CF(M)-3K-12 SUPERCOMBI USER’S GUIDE
16
3.3 Cabling
No.
Cabling Position
Recommend Cable Specification
1
AC IN
Copper Cable with the cross sectional
area larger than 6mm
2
2
AC OUT1: Power
Copper Cable with the cross sectional
area larger than 6mm
2
3
AC OUT2: Short
Break
Copper Cable with the cross sectional
area larger than 6mm
2
4
Battery
Copper Cable with the cross sectional
area larger than 75mm
2
(note)
5
PV
Copper Cable with the cross sectional
area larger than 4mm
2
Table 3. Cabling Installation Instruction
Note
:
The length of the cable from the battery terminals to the SuperCombi
machine should be as short as possible. Less than 1 meter is preferred.
Warning: The consequences caused by the improper installation are not
the responsibility of our company!
Before connecting the battery, please double check the input polarity of the
battery is connected correctly. Wrong polarity connection will damage the
SuperCombi;
For safety, the grid power supply should be cut off before or during the
installation;
To avoid short circuit of the battery during the installation, the battery
should be protected and inaccessible to other appliances;
The torque of the cable should be strictly limited according to the
requirements. Excessive torque will causes the damage of the bolt and
even cause other potential dangers such as short circuit or fire etc.;
It’s very normal that there might be a spark during the first connection with
the battery;