Wiring

1. CONNECTING THE INVERTER AC INPUT (FIGURE 1)

The Inverter AC Input leads (designated “Input Leads”) serve as your normal power sense and charging input for the 
internal battery, therefore the 

EAC ISSM 375 SM

 requires an unswitched AC input of either 120 or 277 VAC. If a local 

switch is present on the designated emergency circuit, the 

EAC ISSM 375 SM

 input must be wired ahead of the switch.

 A. For 120V supply, connect the AC line wire to the BLACK lead coming from the inverter housing labeled INPUT  
   WIRES. 

For 277V supply, connect the AC line wire to the ORANGE lead coming from the inverter housing  

   labeled  INPUT  WIRES. 

CAUTION: Cap the unused BLACK or ORANGE input wire. Failure to do  

 

   so may result in equipment failure and void the warranty.

B. Connect the Neutral wire to the WHITE lead labeled INPUT.

C. Connect the ground wire in accordance with local and national codes. A GREEN wire is provided for this purpose.

DO NOT ENERGIZE THE CIRCUIT AT THIS TIME.

2. CONNECTING THE NORMAL AC INPUT (FIGURE 1)

The Normal AC input leads (designated “Flying Leads”) provide normal power to the designated emergency circuit. If 
the designated circuit is for Normally-Off fixtures (ie. emergency operation only - come on only during power failure), the 
Normal AC input leads are not required and should be capped separately.

 

A. NORMALLY-ON FIXTURES - Select the proper voltage “flying lead” (BLACK for 120V, ORANGE for 277V)  

 

and connect to the unswitched AC input. Cap the unused lead. Connect the Neutral (WHITE) “flying lead” to the  

 

unswitched AC input neutral of the supply line feeding the input wires. Refer to 

Figure 1.

 

B. FIXTURES ON LOCAL SWITCH (fixtures may be turned on and off locally, but will come on during power   

 

failure regardless of switch position) - Connect the load side of the switch to the proper voltage “flying lead” from  

 

(BLACK for 120V, ORANGE for 277V). Cap the unused lead. Ensure the the Inverter AC Input (“Input Leads” are  

 

connected ahead of the local switch. Refer to 

Figure 1.

INSTALLATION INSTRUCTIONS

CAUTION:   Before installing, make certain the A.C. power is off.

NOTE: The battery is shipped in separate packaging for ease of handling. Store the battery in a cool, dry and safe  

location until ready for installation. The battery may be kept in storage for up to 3 months without recharging.

CAUTION: This is a dual input and output voltage unit. It can be connected to either a 120 or 277 volt supply.  

The input and output voltages must match.

  

NOT FOR USE WITH HID LIGHTING

Mounting the 

EAC ISSM 375 SM

1) Remove the front cover of the 

EAC ISSM 375 SM

 by removing the two (2) screws located at the top of cover.

2) Knock out the keyhole slots at the rear of the unit and use for mounting the

 

EAC ISSM 375 SM

 securely to the wall. There 

is an additional round hole for a #10 screw in the cabinet. Code requires that an additional screw be used through this 
hole to prevent the unit from being inadvertently lifted up off the keyhole slots. 

Do not drill any holes in this unit. If a 

recessed junction box is to be mounted in the wall behind the unit, make sure an unswitched AC supply of proper rated 
voltage is extended to the box, and that the remote wiring to the emergency fixtures is also extended to the box prior to 
mounting the unit. A 1/2

 conduit knockout is provided in the back of the unit for wires to pass through. Sixteen inches of 

wire should be routed into the unit from the recessed junction box. NOTE: Input and output wires must be run in separate 
conduits. 

CAUTION: Do not drill holes into the cabinet; drill filings may damage the unit and keep it from operating. If larger 

knockouts are required, use a chassis-punch through the appropriate knockout to punch out a larger knockout.

3) If the wiring is to be external to the wall, extend both the unswitched supply, the normally-on lamp supply (if used), 
and the load wires to the unit at this time. 

CAUTION: The 

EAC ISSM 375 SM

 must be mounted securely. Do not rely on the junction box for supporting the 

weight of the unit. Mount the 

EAC ISSM 375 SM

 securely to the wall using the keyhole slots provided. 

ALWAYS CONSULT LOCAL CODES FOR STRUCTURAL REQUIREMENTS WHEN MOUNTING THE UNIT.

Summary of Contents for EAC ISSM 375 SM

Page 1: ... the battery part number specified for use with the EAC ISSM 375 SM Failure to do so may cause an unsafe condition will void warranty and result in non compliance with UL specifications 8 The EAC ISSM 375 SM uses a sealed valve regulated lead acid battery Batteries can be punctured if not handled properly therefore use caution when servicing batteries In the event battery acid comes in contact wit...

Page 2: ...Figure 1 INSTALLATION INSTRUCTIONS CAUTION Before installing make certain the A C power is off NOTE The battery is shipped in separate packaging for ease of handling Store the battery in a cool dry and safe location until ready for installation The battery may be kept in storage for up to 3 months without recharging CAUTION This is a dual input and output voltage unit It can be connected to either...

Page 3: ...oads Application Notes are available on the internet or through Customer Service 4 CONNECTING THE INTERNAL CIRCUIT BREAKER A Two leads are provided for connection to the internal circuit breaker Select the proper voltage lead VIOLET for 120VAC or YELLOW for 277VAC and connect it to the circuit breaker Cap the unused lead Push the circuit breaker switch to the closed position so that the indicator ...

Page 4: ... emergency fixtures will extinguish The equipment is supplied with an automatic solid state charger designed to fully recharge the battery within 72 hours after AC power is restored and then maintain the battery in a fully charged state Allow the battery to charge for a minimum of 72 hours after installation or power failure before conducting a 90 minute discharge test The Life Safety Code and the...