generador y los dispositivos el ctricos conectados al mismo Herramienta o aparato En marcha en...

Page 34: ...para ayudar a conectar a tierra correctamente el generador como ayuda de protecci n contra descargas el ctricas Consulte con un electricista local calificado con respecto a los requisitos de conexi n...

Page 35: ...trato y puede causar una condici n peligrosa y como consecuencia posibles lesiones corporales graves ADVERTENCIA Nointenteaccionarelgeneradorantesdeterminardearmarlo De lo contrario puede ocurrir un r...

Page 36: ...introduzca el pasador a trav s del agujero en el mango y el bastidor del generador para asegurar el mango correctamente Paraasegurarlalasegundamangorepitaelprocedi miento PRECAUCI N No intente levanta...

Page 37: ...cumplir con los reglamentos de prevenci n de incendios locales estatales y federales Consulte a las autoridades que correspondan P ngase en contacto con el servicio al cliente para comprar un parachis...

Page 38: ...aire libre no fume mientras vierta la gasolina y limpie de inmediato cualquier derramamiento que ocurra Al abastecer de gasolina la generador aseg rese de que la unidad est asentada en una superficie...

Page 39: ...s lo utilice piezas de repuesto id nticas El empleo de piezas diferentes podr a causar un peligro o da ar el producto ADVERTENCIA Antes de inspeccionar limpiar o dar servicio a la m quina apague el mo...

Page 40: ...a Para angostar el espacio golpee suavemente sobre una superficie dura el electrodo de tierra Asiente en su lugar la buj a y enr squela con la mano para evitar trasroscarla Apri telaconunallaveparacom...

Page 41: ...ar Gire la v lvula de combustible hasta la posici n OFF APAGADO Quite la tuber a del combustible de ambos lados del filtro apretandolosextremosdelsujetadorderetenci nconpinzas Deslice la tuber a de co...

Page 42: ...antenimiento debe ser mayor si se el generador se usa en zonas de mucho polvo Si el generador ha sobrepasado los valores m ximos especificados en el cuadro aun debe seguirse el programa de mantenimien...

Page 43: ...enado sin tratamiento ni vaciado de gasolina o reabastecido de gasolina de mala calidad Compruebe el elemento de filtro de aire Limpie o reemplace seg n sea necesario Vac e el combustible y el carbura...

Page 44: ...Compa a o a sus representantes de servicio autorizados La garant a queda anulada si el cliente no instala mantiene o utiliza el producto respetando las instrucciones y las recomendaciones de la Compa...

Page 45: ...P gina 21 Espa ol NOTAS...

Page 46: ...P gina 22 Espa ol NOTAS...

Page 47: ...MIENTO DE LAS NORMAS DE LA FCC PARA CARGADOR DE BATER AS Este dispositivo cumple con la Parte 15 de las Reglas de la FCC Elusodependedelassiguientesdoscondiciones 1 Este dispositivo no puede causar in...

Page 48: ...personalmente Para obtener informaci n sobre el establecimiento de servicio autorizado m s cercano a usted le suplicamos llamar al 1 877 617 3501 PIEZAS DE REPUESTO El n mero de art culo de este prod...

Reviews: